440 04 2024 01

Specifications are subject to change without notice.

Circulation Air Blower Data - *9MPV050

Cooling Adjustment

Heating Rise Adjustment

DIP Switch

(OFF = 0 and

ON = 1)

High Cool @ .50

in wc(125 Pa)

Low Cool (80%

of High Cool)

** Adjust

Jumper

Setting

DIP Switch

(OFF = 0 and

ON = 1)

High Heat

Rise

Change @

0.20 in wc

(50 Pa)

Low Heat

Rise

Change at

Resultant

Static

5 & 6

CFM

L/s

CFM

L/s

3 & 4

00

1246

588

997

471

+

00

--4

--3

*00

1211

571

969

457

*NOM

*00

0

0

00

1122

529

898

424

--

00

5

5

01

1105

521

884

417

+

01

3

4

01

1027

485

822

388

NOM

01

7

7

01

945

446

756

357

--

01

13

14

10

892

421

714

337

+

10

--1

0

10

820

387

656

310

NOM

10

4

5

10

745

352

596

281

--

10

9

9

11

688

325

550

260

+

11

--15

--15

11

609

287

487

230

NOM

11

--13

--12

11

541

255

433

204

--

11

--9

--9

Airflow performance includes 1” washable filter media.
*Factory Setting
**Adjust Jumper Setting (+, NOM, --) is applied to both Cooling and Heating
Note 1: HP Mode Jumper provides a 10% reduction in airflow when in Comfort position and a call for low or high cooling is

present with the ”O” line off. This feature is to provide lower airflow for running in HP Heating Mode if desirable.
Note 2: DEHUM mode (24VAC on DEHUM terminal) provides a 20% airflow reduction during cooling calls.
Note 3: Low Heat ESP is a result of High Heat ESP (-- is decrease in rise).
Note 4: High and low heat rise values are approximate air temperature change from return air temperature when at factory

default settings.

Table 2

Airflow

DIP Switch

(OFF = 0 and ON = 1)

Continuous Fan @

0.10 in wc (25 Pa) ESP

1 & 2

CFM

L/s

*00

592

279

01

1021

482

10

1346

635

11

1346

635

* Factory Setting

Table 3

SW2 DIP Assignments

DIP Switch

Blower Parameter

1 & 2

Cont Fan Adj

3 & 4

Heat Speed Adj

5 & 6

Cool Speed Adj

7 & 8

Cool On/Off Delay

Table 4

Cooling Delay Options (SW2 -- 7, 8)

ON DELAY

OFF DELAY

DIP SW2 -- 7/8

(OFF = 0 and ON = 1)

Timed ON (sec)

Airflow during on

delay

Timer OFF (sec)

Airflow during off

delay

*00

5

OFF

90

100%

01

5

OFF

0

OFF

10

30

50%

30

100%

11

30

50%

180

50%

Airflow % is of High Cool airflow demand determined from SW2--5/6 Table 1
Airflow resumes to 100% after on delay time is completed
Airflow stops (or switches to continuous fan speed) after off delay time is completed
* Factory Setting

MAX CFM (L/s) for Factory Washable Filters

Filter Size (in/mm)

CFM

L/s

14

X 25

(356 x 635)

1400

661

16

X 25

(406 x 635)

1600

755

20

X 25

(508 x 635)

2000

944

24

X 25

(610 x 635)

2500

1180

Max CFM (L/s) based on 600 FPM (3.0 m/s)

NOTE: Disposable filters are typically rated at 300 FPM (1.5 m/s).

These filters only allow half the airflow when compared to 600 FPM

(3.0 m/s) filters.

Содержание *9MPT050F12C1

Страница 1: ...ave This Manual For Future Reference Four Position Furnace International Comfort Products LLC Lewisburg TN 37091 U S A Technical Support 9MPT 2 Circulation Air Blower Data 9MPT 3 Wiring Diagram 9MPT 4...

Страница 2: ...7 1 30 2 30 324 573 1 20 1 90 299 473 1 00 1 80 249 448 1 80 2 60 448 647 1 30 2 30 324 573 1 20 1 90 299 473 1 00 1 80 249 448 1 80 2 60 448 647 1 70 2 50 423 623 1 20 1 90 299 473 1 00 1 80 249 448...

