International Comfort Product WFEU Series Скачать руководство пользователя страница 35

Specifications are subject to change without notice.

35

441 01 7201 00

Sequence of Operation - Heating

1.

Call for Heat

A call for heat is intiated when a connection is observed

between thermostat terminals “R” & “W”.

a.

Pressure Sensor Verification:

The control operates the

inducer in a manner to verify the pressure sensor null
value and span operation are within specification. If the
system is operating correctly, this test takes only a few
seconds. If the system is not functioning properly, the
control times out after a maximum 90 seconds and
displays the proper fault code.

b.

Pre-purge:

The heating cycle begins with operation of

the inducer at “Pre-purge” setting for the 30 seconds.

c.

Igniter Warm-Up:

After the pre-purge timer expires,

the control will set the inducer to the “Ignitor Warm-Up”
setting and energize the igniter for the Igniter Warm-up
period of 17 seconds.

NOTE

:

Inducer motor shuts off during igniter warm up period

and then come back on for the ignition trial.

d.

Trial for Ignition:

Once the igniter warm-up period has

expired, the control sets the inducer to the “Trial for
Ignition” setting and stabilizes the inducer speed to meet
the target pressure. The gas valve is then energized
allowing the flow of gas to the burner. The gas valve
remains open for the Trial for Ignition interva

l.

e.

Flame Sense:

While the gas valve is open, the control

monitors the flame sense circuit to detect the presence of
flame. If flame is not established during the Trial for
Ignition period of 4 seconds, the control de-energizes the
gas valve and operates the inducer for the Inter-purge
period.

f.

Flame Stabilization:

Once flame is established, the

control will set the inducer to the “Flame Stabilization”
setting and maintain the inducer operation at this setting
for the duration of the Flame Stabilization timing of 10
seconds.

g.

Blower On-Delay:

Once a successful ignition occurs,

the control will wait for the Heat Blower On-Delay of 25
seconds (time begins when the gas valve is energized) and
then energize the blower heating speed.

h.

Heating Cycle Run:

After the Flame Stabilization

period is completed, the control will continue to maintain
the heating cycle with the inducer running at the “Run”
setting until one of the following occurs:

(1.)

The call for heat is satisfied (the connection between
“R” & “W” is removed).

(2.)

Flame sense is lost (flame out), in which case the
control will initiate an inter-purge (45s) and recycle.

(3.)

A lockout condition exists, in which case the control
terminates the heating call and waits for the error
condition to resolve according to the programmed
parameters.

i.

Post-purge:

Once the burner cycle has terminated and

loss of flame is verified, the control energizes the inducer
at the “Post-purge” setting for 30s.

j.

Inter-purge:

In the event of a failed trial for ignition, the

control energizes the inducer at the “Post-purge” setting
for the Inter-purge Timing 45s.

k.

Blower Off-Delay:

Once the gas valve has been

de-energized, the control continues to operate the blower
on the HEAT speed for the duration of the Heat Blower
Off-Delay timing. The Heat Blower Off-Delay is
field-selectable (90, *120, 150, 180).

NOTE

:

*120 is default setting.

OFF:

The controls returns to the stand- by mode until either a

thermostat call is received or an error condition occurs.

Sequence of Operation - Cooling

1.

Call for Cool

A call for heat is intiated when a connection is observed

between thermostat terminals “R” & “Y”.

a.

Blower On-Delay:

When the call for cool is initiated,

the control will wait for the Cooling Blower On-Delay
timing of 2 seconds, for both jumper settings.

b.

Blower Off-Delay:

Once the connection between “R”

and “Y” is removed, the control continues to operate the
blower on the COOL speed for the duration of the Cool
Blower Off-Delay timing (fixed 90 seconds).

OFF:

The controls returns to the stand- by mode until either a

thermostat call is received or an error condition occurs.

Sequence of Operation - Fan Only

1.

Operation:

Fan Only Mode is initiated when a

connection is observed between thermostat terminals “R”
& “G”. The “G” terminal is ignored when there is either a
call for heat or call for cool. When in the Fan Only Mode,
the blower will be energized to run on Fan speed.

Fault Code Recall

1.

Function:

When the SW1 button is pressed momentarily,

the control displays the last five (5) fault codes recorded in
non-volatile memory upon demand.

2.

