background image

15

441 01 5003 01

Specifications are subject to change without notice

8. Gas Supply and Piping

CARBON MONOXIDE POISONING, FIRE AND

EXPLOSION HAZARD.
Failure to follow this warning could result in

personal injury, death, and/or property damage.
Models designated for Natural Gas are to be used

with Natural Gas ONLY, unless properly converted to

use with Propane gas.

!

Gas Supply Requirements

Use only the Type of gas approved for this furnace. See rating

plate for approved gas type.

Gas input must not exceed the rated input shown on the rating

plate. Overfiring will result in failure of heat exchanger and

cause dangerous operation.

Do

NOT

allow minimum supply pressure to vary downward.

Doing so will decrease input to furnace. Refer to

Table 3

for

gas supply. Refer to

Table 7

or

Table 8

for manifold pressures.

Table 3

Gas Pressures

Gas Type

Supply Pressure in wc

Recommended

Max.

Min.

Natural

7

14

4.5

Propane

11

14

11

Natural to Propane Gas Conversion

Note: An accessory kit shall be used to convert to propane gas use,

see the furnace rating plate for the Propane conversion accessory

kit part number.

1. After disconnecting power and gas supply to the furnace,

remove the access door, exposing gas valve and burner

compartment.

2. Disconnect gas line from gas valve so manifold assembly

can be removed.

3. Disconnect wiring at gas valve. Be sure to note the proper

location of any and all electrical wiring disconnected.

4. Remove the four (4) screws holding the manifold and gas

valve to the manifold supports. Do Not discard any screws.

5. Carefully remove the manifold assembly.
6. Remove the Natural gas (brass) burner orifices from the

manifold assembly and replace them with the appropriate

Propane (silver) orifices furnished in the conversion kit

unless converting high altitude unit, then see

Table 6

or

Table 8

for appropriate orifices. (

Figure 10

)

Figure 10

Remove Orifices

25--21--00

7.

T

ighten the orifices so they are seated and gas tight about 1

1

/

8

from the face of the orifice to the back of the manifold

pipe (

Figure 11

). Make sure orifice is installed straight so that

it forms a right angle (90

°

) to the manifold.

Figure 11

Changing Orifices

Measure from face of orifice to

the back side of the manifold.

1.11

(28.2mm)

1.21

(30.8mm)

8. Remove the cap screw and pressure regulator adjusting

screw from valve. (see

Figure 12

)

9. Remove the existing regulator spring from the regulator

housing.

10. Insert the replacement spring (red color) contained in this kit

into regulator housing.

11. Install the pressure regulator adjusting screw and give it

eleven (11) full clockwise turns. This will set the manifold

pressure close to required setting for normal operation.

12. Replace the regulator cap screw.

13. Attach the Yellow Attention Label contained in the kit to the

Gas Valve where it can be readily seen.

Color Code For

Propane

Gas

Natural Gas

Pressure
Regulator
Adjusting Screw

Black

Black

Spring

Red

Stainless

Steel

Note: A low gas pressure switch is required for conversion.

Figure 12

Typical Regulator Assembly

Содержание H8UH5050B12C2

Страница 1: ...fy unsafe practices that may result in minor personal injury or product and property damage Note is used to highlight suggestions that will result in enhanced installation reliability or operation Ins...

Страница 2: ...setting ____ Fan Time OFF Setting ___ Manual Gas Shut Off Upstream of Furnace Drip Leg Gas Valve turned ON Type of Gas Natural Propane Filter Type and Size Calculated Firing Rate See Checks and Adjus...

Страница 3: ...air shall also be handled by a duct s sealed to the furnace casing and terminating outside the space containing the furnace A gas fired furnace for installation in a residential garage must be instal...

Страница 4: ...ne fluorine or any other damaging chemicals which could harm the furnace and vent system and permit spillage of combustion products into an occupied space Refer to Combustion Ventilation Air section C...

Страница 5: ...16 49 183 4 476 J Installation Positions This furnace can be installed in an upflow horizontal either left or right airflow position DO NOT install this furnace on its back For the upflow position the...

Страница 6: ...e with sheet metal screws and to the rafters or joists with bolts The preferred method is to use an angle iron frame bolted to the rafters or joists If the furnace is to be installed at ground level i...

Страница 7: ...installation is complete check that all appliances have adequate combustion air and are venting properly See Venting And Combustion Air Check in Gas Vent Installation Section in this manual Contamina...

Страница 8: ...ow and b Outdoor openings located as required in the Outdoor Combustion Air Method above and c Outdoor openings sized as follows 1 Calculate the Ratio of all Indoor Space volume divided by required vo...

Страница 9: ...lowing equations from the National Fuel Gas Code ANSI Z223 1 NFPA 54 2006 9 3 2 2 1 For other than fan assisted appliances such as a draft hood equipped water heater 1000 Btu hr 21 ft3 I other Volume...

Страница 10: ...ry built chimney or vent complying with a recognized standard or a masonry or concrete chimney lined with a lining material acceptable to the authority having jurisdiction Venting into an unlined maso...

Страница 11: ...permitted as outlined in the NFGC venting tables Follow all safe venting requirements Note See section Masonry Chimney Venting 6 Horizontal Venting Category I Furnaces With External Power Venters In...

Страница 12: ...w vent terminal of the furnace to a dryer or water heater vent or other appliance s direct vent intake or exhaust N Clearance from a plumbing vent stack 3 91 cm 3 91 cm O Clearance above a paved sidew...

Страница 13: ...formation on condensate drains b Indicates the chimney exceeds the maximum permissible size in the tables the chimney should be rebuilt or relined to conform to the requirements of the appliances bein...

Страница 14: ...anufacturer s installation instructions CHIMNEY INSPECTION CHART For additional requirements refer to the National Fuel Gas Code NFPA 54 ANSI Z223 1 2006 and ANSI NFPA 211 2006 Chimneys Fire places Ve...

Страница 15: ...ring disconnected 4 Remove the four 4 screws holding the manifold and gas valve to the manifold supports Do Not discard any screws 5 Carefully remove the manifold assembly 6 Remove the Natural gas bra...

Страница 16: ...ing and Adding Propane Low Pressure Switch Propane Low Pressure Switch Detail Alterative installation Figure 13 Right pipe entry O N O F F 25 25 51 Left Hand gas pipe entry detail 25 25 53 Drip Leg Un...

Страница 17: ...may vary in appearance 4 Gas supply line then can be run directly into opening of elbow Piping with Close Nipples and Standard Elbows 1 Assemble elbows and nipples similar to street elbows shown in Fi...

Страница 18: ...pacity can be determined by using the NEC or CEC Furnace must be installed so the electrical components are protected from water and connected to its own separate circuit Junction Box J Box Relocation...

Страница 19: ...arning could result in personal injury or death Do NOT draw return air from inside a closet or utility room where furnace is located Return air duct MUST be sealed to furnace casing FIRE HAZARD Failur...

Страница 20: ...ening shall be accessible when the furnace is installed and shall be of such a size that the heat exchanger can be viewed for possible openings using light assistance or a probe can be inserted for sa...

Страница 21: ...cated from sheet metal Figure 24 Insert filter into side clips first and push filter back until it is fully engaged into back clip Figure 23 Bottom Mounted Filter 25 24 18 1 9 23 cm Center clip side t...

Страница 22: ...his furnace it must be installed on the discharge side of the furnace to avoid condensation in the heat exchanger All furnaces are designed with a break away duct flange on the supply air side of the...

Страница 23: ...ain burner orifices Refer to Table 5 Table 6 Table 7 or Table 8 for correct orifice size and manifold pressure for a given heating value and specific gravity for natural and propane gas Operation Abov...