Страница 3: ...84 0 3 75 653 308 951 449 1365 644 1601 756 0 4 100 631 298 921 435 1309 3118 1530 722 0 5 125 609 287 891 420 1252 591 1460 689 0 6 150 569 268 845 399 1187 560 1380 651 0 7 175 529 250 799 377 1122...

Страница 4: ...4 440 04 2024 01 Specifications are subject to change without notice Wiring Diagram 9MPT Two Stage Heating with PSC Motor...

Страница 5: ...ce 9MPT Parts 25 24 75a 4 YY WW N LL 11 18 V W R S T U J L JJ Q P Y X F UU VV TT SS H RR QQ KK 5 4 3 9 10 M K 2 1 B A 7 D K 6 HH 8 ZZ 13 15 FF EE 16 BB 12 16 GG 17 DD CC FF 14 O N O F F OO 20 NN PP MM...

Страница 6: ...on motor Bellyband Location on Motor A Dimensions Model 9MPT inches mm 050F12 2 09 53 1 075F14 1 81 46 100J16 1 81 46 125L20 1 65 41 9 Key No Description Non Functional Part Number 9MPT 050 F12 075 F...

Страница 7: ...ox 5 8 ID 1172245 1 1 1 1 UU Tube Drain Tee 1 2 ID 1171989 1 1 1 1 VV Tube Relief 1172012 1 1 1 1 WW Drain Vent 1014003 1 1 1 1 XX Clip Retainer 1175788 1 1 1 1 YY Tee Drain 1171915 1 1 1 1 ZZ Sightgl...

Страница 8: ...5 No Elbows 40 5 90 DWV Elbows 1 80 2 60 448 647 1 30 2 30 324 573 1 20 1 90 299 473 1 00 1 80 249 448 1 80 2 60 448 647 1 30 2 30 324 573 1 20 1 90 299 473 1 00 1 80 249 448 1 80 2 60 448 647 1 70 2...

Страница 9: ...airflow reduction during cooling calls Note 3 Low Heat ESP is a result of High Heat ESP is decrease in rise Note 4 High and low heat rise values are approximate air temperature change from return air...

Страница 10: ...1600 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 ESP in w c CFM 00 00 NOM 00 01 01 NOM 01 10 10 NOM 10 11 11 NOM 11 Legend Airflow Selection is from Highest to Lowest Low Cooling Airflows 9MPV050F12 0 200...

Страница 11: ...irflow reduction during cooling calls Note 3 Low Heat ESP is a result of High Heat ESP is decrease in rise Note 4 High and low heat rise values are approximate air temperature change from return air t...

Страница 12: ...1800 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 ESP in w c CFM 00 00 NOM 01 00 01 NOM 10 01 10 NOM 11 10 11 NOM 11 Legend Airflow Selection is from Highest to Lowest Low Cooling Airflows 9MPV075F12 0 200...

Страница 13: ...20 airflow reduction during cooling calls Note 3 Low Heat ESP is a result of High Heat ESP is decrease in rise Note 4 High and low heat rise values are approximate air temperature change from return...

Страница 14: ...0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 ESP in w c CFM 00 00 NOM 00 01 01 NOM 01 10 10 NOM 10 11 11 NOM 11 Legend Airflow Selection is from Highest to Lowest Low Cooling Airflows 9MPV100J20 0 200 400 600 800 1...

Страница 15: ...20 airflow reduction during cooling calls Note 3 Low Heat ESP is a result of High Heat ESP is decrease in rise Note 4 High and low heat rise values are approximate air temperature change from return a...

Страница 16: ...0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 ESP in w c CFM 00 00 NOM 00 01 01 NOM 01 10 10 NOM 10 11 11 NOM 11 Legend Airflow Selection is from Highest to Lowest Low Cooling Airflows 9MPV125L20 0 200 400 600 800 1...

Страница 17: ...YY WW N LL 11 18 R S T U J L JJ Q P Y X F UU VV TT SS H RR QQ KK 5 9 10 M K 2 B A 8 6 HH K 23 OO 20 MM PP NN ZZ 22 4 3 15 BB 12 21 Representative drawing only some models may vary in appearance 2 CEL...

