To configure the integration connection parameters, and the signals list, select menu
Configuration -> IntesisBox
. The
ASCII Configuration
window will be opened.
4.3 Connection configuration
Select the Connection tab to configure the connection parameters.
Two kinds of information are configured using this window, the referent to the BACnet/IP
interface, and the referent to ASCII interface.
BACnet/IP interface configuration parameters:
BACnet interface Configuration
1.
List of BACnet devices to connect to. Check the devices you want to activate. Select a
device to configure its properties.
2.
Set the total of devices to be used. You will be prompted to save the configuration first,
after you can set the amount of BACnet devices.
3.
Enter the BACnet device number.
4.
Enter the port number used by the BACnet device (by default 47808, which is BAC0).
5.
Enter the BACnet device IP address.
6.
Enter the type of reading to perform to the BACnet device: Polling (cyclic read property)
or by Subscription (COV= Change of value subscription).
7.
Enter the BACnet device name (optional, just for identification purposes).
8.
If set active, the communications between devices are performed sequential (required
for MS/TP router/devices).