4.5 Saving the configuration and sending it to IntesisBox
When the configuration is finished, click on button
Save
to save it to the project folder on
hard disk. You will be prompted to generate the configuration file to send to the gateway, if
you select
Yes
, the binary file containing the configuration for the gateway will be generated
and saved also into the project folder.
Once the configuration has been saved and the configuration file for the gateway has been
generated, to send this configuration file to the gateway, click on the button
Send File
. The
process of file transmission can be monitored in the IntesisBox Communication Console
window. If the file transmission is ok, IntesisBox will reboot automatically with the new
configuration loaded.
4.6 Signals viewer
Once the gateway is running with the correct configuration and communicating with ASCII
and BACnet systems, it is possible to view the readings of the integration signals and even
force a change in any signal value from LinkBoxBacnet. To do so, select menu View ->
Signals. The Signals Viewer window will be opened. This window shows all the active
gateway's signals with its main configuration parameters and its real time value in the
column Value.
It is possible to force a specific value to any signal for test purposes, to do so just double
click on the row and select the desired value and Accept in the Data Test window.