background image

Specifications are subject to change without notice.

43

441 01 6100 02

(9.) Install NOx baffles (if removed).

(10.) Reinstall burner assembly. Center burners in cell

openings.

10. Remove old sealant from cell panel and collector box

flange.

11. Spray releasing agent on the heat exchanger cell panel

where

 

collector box assembly contacts cell panel.

NOTE

:  A releasing agent such as cooking spray or equivalent

(must not contain corn or canola oil, aromatic or halogenated
hydrocarbons or inadequate seal may occur) and RTV sealant
(G.E. 162, 6702, or Dow

Corning 738) are needed before

starting installation. DO NOT substitute any other type of RTV
sealant. G.E. 162 (P771

9003) is available through RCD in 3

oz.

tubes.

12. Apply new sealant to flange of collector box and attach to

cell panel using existing screws, making sure all screws

are secure.

13. Reconnect wires to the following components. (Use con-

nection diagram on wiring label, if wires were not marked

for reconnection locations.):

a. Draft safeguard switch.

b. Inducer motor.

c. Pressure switch(es).

d. Limit over

temperature switch.

e. Gas valve.

f. Hot surface igniter.

g. Flame

sensing electrode.

h. Flame rollout switches.

i. Install NOx baffles (if removed).

14. Reinstall internal vent pipe, if applicable.
15. Reinstall vent connector on furnace vent elbow. Securely

fasten vent connector to vent elbow with 2 field

supplied,

corrosion

resistant, sheet metal screws located 180

_

 apart.

16. Replace blower access door only, if it was removed.
17.  Set thermostat above room temperature and check furnace

for proper operation.

18. Verify blower airflow and speed changes between heating

and cooling.

19. Check for gas leaks.
20. Replace outer access door.

A91252

Fig. 46 

 

Cleaning Heat Exchanger Cell

FIRE OR EXPLOSION HAZARD

Failure to follow this warning could result in personal injury,

death and/or property damage.
Never purge a gas line into a combustion chamber.  Never

test for gas leaks with an open flame.  Use a commercially

available soap solution made specifically for the detection of

leaks to check all connections.

!

WARNING

SEQUENCE OF OPERATION
NOTE

:  Furnace control must be grounded for proper operation

or control will lock out. Control is grounded through
green/yellow wire routed to gas valve and manifold bracket
screw.
Using the schematic diagram, follow the sequence of operation

through the different modes. Read and follow the wiring diagram

very carefully.

NOTE

:  If a power interruption occurs during a call for heat (W),

the control will start a 90

sec blower

only ON period two

seconds after power is restored, if the thermostat is still calling for
gas heating. The amber LED light will flash code 12 during the
90

sec period, after which the LED will be ON continuous, as

long as no faults are detected. After the 90

sec period, the furnace

will respond to the thermostat normally.
The blower door must be installed for power to be conducted

through the blower door interlock switch ILK to the furnace

control CPU, transformer TRAN, inducer motor IDM, blower

motor BLWM, hot

surface igniter HSI, and gas valve GV.

1.

Heating

 

The wall thermostat “calls for heat,” closing the R

to

W

circuit. The furnace control performs a self

check, verifies

the pressure switch contacts PRS are open, and starts the

inducer motor IDM.

a.

Inducer Prepurge Period

 As the inducer motor

IDM comes up to speed, the pressure switch contacts

PRS close, 24 VAC power is supplied for a field in-

stalled humidifier at the HUM terminal and the control

begins a 15

sec prepurge period.

b.

Igniter Warm

Up

 At the end of the prepurge period,

the Hot

Surface igniter HSI is energized for a 17

sec-

ond igniter warm

up period.

c.

Trial

for

Ignition Sequence

 When the igniter

warm

up period is completed, the main gas valve re-

lay contacts GVR close to energize the gas valve GV,

the gas valve opens, The gas valve GV permits gas

flow to the burners where it is ignited by the HSI. Five

seconds after the GVR closes, a 2

second flame prov-

ing period begins. The HSI igniter will remain ener-

gized until the flame is sensed or until the 2

second

flame proving period begins.

d.

Flame

Proving

 When the burner flame is proved at

the flame

proving sensor electrode FSE, the furnace

control CPU begins the blower

ON delay period and

continues to hold the gas valve GV open. If the burner

flame is not proved within two seconds, the control

CPU will close the gas valve GV, and the control CPU

will repeat the ignition sequence for up to three more

Trials

For

Ignition before going to Ignition

Lockout.

Lockout will be reset

 automatically after three hours

or by momentarily interrupting 115 vac power to the

furnace, or by interrupting 24 vac power at SEC1 or

SEC2 to the furnace control CPU (not at W, G, R, etc.)

If flame is proved when flame should not be present,

Содержание R8MXL

Страница 1: ...FETY CHECK 30 General 30 Start up Procedures 30 Adjustments 30 Check Safety Controls 32 Checklist 33 SERVICE AND MAINTENANCE PROCEDURES 39 Introduction 39 Electrical Controls and Wiring 39 Care and Ma...

