AN-ODE-2-026 Remote Keypad Control With Autorun 

 

 
 
 
 
 

 

Optidrive Applications Support Library 

Application Note  AN-ODE-2-026 
Title 

Remote Keypad Control With Autorun 

Related Products  Optidrive E2 

Level 

2

 

1 – Fundamental - No previous experience necessary 
2 – Basic – Some Basic drives knowledge recommended 
3 – Advanced – Some Basic drives knowledge required 
4 – Expert – Good experience in topic of subject matter recommended

 

Overview 

For applications that require speed control via pushbuttons, but do not require a dedicated start button, Optidrive E2 provides a 
mode of operation where the drive will automatically start as soon as the hardware enable (run switch) is closed. 

Additionally, the user can determine whether the drive restarts from 0Hz or from the previous operational speed by setting one 
of the drive parameters. 

This document describes how to use the drive digital inputs to carry out remote keypad speed control with Auto-run. 

Wiring Diagram 

 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 

Procedure  

For unidirectional operation 

 

Connect the system as showed above, leaving terminal pin 6 disconnected. 

 

Set P-12 = 1. Set P-15 = 0 (see digital input selection options in table 5.6 of the User guide). 

 

Set P-31 = 2 if the drive should always restart form 0Hz (or minimum speed limit if P-02 > 0).  Set P-31 = 3 if the drive 
should restart from the speed at which it was last running prior to the last STOP. 

 

Close the START/STOP switch to start the drive or open the switch to stop the drive. 

 

Once the drive is running, press the UP button to increase the speed or press the DOWN button to reduce the speed. 

 

START/STOP 

 

SPEED UP 

 

(NO) 

 

SPEED DOWN

 

(NO) 

 
 

FWD / REV 

Pin 1 : 24V 

 

Pin 2 : Digital input 1 

 

Pin 3 : Digital input 2 

 

Pin 4 : Digital input 3 

 

 

 

Pin 6: Bipolar analog input 

 

 

 

11-way control terminal strip 