www.intertec.info
Operating Instructions Filter ventilator FL-ExVENT
COM155769227Ien-4
Page 3 / 8
INTERTEC-Hess GmbH · Raffineriestr. 8 · 93333 Neustadt/Donau · Germany ·
+49 9445 9532-0 · [email protected]
1
Use
The FL-ExVENT filter fan is manufactured according to
Directive 2014/34/EU and is used for the aeration and
ventilation of housings. It consists of an encapsulated
shaded pole motor ExVENT in a stainless steel housing,
or optionally in a GFK housing, which is approved for Ex
zone 1 of equipment category G in temperature class
T4, and an outlet or intake filter.
The fans used have the EU type examination certificate
PTZ 18 ATEX 0050 X and the IECEx certificate IECEx
PTZ 18.0012X .
The motors used have the EU type examination
certificate PTB 10 ATEX 2023 and the IECEx certificate
IECEx PTB 11.0016X .
Siehe
2
Explanation of symbols for warnings
and signal words
The safety information warns the user about risks and
provide information on how risks can be avoided.
Safety information can be found at the start of the
chapter before the instructions which may lead to a
hazardous situation. Additional safety information can be
found at the beginning of this manual.
Safety instructions which must be adhered to are
highlighted as follows:
DANGER
DANGER
This sign is warning about an extremely hazardous
situation which, if not heeded, will lead to death or
serious irreversible injury.
WARNING
WARNING
This sign is warning about a hazardous situation which,
if not heeded, may lead to death or serious irreversible
injury.
CAUTION
NOTICE
This sign is warning about a hazardous situation which,
if not heeded, may lead to slight, reversible injury.
NOTICE
NOTE
It is essential to pay attention to this safety advice as you
may otherwise incur material damage.
INFO
Important notes and useful additional information.
3
Safety information
CAUTION
Risk of injury
There is a risk of injury on rotating and/or hot
components.
4
Technical Data
Rated voltage
max. 230 V AC
Permitted operating voltage
max. 250 V AC
Special voltages with corresponding power adjustment
and component selection are possible
Rated current (in
compliance with VDE 0298)
max 10 A
Rated output
25 W
Protection class
IEC EN 60529
IP55*
Storage temperature
- 60 to + 60°C
Max. permitted operating
ambient temperature
- 40 to + 55°C
Insulation class
H
Temperature class
T4
Motor
ExVENT 30xx L175 PA.
Rated speed
2500 rpm
Air delivery volume
300 cbm/h*
with filter only 150 cbm/h
Installation position
optional
Delivery direction O
blowing out
Delivery direction I
blowing in
Connecting cable
Silicon tube conductor,
resistant to notching and
oil,
3x 1.5 mm², Ø 8.4 mm