Страница 24: ...ATION FEET ABOVE SEA LEVEL 0 to 2000 2001 to 3000 3001 to 4000 4001 to 5000 5001 to 6000 6001 to 7000 7001 to 8000 2500 10 0 10 0 9 0 10 0 9 4 8 5 10 0 Orifice Size 54 54 54 55 55 55 56 Conversion 1 i...

Страница 25: ...nt door exposing the burner compartment 2 Disconnect gas line from gas valve so manifold can be removed 3 Disconnect wiring at gas valve Be sure to note the proper location of all electrical wiring be...

Страница 26: ...eed Chart Wire Color Motor Speed Black High Orange Med High Blue Med Low Red Low Med High speed may not be provided on all models 2 Change the heat or cool blower motor speed by removing the motor spe...

Страница 27: ...s warning could result in personal injury death and or property damage It is recommended that the furnace be inspected and serviced on an annual basis before the heating season by a qualified service...

Страница 28: ...s from furnace control Fan demands from furnace control for heat cool or G will override hard wired speed tap NOTE 3 EAC is NOT active for hard wired mode but IS active for fan demands from furnace co...

Страница 29: ...32 OFF 24VAC or 220VAC is off fuse is open Heartbeat Normal operation or no previous Diagnostic Code ON SOLID Soft Lockout Furnace Control Error 1 hr delay If code repeats immediately following power...

Страница 30: ...2 H8UH5100F14C2 H8UH5125J20C2 H8UH5140J20C2 MUF050W3C2 MUF075W3C2 MUF100W3C2 MUF125W5C2 MUF140W5C2 HL12H3TRC2 HL18H3TRC2 HL25H3TRC2 HL31H4TRC2 HL34H5TRC2 Save This Manual For Future Reference Internat...

Страница 31: ...e Series Hot Surface Combustion Flue Outlet Size Inches 4 4 4 4 4 Limits Controls Thermal Sensor F Limit Control 300 See Parts List 300 See Parts List 300 See Parts List 300 See Parts List 300 See Par...

Страница 32: ...7 587 224 1 236 293 392 552 249 0 204 266 362 523 NOTE 1 Data based on Bottom Only return 2 Data based on Both Sides or Bottom Plus One Side 3 Reduce Airflow by 5 if Bottom ONLY return 4 Gray area is...

Страница 33: ...Bottom Only return 2 Data based on Both Sides or Bottom Plus One Side 3 Reduce Airflow by 5 if Bottom ONLY return 4 Gray area is above maximum temperature rise range Filter Size CFM L S 14 X 25 1400...

Страница 34: ...34 441 01 5003 01 Specifications are subject to change without notice Wiring Diagram H8UH5 MUF HL...

Страница 35: ...to change without notice Parts for H8UH5 MUF HL 25 23 49a 1 S 14 15 W 10 U V 16 L 16 17 N 5 4 3 9 B C A 2 1 BB AA 18 Y X CC M D T S P Z F E G F U 12 11 7 D GG FF EE HH 8 7 J 13 19 Representative draw...

Страница 36: ...8 Furnace Control 1172550 1 1 1 1 1 9 Switch Interlock 1171981 1 1 1 1 1 10 Burner Assembly 1172884 1172965 1172966 1172967 1172968 1 1 1 1 1 11 Flame Sensor 1172827 1 1 1 1 1 12 Ignitor 1172533 1 1 1...

Страница 37: ...Cover Junction box 1012350 1 1 1 1 1 D Partition Blower 1014009 1014010 1014011 1014013 1 1 1 1 1 E Housing Blower 1172885 1172969 1172970 1 1 1 1 1 F Hanger Blower 1012328 2 2 2 2 2 G Panel Blower C...

Страница 38: ...0 1 1 1 1 1 Z Gasket Combustion Blower 1014385 1 1 1 1 1 AA Partition Front Ht Exchanger 1013543 1013521 1013546 1013548 1013549 1 1 1 1 1 BB Gaskets Heat Exchanger 1013991 1013992 1013993 1013994 101...

Отзывы: