4) ETS DATABASE PARAMETERS
All images described in this chapter are retained from the relevant ETS configuration pages of the ITR901-001. The device
database file is compatible with ETS4 and later versions.
4.1) Genel
If the host name is changed by a download in ETS4, a manual device restart (bus disconnection, reset of the line etc.) is
recommended to take over this change.
Fig 5 : General Page Parameters
4.1.1) Parameters List
PARAMETER
DESCRIPTION
VALUES
Host name
Field to enter the device name providing
an easy search of the device by ETS, by
Windows Network and by KNXnet/IP
visualisation systems.
30 Characters allowed
(KNX IP Router)
Slow tunnelling connections
support
Enable to support slow tunnelling
connections.
yes
no
Switch-off time for Manual
Function
After expiry of this time period the
Manual Function is switched off
automatically.
10 mins
1 hour
4 hours
8 hours
Manual Function
Configuration setting for telegram routing
when the Manual Function is active.
disabled
dass all telegrams
pass all Physical address telegrams
pass all Groups address telegrams
pass all telegrams