Страница 2: ...a location and position as spe cified in the Location section of these instructions 3 Provide adequate combustion and ventilation air to the furnace space as specified in Air for Combustion and Ventil...

Страница 3: ...140 3 8 7 16 8 7 16 213 5 213 5 FRONT OF CASING FRONT OF CASING TOP OF CASING TOP OF CASING 6 1 6 1 155 7 155 7 2 1 16 2 1 16 51 6 51 6 5 1 5 1 130 5 130 5 1 7 1 7 43 5 43 5 7 8 7 8 22 2 22 2 ACCESSOR...

Страница 4: ...Specifications are subject to change without notice 4 441 01 6100 02 A10269 Fig 2 Clearances to Combustibles...

Страница 5: ...DISCHARGE ESD PRECAUTIONS PROCEDURE FURNACE RELIABILITY HAZARD Improper installation or service of furnace may cause premature furnace component failure Electrostatic discharge can affect electronic c...

Страница 6: ...XIDE POISONING HAZARD Failure to follow this warning could result in personal injury or death and unit component damage Corrosive or contaminated air may cause failure of parts containing flue gas whi...

Страница 7: ...also prevents the entrainment of drywall dust into combustion air which can cause fouling and plugging of furnace components The temperature of the return air to the furnace is maintained between 55_F...

Страница 8: ...pped with means to prevent operation of either unit unless the damper is in the full heat or full cool position AIR FOR COMBUSTION AND VENTILATION Provisions for adequate combustion ventilation and di...

Страница 9: ...IDE POISONING HAZARD Failure to follow this warning could result in death and or personal injury Many homes require air to be supplied from outdoors for furnace combustion ventilation and dilution of...

Страница 10: ...lectrical and gas lines etc Combination of Indoor and Outdoor Air 1 Indoor openings shall comply with the Indoor Combus tion Air Method below and 2 Outdoor openings shall be located as required in the...

Страница 11: ...as shown in Fig 13 NOTE It is required that the perforated supply air duct flanges be completely folded over or removed from furnace when installing the furnace on a factory supplied cased coil or co...

Страница 12: ...red 15 7 8 403 19 483 16 1 2 419 19 5 8 498 Downflow Applications on Combustible Flooring subbase required 15 1 8 384 19 483 16 3 4 425 20 5 8 600 Downflow Applications on Combustible Flooring Coil wi...

Страница 13: ...r Inlet These furnaces are shipped with bottom closure panel installed in bottom return air opening This panel MUST be in place when side return air inlet s is used without a bottom return air inlet N...

Страница 14: ...pply air outlet on furnace Bend flange inward past 90_ with wide duct pliers See Fig 14 The supply air duct must be connected to ONLY the furnace supply outlet or air conditioning coil casing when use...

Страница 15: ...IN BOTTOM A10131 Fig 16 Horizontal Suspension with Straps 30 IN 762mm MIN WORK AREA 6 MIN TYPE B VENT 17 3 4 22 SHEET METAL SEDIMENT TRAP EQUIPMENT MANUAL SHUT OFF GAS VALVE LINE CONTACT ONLY PERMISS...

Страница 16: ...shall be installed at the furnace gas control valve and extend a minimum of 2 in 51 mm outside the furnace WARNING Gas piping must be installed in accordance with national and local codes Refer to cu...

Страница 17: ...Yellow 3 1425 1380 1335 1290 1235 1185 1125 1075 1020 940 Orange 2 1260 1210 1160 1105 1050 990 935 880 820 755 Red 1 3 1095 1040 980 905 845 780 720 650 585 520 0902120 Gray 5 2180 2130 2080 2030 19...

Страница 18: ...nal plumbing and gas codes before the furnace has been connected After all connections have been made purge lines and check for leakage at furnace prior to operating furnace If pressure exceeds 0 5 ps...

Страница 19: ...change without notice 19 441 01 6100 02 A02163 Fig 20 Downflow Return Air Configurations and Restrictions A02162 Fig 21 Horizontal Return Air Configurations and Restrictions 2 51mm Street Elbow A0855...

Страница 20: ...ZARD Failure to follow this warning could result in personal injury death or property damage The cabinet MUST have an uninterrupted or unbroken ground according to current edition of NEC NFPA 70 or lo...

Страница 21: ...7 Refer to power cord manufacturer s listings 1 Remove cover from J Box 2 Route listed power cord through 7 8 in 22 mm diameter hole in J Box 3 Secure power cord to J Box bracket with a strain relief...

Страница 22: ...24 V WIRING FIELD 115 208 230 460 V WIRING FACTORY 24 V WIRING FACTORY 115 V WIRING 208 230 OR 460 V THREE PHASE 208 230 V SINGLE PHASE BLOWER DOOR SWITCH WHT BLK WHT BLK NOTES Connect Y terminal in...

Страница 23: ...proper vent sizing and installation requirements including local building codes the current edition of National Fuel Gas Code ANSI Z223 1 NFPA 54 NFGC Parts 12 and 13 the local building codes and furn...

Страница 24: ...e between the chimney and the metal liner Exterior Masonry Chimney FAN NAT Installations with Type B Double Wall Vent Connectors NFPA AGA Table 8 Combined Appliance Maximum Input Rating in Thousands o...

Страница 25: ...bris in cleanout Mortar tile metal vent fuel oil residue Is liner and top seal in good condition Is chimney property lined with clay tile liner Crown condition Missing mortar or brick Rebuild crown Ye...

Страница 26: ...ews The factory supplied vent elbow does NOT count as part of the number of vent connector elbows The vent connector can exit the furnace through one of 5 locations on the casing 1 Attach the single w...

Страница 27: ...2 Horizontal Left Vent elbow right Fig 35 132 000 5 127 7 2 NOTE All vent configurations must also meet National Fuel Gas Code venting requirements NFGC 4 in 102 mm inside casing or vent guard Includi...

Страница 28: ...Left then Up SEE NOTES 1 2 3 4 5 7 8 9 on the page following these figures A03212 Fig 32 Downflow Application Vent Elbow Up then Right SEE NOTES 1 2 4 7 8 9 on the page following these figures A03213...

Страница 29: ...and downflow installations must use Type B vent immediately after exiting the furnace except when factory authorized Downflow Vent Guard Kit is used in the downflow position See Specification Sheet fo...

Страница 30: ...alve and humidifier will not be turned on See Fig 24 ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Blower access door switch opens 115 v power to cont...

Страница 31: ...d Turn gas valve ON OFF switch to ON e Manually close blower door switch f Set thermostat to call for heat g Remove regulator seal cap and turn regulator adjusting screw counterclockwise out to decrea...

Страница 32: ...the wires normally connected to thermostat sub base terminals R and W The thermostat anticipator should NOT be in the circuit while measuring current 1 Remove thermostat from subbase or from wall 2 C...

Страница 33: ...Turn off 115 v power to furnace b Disconnect inducer motor lead wires from wire harness c Turn on 115 v power to furnace d Set thermostat to call for heat and wait 1 minute When pressure switch is fun...

Страница 34: ...116 290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 4...

Страница 35: ...Specifications are subject to change without notice 35 441 01 6100 02 Table 12 Orifice Size and Manifold Pressure In W C for Gas Input Rate A10180...

Страница 36: ...Specifications are subject to change without notice 36 441 01 6100 02 Table 12 Orifice Size and Manifold Pressure In W C for Gas Input Rate CONT A10180A...

Страница 37: ...Specifications are subject to change without notice 37 441 01 6100 02 Table 13 Orifice Size And Manifold Pressure In W C For Gas Input Rate A10181...

Страница 38: ...Specifications are subject to change without notice 38 441 01 6100 02 Table 13 Orifice Size And Manifold Pressure In W C For Gas Input Rate CONT A10181A...

Страница 39: ...itch with a suitable warning label WARNING The electrical ground and polarity for 115 v wiring must be properly maintained Refer to Fig 25 for field wiring information and to Fig 47 for furnace wiring...

Страница 40: ...ons on the label attached to the furnace WARNING CARBON MONOXIDE POISONING AND FIRE HAZARD Failure to follow this warning could result in personal injury death and or property damage Never operate uni...

Страница 41: ...a small paint or flux brush Do not remove or disturb balance weights clips on blower wheel blades 8 Vacuum any loose dust from blower housing wheel and motor 9 If a greasy residue is present on blowe...

Страница 42: ...on necting wires from switches because damage may occur a Draft safeguard switch b Inducer motor c Pressure switch es d Limit over temperature switch e Gas valve f Hot surface igniter g Flame sensing...

Страница 43: ...agram follow the sequence of operation through the different modes Read and follow the wiring diagram very carefully NOTE If a power interruption occurs during a call for heat W the control will start...

Страница 44: ...lay to 5 sec See Fig 24 3 Continuous Blower Mode When the R to G circuit is closed by the thermostat the blower motor BLWM will operate on continuous blower speed same as HEAT speed Terminal EAC 1 is...

Страница 45: ...Specifications are subject to change without notice 45 441 01 6100 02 A150040 Fig 47 Wiring Diagram...

Страница 46: ...the control will go through a brief component test sequence The inducer will start and run for the entire component test The HSI blower motor FAN speed AMBER LED boards only HEAT speed and COOL speed...

Страница 47: ...tor Inadequate combustion air supply flame rollout switch open Restricted vent Proper vent sizing Excessive wind 34 IGNITION PROVING FAILURE If flame is not sensed during the trial for ignition period...

Страница 48: ...T Two stage TYPE N Standard L Low Nox FEATURE 045 45 000 BTU hr 070 70 000 BTU hr 090 90 000 BTU hr 110 110 000 BTU hr 135 135 000 BTU hr HEAT INPUT 14 143 16 17 171 2 21 21 24 241 2 CABINET WIDTH 08...

Отзывы: