MH-RC-MBS-1
User’s Manual r6.
3 EN
© Intesis Software S.L.U. - All rights reserved
This information is subject to change without notice
IntesisBox
®
is a registered trademark of Intesis Software SLU
URL
Email
Phone
http://www.intesisbox.com
[email protected]
+34 938047134
8/23
Register Address
(protocol address)
Register Address
(PLC address)
R/W Description
4
5
R/W
AC unit Temperature Setpoint
2,3,4
▪
-32768 (Initialization value)
ALL MODES (EXCEPT HEAT)
▪
18..30ºC (ºC/x10ºC)
▪
64..86ºF
HEAT
▪
16..30ºC (ºC/x10ºC)
▪
61..61ºF
5
6
R
▪
-32768 (Initialization value)
▪
10..38ºC (ºC/x10ºC)
▪
50..100ºF
6
7
R/W
Window Contact
▪
0: Closed (Default)
▪
1: Open
7
8
R/W
MH-RC-MBS-1 Disablement
5
▪
0: MH-RC-MBS-1 enabled (Default)
▪
1: MH-RC-MBS-1 disabled
8
9
R/W
▪
0: Remote Control enabled (Default)
▪
1: Remote Control disabled
9
10
R/W
AC unit Operation Time
▪
0..65535 (hours). Counts the time the AC
un
it is in “On” state.
10
11
R
AC unit Alarm Status
▪
0: No alarm condition
▪
1: Alarm condition
11
12
R
Error Code
6
▪
0: No active error
▪
65532 (-4): Initialization process (around
2min) before normal operation starts. This
error appears in case that MH-RC-MBS-1 is
set as Master.
▪
65535 (-1): Error in the communication of
MH-RC-MBS-1 or Remote Controller with the
AC unit.
▪
Any other error present, see the table at the
end of this document.
22
23
R/W
Indoor unit´s ambient temperature from
external sensor (at Modbus side)
▪
-32768: (Initialization value). No
temperature is being provided from an input
sensor. There’s no inpu
t sensor.
▪
Any other: (ºC/x10ºC/ºF)
3
Magnitude for this register can be adjusted to Celsius x 1ºC, Celsius x 10ºC (default) or Fahrenheit. See section 4.2.3 for more
information.
4
It is not possible turn to x10 the value shown in Fahrenheit.
5
This value is stored in non-volatile memory
6
See section 7 for possible error codes and their explanation
7
See section 4.2.3 for more information