DEFAULT ALARM SETUP
LPG
0-100%LEL
SN:20235-1-1 ADD:4110
GAS DETECTOR
CH4
LPG
0-100%LEL
SN:20235-1-1 ADD:4110
GAS DETECTOR
H2S
LPG
0-100%LEL
SN:20235-1-1 ADD:4110
GAS DETECTOR
CH4
Fault
101
Relay
103
Relay
104
Any AL
102
Default Alarm Levels:
Flammable Gases (Default Methane)
Hydrogen Sulphide (H2S)
Carbon Monoxide (CO)
See IGD Publication OIGD193 for full details
AL1 10% LEL
AL2 20% LEL
AL1 5ppm
AL2 10ppm
AL1 20ppm
AL2 55ppm
Controller Relays
Cable 1
Cable 2
Any Alarm Level 1
Any Alarm Level 2
Any Alarm Level 3
Monitoring
Station
Fire Panel
Beacon Sounders Connected
Directly to the Controller A-V
Output Are Active on Any Alarm
When the controller is first powered the
option is displayed for 10s to run the FIND
wizard. Select by pressing the jog wheel and
the controller will find connected devices, set
up detector channels and alarms. See
controller manual for full details
Beacon Sounders Connected
Directly to Detectors activate
on any AL1 for detectors on the
same cable run.
Any fault
Relays on Detectors
Are Active on Any AL2
For detectors on the
Same Cable Run
Each Cable Run MUST Have a Unique Set
of Addresses, No Duplicates
Note Sounders Connected Directly to the
Controller Will Mute by Accepting
Alarms (Press Jog Wheel) Beacons and
Relays Remain Active Until Alarms Can
Be Reset.
32
Содержание TOC-635
Страница 4: ...SECTION 1 MOUNTING DETAILS FOR EQUIPMENT...
Страница 10: ...SECTION 2 SITING GAS DETECTORS...
Страница 17: ...SECTION 3 GENERAL CABLING PRINCIPLES CABLE TYPES AND CABLE SIZING...
Страница 24: ...SECTION 4 MAKING DEVICE CONNECTIONS TO DETECTOR NODES...
Страница 43: ...SECTION 5 Control Panel Interfaces and Connections...
Страница 67: ...Notes...