International comfort products PAN324 Скачать руководство пользователя страница 3

3

2 in. beyond the casing on all 4 sides of the unit. Do not

secure the unit to the slab

except

when required by local

codes.

OPTIONAL

RETURN

AIR

OPENING

OPTIONAL

SUPPLY

AIR

OPENING

EVAP. COIL

COND. COIL

2"

FIGURE 2

Slab Mounting Details

ADDITIONAL

GROUND

LEVEL

PLATFORM

REQUIREMENTS
The unit MUST be situated to provide safe access for

servicing.

The unit must be level and supported above grade by

beams, platform, or a pad.

Platform or pad can be of open or solid construction but

should be of permanent materials such as concrete, bricks,

blocks, steel, or pressure--treated timbers approved for

ground contact. Soil conditions must be considered so that

the platform or pad does not shift or settle and leave the unit

partially supported.

Position platform separate from building foundation.

Install in well--drained area, with top surface of platform

above grade level.

Platform must be high enough to allow for proper

condensate trap installation and drainage.

Step 3—Provide Clearances

The required minimum service clearances are shown in Fig.

3 and 4. Adequate ventilation and outdoor air must be

provided. The outdoor fan draws air through the outdoor coil

and discharges it through the top fan grille. Be sure that the

fan discharge does not recirculate to the outdoor coil. Do not

locate the unit in either a corner or under an overhead

obstruction. The minimum clearance under a partial

overhang (such as a normal house overhang) is 48 in.

(1219mm) above the unit top. The maximum horizontal

extension of a partial overhang must not exceed 48

in.(1219mm).

IMPORTANT

: Do not restrict outdoor airflow. An air

restriction at either the outdoor--air inlet or the fan discharge

may be detrimental to compressor life.
Do not place the unit where water, ice, or snow from an

overhang or roof will damage or flood the unit. Do not install

the unit on carpeting or other combustible materials.

Slab--mounted units should be at least 4 in. (102mm) above

the highest expected water and runoff levels. Do not use

unit if it has been under water.

Step 4—Field Fabricate Ductwork

Secure all ducts to roof curb and building structure on

vertical discharge units. Do not connect ductwork to unit.

For horizontal applications, unit is provided with flanges on

the horizontal openings. All ductwork should be secured to

the flanges. Insulate and weatherproof all external

ductwork, joints, and roof openings with counter flashing

and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be

insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should

be ducted through the roof deck to comply with applicable

fire codes.
A minimum clearance is not required around ductwork.

Cabinet return--air static shall not exceed --.25 in. wc.

Step 5—Rig and Place Unit

Rigging and handling of this equipment can be hazardous

for many reasons due to the installation location (roofs,

elevated structures, etc.).
Only trained, qualified crane operators and ground support

staff should handle and install this equipment.
When working with this equipment, observe precautions in

the literature, on tags, stickers, and labels attached to the

equipment, and any other safety precautions that might

apply.
Training for operators of the lifting equipment should

include, but not be limited to, the following:

1. Application of the lifter to the load, and adjustment of

the lifts to adapt to various sizes or kinds of loads.

2. Instruction in any special operation or precaution.
3. Condition of the load as it relates to operation of the

lifting kit, such as balance, temperature, etc.

Follow all applicable safety codes. Wear safety shoes and

work gloves.
INSPECTION
Prior to initial use, and at monthly intervals, all rigging

brackets and straps should be visually inspected for any

damage, evidence of wear, structural deformation, or

cracks. Particular attention should be paid to excessive

wear at hoist hooking points and load support areas.

Brackets or straps showing any kind of wear in these areas

must not be used and should be discarded.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Before installing or servicing system, always turn off

main power to system. There may be more than one

disconnect switch. Turn off accessory heater power

switch if applicable. Tag disconnect switch with a suitable

warning label.

!

WARNING

UNIT FALLING HAZARD

Failure to follow this warning could result in personal

injury or death.
Never stand beneath rigged units or lift over people.

!

WARNING

Содержание PAN324

Страница 1: ...ner Weights 7 Connect Condensate Drain 8 Install Duct Connections 8 Install Electrical Connections 9 10 PRE START UP 11 START UP 11 Check for Refrigerant Leaks 11 Start Up Adjustments 11 Wiring Diagra...

Страница 2: ...Before installing or servicing system turn off power supply to the unit and install lockout tag There may be more than one disconnect switch Turn off accessory heater power switch if applicable WARNI...

Страница 3: ...tal applications unit is provided with flanges on the horizontal openings All ductwork should be secured to the flanges Insulate and weatherproof all external ductwork joints and roof openings with co...

Страница 4: ...Failure to follow this warning could result in personal injury death or property damage Rigging bracket MUST be under the rain lip to provide adequate lifting WARNING PROPERTY DAMAGE HAZARD Failure to...

Страница 5: ...355 6 BOTTOM OF UNIT 0 50 12 7 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS...

Страница 6: ...BOTTOM OF UNIT 0 50 12 7 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS AND OT...

Страница 7: ...00 1000 1200 1400 1600 1750 FIGURE 5 Unit Corner Weight lbs and Rigging 1 2 4 3 Rigging Brackets are factory installed on 3 phase units only Single phase units require accessory kit NPLIFTBK003A10 COR...

Страница 8: ...sistant material connector between ductwork and unit discharge connection If flexible duct is used insert a sheet metal sleeve inside duct Heat resistant duct connector or sheet metal sleeve must exte...

Страница 9: ...tandards for heating and air conditioning systems Secure all ducts to building structure 7 Flash weatherproof and vibration isolate all openings in building structure in accordance with local codes an...

Страница 10: ...can Wire Gage AWG color coded insulated 35 C minimum wires to make the controlvoltage connections between the thermostat and the unit If the thermostat is located more than 100 ft 30 5 m from the unit...

Страница 11: ...and handling carefully straighten fins with a fin comb 4 Verify the following conditions a Make sure that condenser fan blade is correctly positioned in fan orifice Top 1 3 of condenser fan blade sho...

Страница 12: ...12 FIGURE 11 PAN324 60 Wiring Diagram...

Страница 13: ...C lower than required suction tube temperature NOTE If the problem causing the inaccurate readings is a refrigerant leak refer to Check for Refrigerant Leaks section INDOOR AIRFLOW AND AIRFLOW ADJUST...

Страница 14: ...l for cooling from the room thermostat Table 4 Cooling Charging Chart Table 5 PAN3 Wet Coil Pressure Drop in wc UNIT SIZE STANDARD CFM S C F M 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 17...

Страница 15: ...095 2026 1962 1887 1817 1748 1679 1583 1439 High Watts 1012 993 981 963 948 927 904 886 846 CFM 2184 2109 2036 1963 1886 1812 1729 1647 1496 Air delivery values are without air filter and are for dry...

Страница 16: ...ot to disturb balance weights clips on blower wheel vanes c Remove caked on dirt from wheel and housing with a brush Remove lint and or dirt accumulations from wheel and housing with vacuum cleaner us...

Страница 17: ...ollow this warning could result in property damage personal injury or death System under pressure Relieve pressure and recover all refrigerant before system repair or final unit disposal Use all servi...

Страница 18: ...ctive run start capacitor overload or start relay Determine cause and replace Faulty outdoor fan motor or capacitor Replace Restriction in refrigerant system Locate restriction and remove Compressor o...

Страница 19: ...R AIR FILTER IS CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE __...

Отзывы: