Table 7—

Troubleshooting Chart

SYMPTOM

CAUSE

REMEDY

Compressor and outdoor fan will not

start

Power failure

Call power company

Fuse blown or circuit breaker tripped

Replace fuse or reset circuit breaker

Defective contactor, transformer, control relay, or

high--pressure, loss--of--charge or low--pressure

switch

Replace component

Insufficient line voltage

Determine cause and correct

Incorrect or faulty wiring

Check wiring diagram and rewire correctly

Thermostat setting too low/too high

Reset thermostat setting

Compressor will not start but condenser

fan runs

Faulty wiring or circuit

Loose connections in compressor

Check wiring and repair or replace

Compressor motor burned out, seized, or

Determine cause

internal overload open

Replace compressor

Defective run capacitor, overload, or PTC (posi-

tive temperature coefficient) thermistor

Determine cause and replace

One leg of 3--phase power dead

Replace fuse or reset circuit breaker

Determine cause

Low input voltage (20 percent low)

Determine cause and correct

Compressor cycles (other than normally

satisfying) cooling/heating calls

Refrigerant overcharge or undercharge

Recover refrigerant, evacuate system, and

recharge to capacities shown on rating

plate

Defective compressor

Replace and determine cause

Insufficient line voltage

Determine cause and correct

Blocked outdoor coil

Determine cause and correct

Defective run/start capacitor, overload or start

relay

Determine cause and replace

Faulty outdoor fan motor or capacitor

Replace

Restriction in refrigerant system

Locate restriction and remove

Compressor operates continuously

Dirty air filter

Replace filter

Unit undersized for load

Decrease load or increase unit size

Thermostat temperature set too low

Reset thermostat setting

Low refrigerant charge

Locate leak, repair, and recharge

Air in system

Recover refrigerant, evacuate system, and

recharge

Outdoor coil dirty or restricted

Clean coil or remove restriction

Excessive head pressure

Dirty air filter

Replace filter

Dirty indoor or outdoor coil

Clean coil

Refrigerant overcharged

Recover excess refrigerant

Air in system

Recover refrigerant, evacuate system, and

recharge

Indoor or outdoor air restricted or air short--cycling

Determine cause and correct

Head pressure too low

Low refrigerant charge

Check for leaks, repair and recharge

Restriction in liquid tube

Remove restriction

Excessive suction pressure

High heat load

Check for source and eliminate

Reversing valve hung up or leaking internally

Replace valve

Refrigerant overcharged

Recover excess refrigerant

Suction pressure too low

Dirty air filter

Replace filter

Low refrigerant charge

Check for leaks, repair and recharge

Metering device or low side restricted

Remove source of restriction

Insufficient coil airflow

Check filter–replace if necessary

Temperature too low in conditioned area

Reset thermostat setting

Outdoor ambient below 55

°

F

Install low--ambient kit

Filter drier restricted

Replace

Содержание PAN324

Страница 1: ...ner Weights 7 Connect Condensate Drain 8 Install Duct Connections 8 Install Electrical Connections 9 10 PRE START UP 11 START UP 11 Check for Refrigerant Leaks 11 Start Up Adjustments 11 Wiring Diagra...

Страница 2: ...Before installing or servicing system turn off power supply to the unit and install lockout tag There may be more than one disconnect switch Turn off accessory heater power switch if applicable WARNI...

Страница 3: ...tal applications unit is provided with flanges on the horizontal openings All ductwork should be secured to the flanges Insulate and weatherproof all external ductwork joints and roof openings with co...

Страница 4: ...Failure to follow this warning could result in personal injury death or property damage Rigging bracket MUST be under the rain lip to provide adequate lifting WARNING PROPERTY DAMAGE HAZARD Failure to...

Страница 5: ...355 6 BOTTOM OF UNIT 0 50 12 7 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS...

Страница 6: ...BOTTOM OF UNIT 0 50 12 7 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS AND OT...

Страница 7: ...00 1000 1200 1400 1600 1750 FIGURE 5 Unit Corner Weight lbs and Rigging 1 2 4 3 Rigging Brackets are factory installed on 3 phase units only Single phase units require accessory kit NPLIFTBK003A10 COR...

Страница 8: ...sistant material connector between ductwork and unit discharge connection If flexible duct is used insert a sheet metal sleeve inside duct Heat resistant duct connector or sheet metal sleeve must exte...

Страница 9: ...tandards for heating and air conditioning systems Secure all ducts to building structure 7 Flash weatherproof and vibration isolate all openings in building structure in accordance with local codes an...

Страница 10: ...can Wire Gage AWG color coded insulated 35 C minimum wires to make the controlvoltage connections between the thermostat and the unit If the thermostat is located more than 100 ft 30 5 m from the unit...

Страница 11: ...and handling carefully straighten fins with a fin comb 4 Verify the following conditions a Make sure that condenser fan blade is correctly positioned in fan orifice Top 1 3 of condenser fan blade sho...

Страница 12: ...12 FIGURE 11 PAN324 60 Wiring Diagram...

Страница 13: ...C lower than required suction tube temperature NOTE If the problem causing the inaccurate readings is a refrigerant leak refer to Check for Refrigerant Leaks section INDOOR AIRFLOW AND AIRFLOW ADJUST...

Страница 14: ...l for cooling from the room thermostat Table 4 Cooling Charging Chart Table 5 PAN3 Wet Coil Pressure Drop in wc UNIT SIZE STANDARD CFM S C F M 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 17...

Страница 15: ...095 2026 1962 1887 1817 1748 1679 1583 1439 High Watts 1012 993 981 963 948 927 904 886 846 CFM 2184 2109 2036 1963 1886 1812 1729 1647 1496 Air delivery values are without air filter and are for dry...

Страница 16: ...ot to disturb balance weights clips on blower wheel vanes c Remove caked on dirt from wheel and housing with a brush Remove lint and or dirt accumulations from wheel and housing with vacuum cleaner us...

Страница 17: ...ollow this warning could result in property damage personal injury or death System under pressure Relieve pressure and recover all refrigerant before system repair or final unit disposal Use all servi...

Страница 18: ...ctive run start capacitor overload or start relay Determine cause and replace Faulty outdoor fan motor or capacitor Replace Restriction in refrigerant system Locate restriction and remove Compressor o...

Страница 19: ...R AIR FILTER IS CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE __...

Отзывы: