Circulation Air Blower Data - *9MPV050
Cooling Adjustment
Heating Rise Adjustment
DIP Switch
(OFF = 0 and
ON = 1)
High Cool @ .50
in wc(125 Pa)
Low Cool (80%
of High Cool)
** Adjust
Jumper
Setting
DIP Switch
(OFF = 0 and
ON = 1)
High Heat
Rise
Change @
0.20 in wc
(50 Pa)
Low Heat
Rise
Change at
Resultant
Static
5 & 6
CFM
L/s
CFM
L/s
3 & 4
00
1246
588
997
471
+
00
--4
--3
*00
1211
571
969
457
*NOM
*00
0
0
00
1122
529
898
424
--
00
5
5
01
1105
521
884
417
+
01
3
4
01
1027
485
822
388
NOM
01
7
7
01
945
446
756
357
--
01
13
14
10
892
421
714
337
+
10
--1
0
10
820
387
656
310
NOM
10
4
5
10
745
352
596
281
--
10
9
9
11
688
325
550
260
+
11
--15
--15
11
609
287
487
230
NOM
11
--13
--12
11
541
255
433
204
--
11
--9
--9
Airflow performance includes 1” washable filter media.
*Factory Setting
**Adjust Jumper Setting (+, NOM, --) is applied to both Cooling and Heating
Note 1: HP Mode Jumper provides a 10% reduction in airflow when in Comfort position and a call for low or high cooling is
present with the ”O” line off. This feature is to provide lower airflow for running in HP Heating Mode if desirable.
Note 2: DEHUM mode (24VAC on DEHUM terminal) provides a 20% airflow reduction during cooling calls.
Note 3: Low Heat ESP is a result of High Heat ESP (-- is decrease in rise).
Note 4: High and low heat rise values are approximate air temperature change from return air temperature when at factory
default settings.
Table 2
Airflow
DIP Switch
(OFF = 0 and ON = 1)
Continuous Fan @
0.10 in wc (25 Pa) ESP
1 & 2
CFM
L/s
*00
592
279
01
1021
482
10
1346
635
11
1346
635
* Factory Setting
Table 3
SW2 DIP Assignments
DIP Switch
Blower Parameter
1 & 2
Cont Fan Adj
3 & 4
Heat Speed Adj
5 & 6
Cool Speed Adj
7 & 8
Cool On/Off Delay
Table 4
Cooling Delay Options (SW2 -- 7, 8)
ON DELAY
OFF DELAY
DIP SW2 -- 7/8
(OFF = 0 and ON = 1)
Timed ON (sec)
Airflow during on
delay
Timer OFF (sec)
Airflow during off
delay
*00
5
OFF
90
100%
01
5
OFF
0
OFF
10
30
50%
30
100%
11
30
50%
180
50%
Airflow % is of High Cool airflow demand determined from SW2--5/6 Table 1
Airflow resumes to 100% after on delay time is completed
Airflow stops (or switches to continuous fan speed) after off delay time is completed
* Factory Setting
MAX CFM (L/s) for Factory Washable Filters
Filter Size (in/mm)
CFM
L/s
14
″
X 25
″
(356 x 635)
1400
661
16
″
X 25
″
(406 x 635)
1600
755
20
″
X 25
″
(508 x 635)
2000
944
24
″
X 25
″
(610 x 635)
2500
1180
Max CFM (L/s) based on 600 FPM (3.0 m/s)
NOTE: Disposable filters are typically rated at 300 FPM (1.5 m/s).
These filters only allow half the airflow when compared to 600 FPM
(3.0 m/s) filters.