Intertec Data Systems EFD145DLFR000 Series Скачать руководство пользователя страница 18

18 

Numbers in [brackets] are for 50 Hz international systems. 

Pub. No. 18-HE122D1-1-EN

Installer’s Guide

F. AIR CLEANER OPERATION

 

s

s

CAUTION

!

 

Do NOT

 operate the air cleaner during construction  

or remodeling of a home. The air cleaner is designed 

for use in normal living conditions to capture small 

particles. The volume of dust and condensate in 

the presence of chlorides and fluorides from paint, 

varnish, stains, adhesives, cleaning compounds, 

and cement creates a corrosive condition which 

may cause rapid deterioration of the cabinet and 

internal components of the air cleaner and the air 

handler/furnace.

DISPLAY FEATURES (Figure 22)

The air cleaner display can be used for several 

functions:

•  Provide the homeowner the operating status of the 

air cleaner, including an indication the PRE-FILTER 

or COLLECTION CELLS need cleaning.

•  The installer accesses the SET-UP mode to 

change the time to clean settings for the PRE-

FILTER and COLLECTION CELLS as well as change 

the Power Level setting.

•  The unit will display fault codes for the homeowner 

indicating there is a problem with the air cleaner and 

various fault codes for the service technician to assist 

in troubleshooting the problem.

Turn the air cleaner on by pushing the POWER  button. 

The backlit POWER and Filter RESET buttons will 

illuminate along with the first Green LED 

(G1)

 indicating 

24 Volt power is present to the air cleaner.

When the indoor fan is operating the first LED 

(G1)

 

will slowly flash. This indicates the FIELD CHARGER 

and COLLECTION CELLS have power and the unit is 

operating normally. There is a 10 [12] minute time delay 

between the indoor fan starting and LED 

(G1)

 flashing.

In normal operation, the air cleaner makes a slight 

sound as the air passes through it and is cleaned.  In 

some applications, you may notice this sound coming 

from the return air vent(s). If desired, this sound level 

can be  reduced with minimal impact on air cleaning 

efficiency by reducing the power setting of the FIELD 

CHARGER in the SET-UP mode.

NOTE:  There is a 10 [12] minute delay after the 

indoor fan operates, before the air cleaner starts to 

operate, each time the power to the air cleaner is 

turned off/on. This can be bypassed by going into 

and then out of the SET-UP mode.

G. SET-UP MODE

A combination of RED, YELLOW, and GREEN LED's 

are used to indicate the following settings. See Figure 

23.

•  The three GREEN LED's are used to indicate PRE-

FILTER cleaning interval. This is measured in actual run 

time of the indoor fan. The default setting is 2 months 

[10 weeks]. See Figure 24.

•  The four YELLOW LED's indicate the COLLECTION 

CELLS cleaning interval. This is measured in actual run 

time of the indoor fan. The default setting is 6 months 

[31 weeks]. See Figure 25.

•  The three RED LED's indicate the Power Level 

setting. The default is maximum. See Figure 26.

INSTALLER SET-UP MODE

To enter the 

SET-UP

 Mode press and hold both the 

POWER and RESET buttons for a minimum of 5 [6] 

seconds. The current settings are then displayed. See 

Figure 23. If this is the desired setting or at any time you 

want to exit the SET-UP mode, press and hold BOTH 

the POWER and RESET buttons for a minimum of 5 [6] 

seconds to exit. 

To change any of the settings, press the POWER button once.

PRE-FILTER SETTING (Figure 24) 24V Mode 

Only.

One or more of the GREEN  LED’s will come on 

indicating the PRE-FILTER cleaning time setting. 

Repeatedly press the RESET button to cycle through 

the time options for the PRE-FILTER cleaning cycle until 

the desired setting is displayed.  Press the POWER 

button once to accept that setting and move to the 

COLLECTION CELL cleaning settings.

Figure 24  Green LED Pre-Filter Settings

    * Factory Setting

Figure 22  LED Display

PRE-FILTER

RESET

CLEAN

LED's

POWER

PRE-FILTER

RESET

G1

G2

G3

Y1

Y3

Y4

R1

R2

R3

Y2

CLEAN

DIRTY

G1

G2

G3

Y1

Y3

Y4

R1

R2

R3

Y2

CLEAN

DIRTY

G1

G2

G3

Y1

Y3

Y4

R1

R2

R3

Y2

CLEAN

DIRTY

One Month

[5 Weeks]

Two  Months *

[10 Weeks]

Three Months

[15 Weeks]

Figure 23 Factory Settings

G1

G2

G3

Y1

Y3

Y4

R1

R2

R3

Y2

CLEAN

DIRTY

Power Level

Collection Cell

Pre-Filter

FIELD CHARGER Power

Maximum

COLLECTION CELL

6 Months [31 weeks]

PRE-FILTER

2 Months [10 weeks]

Factory settings

Содержание EFD145DLFR000 Series

Страница 1: ...t comply with NATIONAL STATE AND LOCAL CODES IMPORTANT This Document is customer property and is to remain with this unit Please return to service information pack upon completion of work Installation...

Страница 2: ...heck carefully for any shipping damage This must be reported to and claims made against the trans portation company immediately Check to be sure all major components are in the unit Any missing parts...

Страница 3: ...air cleaner to air handler furnace or ductwork please keep screws out of the circled areas The door attaches to the slots in the location Figure 7 Avoiding Screw Interference Supply Plenum Furnace or...

Страница 4: ...ions are preferred for greatest efficiency Four inches per linear foot approximately 20 angle should be allowed space permitting 9 Seal all joints in the return air system to prevent dust from enterin...

Страница 5: ...R FIELD CHARGER and both COLLECTION CELLS Set the components aside until the cabinet is installed and the indoor unit is in place 2 Install the self adhesive gasket material on the side of the air cle...

Страница 6: ...n the side of the air cleaner cabinet flange that will mate with the indoor unit This flange has a double set of holes See Figure 14 UPFLOW AIR HANDLER APPLICATIONS ONLY 9 Position the baffle onto the...

Страница 7: ...the indoor unit is in place 2 Install the self adhesive gasket material on the side of the air cleaner cabinet flange that will mate with the indoor unit This flange has a double set of holes See Fig...

Страница 8: ...E Wiring penetration must be sealed NOTE For non Trane American Standard Heating Air Conditioning systems order a 120 VAC to 24 VAC transformer KIT BAYTRANS12024 to provide 24 volt power only to the a...

Страница 9: ...ndler Figure 20A Wiring Diagram for 24 V Mode NOTE The Black wire must be con nected to chassis ground to ensure proper operation The represents an alpha character BAYTRANS12024 Transformer BLUE GREEN...

Страница 10: ...power going into the air handler 2 On the communicating systems air handler remove the blower access panel 3 Remove the communicating control box cover 4 Locate the red jumper wire which is attached f...

Страница 11: ...ISCONNECT POWER BEFORE SERVICING COULD RESULT IN DEATH OR SERIOUS INJURY ELECTRICAL CONNECTIONS TO A STANDARD 24 VOLT AIR HANDLER Field wiring O R B YI W1 YO Y2 BK G W2 W3 In Out O R B YI W1 YO G W2 W...

Страница 12: ...wire from the air cleaner wire harness to earth ground by attaching the wire to a grounded screw that is connected to the metal air handler chassis or control plate assembly 7 The Green and White wir...

Страница 13: ...quick connect terminal to the blue wire and the green wire 9 Attach the blue wire from the air cleaner wiring harness to the open tab on the piggyback terminal supplied in the BAYACCECOMM101 Attach pi...

Страница 14: ...with the air cleaner onto the IFC platform where the 35VA transformer was previously located Use the sheet metal screws supplied with the air cleaner to mount the 50VA transformer Reconnect the 115V...

Страница 15: ...and RH together Oil burner primary TT contacts must be isolated using field supplied relay RLY00925 or equivalent NOTE 3 The black wire Bk from ACCE unit must be connected to chassis ground to ensure...

Страница 16: ...e the wiring diagrams for information on how to attach the wires in a two whole house air cleaner system The figure on the top of page 16 shows the wiring hookup for two whole house air cleaners attac...

Страница 17: ...ems 17 Installer s Guide FIELD SUPPLIED 50 VA TRANSFORMER FIELD SUPPLIED 75 VA TRANSFORMER ELECTRICAL CONNECTIONS FOR DUAL WHOLE HOUSE AIR CLEANERS AND FURNACE IN CONVENTIONAL 24V MODE ELECTRICAL CONN...

Страница 18: ...IELD CHARGER in the SET UP mode NOTE There is a 10 12 minute delay after the indoor fan operates before the air cleaner starts to operate each time the power to the air cleaner is turned off on This c...

Страница 19: ...ER is to capture large particles before they enter the COLLECTION CELLS which allows the collection cells to work more efficiently 1 Turn the air conditioning system off at the Comfort Control thermos...

Страница 20: ...a vacuum hose vacuum in even strokes across the length of the PRE FILTER After vacuuming the entire PRE FILTER using even strokes going in one direction repeat the process using even strokes going in...

Страница 21: ...R CLEANER 1 Replace the PRE FILTER into the air cleaner Ensure that the AIRFLOW indicator arrow on the PREFILTER is pointing in the same direction as the AIRFLOW indicator arrow on the air cleaner cab...

Страница 22: ...ell Identification Alternate Cleaning option for homeowners with 200 or 200 1 COLLECTION CELLS ONLY Vacuuming the PRE FILTER and COLLECTION CELLS restores them to a high efficiency However some enviro...

Страница 23: ...and hold the RESET key until the COLLECTION CELL LED turns off 1 to 2 seconds If two air cleaners are connected on the same system reset all timers on both air cleaners at the same time to the same se...

Страница 24: ...de View AIRFLOW 27 DEPTH CABINET ADD DOOR DEPTH FOR TOTAL OUTLINE DRAWING FOR UPFLOW FURNACES Dimensions all dimensions in inches I OUTLINE DRAWINGS UPFLOW FURNACE MODEL NUMBERS ifD Air Cleaner A B mu...

Страница 25: ...D DOOR DEPTH FOR TOTAL Dimensions all dimensions in inches OUTLINE DRAWING FOR DOWNFLOW FURNACES DOWNFLOW FURNACE MODEL NUMBERS ifD Air Cleaner A B multiple piece cabinet B one piece cabinet EFD17DCLF...

Страница 26: ...EPTH CABINET ADD DOOR DEPTH FOR TOTAL OUTLINE DRAWING FOR AIR HANDLERS AIR HANDLER MODEL NUMBERS ifD Air Cleaner A B multiple piece cabinet B one piece cabinet EFD175CLAH000E 17 5 14 9 15 EFD215CLAH00...

Страница 27: ...FD175DLFR000 0 05 0 08 0 12 0 17 0 22 0 28 0 34 EFD210DLFR000 0 04 0 06 0 09 0 12 0 15 0 20 0 24 0 29 0 34 EFD245DLFR000 0 03 0 04 0 06 0 09 0 12 0 15 0 19 0 22 0 26 EFD17DDLFR000 0 07 0 11 0 18 0 25...

Страница 28: ...idential applications For more information please visit www trane com or www americanstandardair com The manufacturer has a policy of continuous data improvement and it reserves the right to change de...

Отзывы: