background image

www.intertec.info

Operating Instructions CP VARITHERM DNPA HI

HOM177737483Ien-7

Page 5 / 7

INTERTEC-Hess GmbH · Raffineriestr. 8 · 93333 Neustadt/Donau · Germany · 

 +49 9445 9532-0 ·   [email protected]

For free convection, the heater needs to be installed with
ribs  standing  vertically.  The  minimum  distances  to  the
floor and to devices above it must be complied with. The
label needs to remain legible.

For  the  operation  of  the  device,  it  is  absolutely
necessary  to  connect  an  external  digital  temperature
controller  TC…  in  series  with  the  heater.  The  controller
housing may only be mounted at a place where 80°C is
not  exceeded.  See  separate  operating  instructions  for
series digital temperature controller TC.

To  ensure  operational  safety,  the  heater  must  operate
under temperature conditions which will NOT exceed the
trigger temperature of the limiter.

The operating temperatures must be adhered to.

The  connection  cable  must  be  permanently  installed  up
to  the  inlet  into  the  on-site  junction  box,  taking  the
permissible  bending  radius  =  5  x  outer  diameter  into
consideration.

Additional  installation  material,  such  as  rails  or  panels
and also junction boxes, are not included in the standard
scope of delivery (see 

Installation accessories [

}

Page 3]

)

and must be ordered additionally.

8

Connection

 WARNING

The heater is only designed for non hazardous
areas.

INTERTEC-Hess GmbH accepts no liability for improper
use.

 INFO

The device may only be connected up and secured by a
trained person, taking into account the "rated voltage"
and "rated current" specified on the nameplate.

Where  operating  voltage  =  measured  voltage  (rated
voltage),  then  the  heater  is  at  its  rated  output.  Mains
voltage fluctuations up to 10 % are then permissible.

Each  heater  with  integrated  TS  thermostat  must  be
preceded  by  a  10  A  fuse  or  a  motor  protection  switch
with short-circuit and thermal quick release (set to 10 A)
as  short-circuit  protection.  When  using  a  heater  without
integrated  thermostat,  the  fuse  protection  can  be
selected  according  to  the  cross-section  of  the  supply
cable.

In  a  TT  or  TN  system,  a  residual  current  device  (RCD)
must  be  used  where  the  measured  triggering  residual
current  does  not  exceed  100  mA.  Residual  current
devices with a measured triggering residual current of 30
mA  are  preferable.  In  an  IT  system,  an  insulation
monitoring  device  needs  to  be  used  which  switches  off
the  supply  as  soon  as  the  insulation  resistance  is  no
greater than 50 Ω per Volt of the rated voltage.

ATTENTION:
Never remove the
adapter/ cable gland!

Illustration 2: 

Example heater with KLE connection

 CAUTION

NOTICE: Do not remove adapter/ cable
connection to connect up the heater!

This would cause irreversible damage to the heater.

The illustration may deviate from the heater.

Отзывы: