- 14 - 

 

 
 
 

2.3.1. Connection of the room thermostat 

The  Controller  can  be  connected  to  a  different  type  room  thermostat,  having 

independent switch circuit closer that is switched on, when the real room temperature is lower 
than the assigned one.  In fact  the thermostats equipped with  a relay on their outputs (which 
are most of the programmable thermostats) and some of the electronics thermostats meet that 
requirement. The thermostats having a phase of their output (result of the power supply) have 
to be connected by means of a middle relay. 

There is a safety voltage of 5 V between the Controller terminals, designed for a room 

thermostat connection that allows the thermostat to be connected by a two-core regular cable 
2x0.35mm

2

.  The  cable  is  intended  to  transfer  two-digit  information  and  therefore  its  length 

has to be fixed only in relation with its resistance that can reach 100

 

The room thermostat location is something very important. It is suitable the thermostat 

to be placed at the most occupied room in the house that will become a standard for the whole 
house  (premises)  heating.  Such  areas  could  be  the  living-room  and  the  kids’  room  in  the 
family houses. The position of the room thermostat in the kitchen is not correct, because it can 
be influenced by the cooking. The location in the corridors is incorrect either, because of its 
temperature that differs from the room one. The room thermostat has to be mounted far from 
radiators (or other heating elements) and any sun shine influence. It should not be installed on 
the  outer  wall,  where  the  cooling  of  the  masonry  will  affect  to  the  results  of  the  thermostat 
operation. Sometimes the above mentioned unfavorable influences can be used to improve the 
thermostat functions, for example when a thermostat with a high hysteresis is getting closer to 
the heating elements, providing quicker reaction to the temperature variation; or a thermostat 
mounted  on  the  outer  wall  can  provide  in  time  reaction  to  the  variation  of  the  outdoor 
temperature. 

Содержание Dynamic Boiler Controller

Страница 1: ...t 00359 898 606 796 f 00359 596 325 80 info intiel com www intiel com 9 Peter Beron Str Pomorie 8000 Bulgaria 1 INTIEL THE ELECTRONICS ON YOUR SIDE Dynamic Boiler Controller User s Manual...

Страница 2: ...r which is being managed by the domestic hot water thermostat installed in the water heater or in the accumulating reservoir where also can be added a timer switch The Controller provides the heating...

Страница 3: ...tat or the sensor after the mixed valve O does not send a command for a start in a period adjusted by the customer of 12 24 36 or 48 hours after the last command is being sent 1 1 15 The main distingu...

Страница 4: ...best results can be achieved by using proportional thermostat with an integration control of the temperature The precision class of the used room thermostat directly affects to the precision in keepi...

Страница 5: ...low heating water temperature bellow 5 and fuel presence the boiler and pumps are being switched on as the valve starts opening in order to prevent freezing light indication 8 is being activated figur...

Страница 6: ...dication for return temperature water decreasing bellow the assigned value 7 Control indication showing exceeded emergency outlet boiler temperature 8 Control indication showing very low heating water...

Страница 7: ...ch the heating water temperature has a maximum value Tou min see point 1 5 5 1 With temperatures below 20 and above 120 instead of values are being indicated low and hi To enter the main menu button S...

Страница 8: ...e settings restore the default settings Test actuator it is being used for a control of correct wiring connection of the actuator Press SET button in order to make some changes By means of button it i...

Страница 9: ...oiler outlet temperature exceeds the assigned one the Controller indicator 7 Figure 3a will light the boiler will stop by force the mixed valve will be open and the circulation pumps P1 and P2 will st...

Страница 10: ...e can be constant or it can be defined in relation to the outdoor temperature Thus there is no cooling of the radiators during penetrating of a cold air through the windows towards the floor If such f...

Страница 11: ...assigned one The previous mentioned could happen if the outlet boiler temperature reaches its emergency value and the Controller has been opened the mixed valve 1 5 5 1 Selection of the lower border o...

Страница 12: ...0 2 Installation of the Controller 2 1 Introduction The installation of the Controller must be done by a qualified staff The connection of the boiler the mixed valve servo actuator and the circulation...

Страница 13: ...sor of the return boiler water V together with the sensor of the outlet water temperature K and in the same time setting up the minimal temperature of the return water at 650 C In this way the outlet...

Страница 14: ...h its resistance that can reach 100 The room thermostat location is something very important It is suitable the thermostat to be placed at the most occupied room in the house that will become a standa...

Страница 15: ...domestic hot water circuit are shown at Figure 7 a With four way mixed valve and third circulation pump for domestic hot water circuit Figure 7a b With four way mixed valve and three way magnet valve...

Страница 16: ...the domestic hot water timer is being switched on by time while the premises heating is being provided opned mixed valve so the Controller will send a signal for a complete mixed valve closing in ord...

Страница 17: ...lower than 60 the boiler fan operates constantly and it is managed by means of the room or outdoor thermostat During smooth increasing of the boiler temperature above 60 for example when the valve is...

Страница 18: ...terminals X16 This contact is being opened in case of boiler overheating If an emergency thermostat is not provided so terminals X16 are to be connected in a short circuit by means of outer electrical...

Страница 19: ...tion 6 appears and the servo actuator starts closing the boiler water flow to the heating circuit The recommended levels of the fixed return boiler water temperature are as follows Boilers with steel...

Страница 20: ...er activating the first stage the boiler would not be stopped by the working thermostat neither to be able to reach the assigned boundary level of the outlet boiler temperature That means the lowest p...

Страница 21: ...use Regarding faster actuators it is to be fixed less operation time and vice versa The default setting is 20 3 1 8 Control of the domestic hot water thermostat operation If no one of the indications...

Страница 22: ...rcuit in the sensor or temperature bellow 300 C The sensor is to be replaced The premises cannot be heated to the desired temperature Low temperature of the boiler water Increase the assignation of th...

Страница 23: ...inary adjusted with most of the room thermostats For example it can be a not freezing temperature that is adjusted to most of the room thermostats Then to go back to winter mode is enough to get back...

Страница 24: ...water tank temperature 30 80 60 Thermost at st1 Operation thermostat assignation of 1st burner stage 75 90 85 Thermost at st2 Operation thermostat assignation of 2nd burner stage 60 75 65 Outdoor temp...