Страница 18: ...le Spd 1174887 1174888 1174889 1174895 1 1 1 1 23 Choke Power 1172838 1 1 See Table below for bellyband location on motor Bellyband Location on Motor A Dimensions Model 9MPV inches mm 040F12 13 8 34 9...

Страница 19: ...Tube Drain Coll Box 5 8 ID 1172245 1 1 1 1 UU Tube Drain Tee 1 2 ID 1171989 1 1 1 1 VV Tube Relief 1172012 1 1 1 1 WW Drain Vent 1014003 1 1 1 1 XX Clip Retainer 1175788 1 1 1 1 YY Tee Drain 1171915 1...

Страница 20: ...Std Pressures in wc Pa 54 No Elbows 404 5 905 DWV Elbows 2 10 3 47 523 864 3 38 1 90 842 473 1 38 2 29 344 570 2 21 1 22 550 304 2 26 3 52 563 877 2 77 1 52 690 378 1 50 2 35 374 585 2 06 1 16 513 28...

Страница 21: ...airflow reduction during cooling calls Note 3 Low Heat ESP is a result of High Heat ESP is decrease in rise Note 4 High and low heat rise values are approximate air temperature change from return air...

Страница 22: ...Airflow 0 200 400 600 800 1000 1200 1400 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 ESP inches of wc CFM 00 00 NOM 00 01 01 NOM 01 10 10 NOM 10 11 11 NOM 11 9MVX040F12 Low Cool Airflow 0 200 400 600...

Страница 23: ...low reduction during cooling calls Note 3 Low Heat ESP is a result of High Heat ESP is decrease in rise Note 4 High and low heat rise values are approximate air temperature change from return air temp...

Страница 24: ...l Airflow chart 0 200 400 600 800 1000 1200 1400 1600 1800 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 ESP inches of wc CFM 00 00NOM 00 01 01NOM 01 10 10NOM 10 11 11NOM 11 9MVX060F12 LowCoolAirflowchart 0...

Страница 25: ...20 airflow reduction during cooling calls Note 3 Low Heat ESP is a result of High Heat ESP is decrease in rise Note 4 High and low heat rise values are approximate air temperature change from return...

Страница 26: ...ows 0 400 800 1200 1600 2000 2400 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 ESP inches of wc CFM 00 00 NOM 00 01 01 NOM 01 10 10 NOM 10 11 11 NOM 11 9MVX080J20 LowCoolAirflow 0 200 400 600 800 1000...

Страница 27: ...airflow reduction during cooling calls Note 3 Low Heat ESP is a result of High Heat ESP is decrease in rise Note 4 High and low heat rise values are approximate air temperature change from return air...

Страница 28: ...ngAirflows 200 600 1000 1400 1800 2200 2600 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 ESP inchesof wc CFM 00 00 NOM 00 01 01 NOM 01 10 10 NOM 10 11 11 NOM 11 9MVX100L20 Low Cool Airflow 0 200 400 60...

Страница 29: ...RANS RED HP MODE AC HP EFFICIENCY HP COMFORT J2 NOM BLOWER ADJUST J1 Y1 O AC HP EFFICIENCY HP COMFORT J2 NOM J1 1 2 3 4 6 5 7 8 SELECT SELECTION BLOWER ADJUST INCREASE NO CHANGE DECREASE HP MODE SELEC...

Страница 30: ...4889 1174895 1 1 1 1 23 Choke Power 1172838 1 1 24 Baffle Flue 1177823 1 24 Baffle Right 1177824 1 1 1 25 Baffle Left 1177825 1 1 1 See Table below for bellyband location on motor Bellyband Location o...

Страница 31: ...cket 1171987 1 1 1 1 TT Tube Drain Coll Box 5 8 ID 1172245 1 1 1 1 UU Tube Drain Tee 1 2 ID 1171989 1 1 1 1 VV Tube Relief 1172012 1 1 1 1 WW Drain Vent 1014003 1 1 1 1 XX Clip Retainer 1175788 1 1 1...

Страница 32: ...32 440 04 2024 01 Specifications are subject to change without notice Wiring Diagram 9MPV 9MVX Variable Speed Blower Motor...

Отзывы: