• Total Vm
p of the string shall be within the operating voltage range of solar
battery charger (16~18V for 1000VA/1200VA model and 32~36Vfor
2000VA/2200VA model are recommended).
• Total Imp of
the string shall be less than the max. charging current of the
solar battery charger (50A for 1000VA/2000VA and 60A for
1200VA/2200VA model)
• Total Voc of the string sh
all be less than the max. PV input voltage of the
solar battery charger (55V for all model).
• Total Isc of
the string shall be less than the max. PV input current of the
solar battery charger (65A for all model).
Example 1 - How to connect 1000VA model to PV panels with the following
parameters?
• Pmax
:
150W
• Vmp
:
18V
• Voc
:
21.6V
• Imp
:
8.2A
• lsc
:
8.75A
(1) Max. charging current is 50A,
50A/8.2A = 6.09 =>max. number of PV panel in parallel is 6.
(2) Operating Voltage Range is 16T8V,
One PV panel Vmp 18V is between 16~18V => max. number of PV panel
in series is 1.
(3) Taking (1) ~ (2) into consideration, and the optimized configuration is 6
PV panels in parallel, as shown below