background image

  

2 / 2

 

This information is subject to change without prior notice 

IntesisBox

 

is a registered trademark of Intesis Software S.L.U.

 

email: 

[email protected]

  

web: 

www.intesisbox.com 

 

phone: +34 938047134

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

 

 

 

Enclosure 

Plastic, type PC (UL 94 V-0) 
Net dimensions (d

x

w

x

h): 90x88x56 mm  

Recommended space for installation (d

x

w

x

h): 130x100x100mm 

Color: Light Grey. RAL 7035 

 

Battery 

Size: Coin 20mm x 3.2mm 
Capacity: 3V / 225mAh 
Type: Manganese Dioxide Lithium 

Mounting 

Wall. 
DIN rail EN60715 TH35. 

 

Console Port 

Mini Type-B USB 2.0 compliant 
1500VDC isolation 

Terminal Wiring 

(for power supply and 
 low-voltage signals) 

Per terminal: solid wires or stranded wires (twisted or with 
ferrule) 

1 core: 0.5mm

2

… 2.5mm

2

 

2 cores: 0.5mm

2

… 1.5mm

2

 

3 cores: not permitted 

If cables are more than 3.05 meters long, Class 2 cable is required.

 

 

USB port 

Type-A USB 2.0 compliant 
Only for USB flash storage device  

(USB pen drive) 

Power consumption limited to 150mA  

(HDD connection not allowed)

 

Power 

1 x Plug-in screw terminal block (3 poles) 

Positive, Negative, Earth 
24VDC 

 

Push Button 

Button A: Check the user manual 
Button B: Check the user manual 

Operation 
Temperature 

0°C to +60°C 

Ethernet 

1 x Ethernet 10/100 Mbps RJ45 
2 x Ethernet LED: port link and activity 

 

Operational 
Humidity 

5 to 95%, no condensation 

Port A 

1 x DALI port (Plug-in screw terminal block orange 2 poles) 

1500VDC isolation from other ports 
DALI power consumption: 240mA 
Voltage rating: 16VDC 

1 x Plug-in screw terminal block green (2 poles) 
        Reserved for future use 

 

Protection  

IP20 (IEC60529) 

LED 
Indicators 

10 x Onboard LED indicators 

2 x Run (Power)/Error  
2 x Ethernet Link/Speed 
2 x Port A TX/RX 

2 x Port B TX/RX 

1 x Button A indicator 
1 x Button B indicator 

Switch A  

(SWA)

 

1 x DIP-Switch for serial EIA485 configuration: 

Reserved for future use 

 

 

 

PORT B 

1 x Serial EIA232 (SUB-D9 male connector) 

Reserved for future use

 

1 x Serial EIA485 Plug-in screw terminal block (3 poles) 

A, B, SGND (Reference ground or shield) 
1500VDC isolation from other ports 

(except PORT B: EIA232)  

 

 

Switch B  

(SWB)

 

1 x DIP-Switch for serial EIA485 configuration: 

Position 1:  

ON:

 

120 Ω termination active 

Off:

 

120 Ω termination inactive 

Position 2-3: 

ON:

 Polarization active 

Off:

 Polarization inactive

 

 

 

 

CONNECTIONS 

ELECTRICAL & MECHANICAL FEATURES 

Power Supply 

Must use NEC Class 2 or Limited Power Source (LPS) and SELV

 

rated power supply. 

 

If using DC power supply: 

Respect polarity applied of terminals (+) and (-). Be sure the voltage applied is within the range admitted 
(check table below). The power supply can be connected to earth but only through the negative terminal, 
never through the positive terminal. 

 

If using AC power supply: 

Make sure the voltage applied is of the value admitted (24 Vac). Do not connect any of the terminals of the 
AC power supply to earth, and make sure the same power supply is not supplying any other device. 

 

Ethernet / BACnet IP (UDP) / Console (UDP & TCP) 

Connect  the  cable  coming  from  the  IP  network  to  the  connector  ETH  of  the  gateway.  Use  an  Ethernet  CAT5 
cable. If communicating through the LAN of the building, contact the network administrator and make sure traffic 
on  the  port  used  is  allowed  through all  the  LAN  path  (check  the  gateway user manual  for  more  information). 
DHCP is enabled by default. When disabled, default IP is 192.168.100.246. 
 

PortA / DALI 
Connect the DALI bus to connectors A4 (+), A3 (-) of 

gateway’s PortA. IntesisBox provides 16VDC (+/-

2%) DALI voltage to the bus. 
 
PortB / BACnet MSTP 

Connect the EIA485 bus to connectors B1 (-), B2 (+) and B3 (SNGD) of 

gateway’s PortB. Respect the polarity.  

 
Remember  the  characteristics  of  the  standard  EIA485  bus:  maximum  distance  of  1200  meters,  maximum  32 
devices connected to the bus, and in each end of the bus it must be a termination resistor of 120 Ω. The gateway 
has an internal bus biasing circuit that incorporates the termination resistor. If you install the gateway in one of 
the ends of the bus, then do not install an additional termination resistor in that end. 
 

Console Port 

Connect  a  mini-type  B  USB  cable  from  your  computer  to  the  gateway  to  allow  communication  between  the 
Configuration Software and the gateway. Remember that Ethernet connection is also allowed. Check the user 
manual for more information. 
 

USB 

Connect a USB storage device (not a HDD) if required. Check the user manual for more information. 

Power Supply 

Ethernet 
BACnet IP 

USB  
storage 

BACnet MSTP 

Console 
Port 

100 mm (h) 

100 mm (w) 

130 mm (d) 

DALI 

 

Отзывы: