Setting voltage point
back to utility source
when selecting “SBU
priority” or “Solar
first” in program 01
24V model: default 23.0V, 22.0V~25.6V Settable
13
Setting voltage point
back to battery mode
when selecting “SBU
priority” or “Solar first”
in program 01
24V model: default 27.0V, 24.0V~29.0V Settable
14
Charger source priority:
To configure charger
source priority
If this off grid solar inverter is working in Line, Standby or Fault
mode, charger source can be programmed as below:
Solar first
Solar energy will charge battery as
first priority.
Utility will charge battery only when
solar energy is not available.
Utility first
Utility will charge battery as first
priority.
Solar energy will charge battery only
when utility power is not available.
Solar and Utility
Solar energy and utility will both
charge battery.
Only Solar
Solar energy will be the only charger
source no matter utility is available or
not.
If this off grid solar inverter is working in Battery mode or Power
saving mode, only solar energy can charge battery. Solar energy
will charge battery if it's available and sufficient.
15
Alarm control
Alarm on (default)
Alarm off
16
Backlight control
Backlight on (default)
Backlight off
17
Beeps while primary
source is interrupted
Alarm on (default)
Alarm off
18
Overload bypass:
When enabled, the unit
will transfer to line mode
if overload occurs in
battery mode.
Bypass disable (default)
Bypass enable