Page 17
Drainage test
Check whether the drainpipe is unhindered.
This test should be performed on newly built
houses before the ceiling is paved.
Units with a pump.
Units without a pump.
1. Remove the test cover.
Fill the water pan with 2 liters of water.
2. Turn on the unit in COOLING mode. You will
hear the drain pump.Check whether the
water is discharged properly (a 1-minute lag
is possible, depending on the length of the
drain pipe), Check whether water leaks from
the joints.
3. Turn off the air conditioner and put the cap
back on.
3. Using a 65-mm (2.5”) core drill, drill a hole in
the wall. Make sure that the hole is drilled at
a slight downward angle, so that the outdoor
end of the hole is lower than the indoor end
by about 12mm (0.5”). This will ensure proper
water drainage (See Fig. 6.5). Place the
protective wall cuff in the hole. This protects
the edges of the hole and will help seal it
once you finish installation.
Wall
Indoor
Outdoor
≈ 12mm
/
0.5 inch
Fig. 6.5
NOTE:
When drilling the hole, make sure to
avoid wires, plumbing, and other sensitive
components.
4.
Pass the drain hose through the wall hole.
Make sure the water drains to a safe location
where it will not cause water damage or a
slipping hazard.
NOTE:
The drainpipe outlet should be at least
5cm (1.9”) above the ground. If it touches the
ground, the unit may become blocked and
malfunction. If you discharge the water directly
into a sewer, make sure that the drain has a U
or S pipe to catch odors that might otherwise
come back into the house.
Test cap
Fig.6.7
Fig.6.8
CLOSED
OP
EN
CL
OS
ED
OPEN
Stow tube
Fig.6.6
Stow tube
Fill the water pan with 2 liters of water.
Check that the drainpipe is unhindered.
Refrigerant Piping Connection
Safety Precautions
WARNING
• All field piping must be completed by a
licensed technician and must comply with
the local and national regulations.
• When the air conditioner is installed in a
small room, measures must be taken to
prevent the refrigerant concentration in
the room from exceeding the safety limit
in the event of refrigerant leakage. If the
refrigerant leaks and its concentration
exceeds its proper limit, hazards due to
lack of oxygen may result.
• When installing the refrigeration system,
ensure that air, dust, moisture or foreign
substances do not enter the refrigerant
circuit. Contamination in the system may
cause poor operating capacity, high
pressure in the refrigeration cycle,
explosion or injury.
• Ventilate the area immediately if there is
refrigerant leakage during the installation.
Leaked refrigerant gas is both toxic and
flammable. Ensure there is no refrigerant
leakage after completing the installation
work.
Notes On Pipe Length and Elevation
Ensure that the length of the refrigerant pipe, the
number of bends, and the drop height between
the indoor and outdoor units meets the
requirements shown in Table 7.1:
Table 7.1: The Maximum Length And Drop
Height Based on Models. (Unit: m/ft.)
Type of model
Capacity
(Btu/h)
Length of
piping
Maximum drop
height
North America,
Australia
and the
eu frequency
conversion Split
Type
<15K
25/82
10/32.8
≥
15K - <24K
30/98.4
20/65.6
≥
24K - <36K
50/164
25/82
≥
36K -
≤
60K 65/213
30/98.4
Other Split Type
12K
15/49
8/26
18K-24K
25/82
15/49
30K-36K
30/98.4
20/65.6
42K-60K
50/164
30/98.4
Refrigerant Piping with Twin Indoor Units
When installing multiple indoor units with a single outdoor unit, ensure that the length of the
refrigerant pipe and the drop height between the indoor and outdoor units meet the requirements
illustrated in the following diagram:
L
L1
L2
H2
The line branch pipe
Indoor unit
Outdoor unit
H1
Indoor unit
The drop height
between two
indoor units
must be less
than or equal to
50cm (19.6”)
The drop height
between indoor
unit
and outdoor unit
must be less than
or equal to 20m
(65.6’)
Fig. 7.1
7
Содержание U4MRS-12B
Страница 31: ...Page 31...
Страница 32: ...2 Indoor Unit Installation 07 1 04 08 09 13 14 14 2 05 3 07 6 15 4 07 5 12...
Страница 33: ...3 07 MC MC L N 18 20 27 28 22 23 o 25 7 18 9 27 10 29 8 20...
Страница 35: ...5 2 1 2 3 4 12 5...
Страница 36: ...6 L N 1 2 3 4 5 MC MC 6 7 3 9 27 29 22 19 15 17...
Страница 37: ...7 4 4 1 1 9 000btu h 18 000btu h 1m 3 2 1m 3 2...
Страница 41: ...11 125mm 4 92 160mm 6 3 18 60 4 1 5 6 1 2 3 1 2 3 2 3 4 11 4 12 4 15 4 16 4 13...
Страница 42: ...12 5 1 2 M10 5 1 5 2 1 1 60cm 23 6 5 1 5 2 5 3...
Страница 48: ...18 7 2 7 3 10 32 8 7 2 7 62m s 1500 fpm 6m 20ft 7 3...
Страница 53: ...23 7 10 7 11 90 3 10cm 3 9 6 7 8 9...
Страница 54: ...24 CONFIRM 3 6 ON on 4 5 1 2 FAN ONLY 2 o 3 FAN ONLY H L 4 COPY AF booster HRV 3...
Страница 57: ...27 76cmHg 9 0 1 MPa 40L min 0 1MPa 2 0 1MPa 1 2 1 2 3 4 5 15 76cmHG 1x105Pa 6 7 5 8 1 4 5 9 10 11 12 9 1 9 2...
Страница 59: ...29 1 2 3 COOL 4 d 5 6 2 000ml COOL 10...
Страница 60: ...30...
Страница 61: ...31...
Страница 91: ...Pagina 31...
Страница 92: ...Pagina 32 Scan here to download the latest version of this manual DUCT TYPE AIR CONDITIONING SYSTEMS...