Operation:

The control must be powered and the

thermostat satisfied (no call for heat or cool). Depress and
release the SW1 button once (less than 5 seconds); the
LED will flash the Fault Code History (up to 5 fault codes
from newest to oldest)

NOTE

:

Fault Code Display Means:

Multi-Color LED (Green,

Amber, Red).

Clear Fault Memory

1.

Function:

When the SW1 button is pressed and held for

an extended period (more than 5 seconds, less than 10
seconds), the control erases the stored fault code history.

2.

Operation:

The control must be powered and the

thermostat satisfied (no call for heat or cool). Depress and
hold the SW1 button for at least 5 seconds (but not more
than 10 seconds), until the LED flashes a rapid Green,
then release. The fault code history will be erased.

Component Test

1.

Function:

When the SW1 button is pressed and held for

an extended period of time (more than 10 seconds, less
than 15 seconds), the control will initiate a component
self test.

2.

Operation:

The control must be powered and the

thermostat satisfied (no call for heat or cool). Depress and
hold the SW1 button for at least 10 seconds (but not more
than 15 seconds), until the LED flashes Amber, then
release. The control will execute the following functions:

a.

Inducer starts and runs throughout the entire test

b.

Hot surface igniter on for 15 seconds, then off

c.

Blower motor will be turned on at constant fan speed, heat
speed, and cool speed for 15 seconds each.

d.

Control returns to standby mode.

NOTE

:

If SW1 button is held for longer than 15 seconds, the

control will remain in standby mode

Wiring Diagrams

Refer to Fig. 38 for wiring diagram.

Troubleshooting

Refer to the service label. (Fig. 35), wiring diagram (Fig. 38), and

the Service Guide (Page 37) can be a useful tool in isolating
furnace operation problems. The Guide will help to identify the

problem or failed component. After replacing any component,

verify correct operation sequence.

Содержание WFEU Series

Страница 1: ...4 START UP ADJUSTMENT AND SAFETY CHECK 26 START UP PROCEDURES 26 ADJUSTMENTS 26 CHECK SAFETY CONTROLS 28 SERVICE AND MAINTENANCE PROCEDURES 30 INTRODUCTION 31 ELECTRICAL CONTROLS AND WIRING 31 CARE AN...

Страница 2: ...and ventilation air to the furnace space as specified in Air for Combustion and Ventilation section 4 Combustion products must be discharged outdoors Connect this furnace to an approved vent system on...

Страница 3: ...FURNACE SIZE A B C D VENT CABINET WIDTH IN MM OUTLET WIDTH IN MM TOP FLUE COLLAR ONLY IN MM BOTTOM WIDTH IN MM VENT CONNECTION SIZE IN MM SHIP WT LB KG WFEU040B036 17 1 2 445 15 7 8 403 11 9 16 294 16...

Страница 4: ...ational Fuel Gas Code NFGC NFPA 54 ANSI Z223 1 and the Installation Standards Warm Air Heating and Air Conditioning Systems ANSI NFPA 90B General Installation S Current edition of the NFGC and the NFP...

Страница 5: ...Firmly touch the clean unpainted metal surface of the furnace chassis which is close to the control Firmly touch the clean unpainted metal surface of the furnace chassis which is close to the control...

Страница 6: ...nstallations may require OUTDOOR AIR for combustion due to chemical exposures S Commercial buildings S Buildings with indoor pools S Laundry rooms S Hobby or craft rooms and S Chemical storage areas I...

Страница 7: ...00 4 400 5 500 6 600 0 20 3 150 4 200 5 250 3 300 4 950 6 600 8 250 9 900 0 10 6 300 8 400 10 500 6 600 9 900 13 200 16 500 19 800 0 00 NP NP NP NP NP NP NP NP Air Changes Hour FIRE HAZARD Failure to...

Страница 8: ...ON AIR OPENINGS SHALL BE AT LEAST 3 IN 305mm 305mm 305mm 305mm 305mm 76mm Minimum dimensions of 3 in 76 mm NOTE Use any of the following combinations of openings A B C D D E F G A03174 Fig 7 Air for C...

Страница 9: ...reely communicates with the outdoors provided there are adequate permanent ventilation openings directly to out doors having free area of at least 1 in 2 4 000 Btuh of total input rating for all gas a...

Страница 10: ...ved for use on combustible flooring when any one of the following 3 accessories are used S Downflow combustible floor subbase S Manufacturer s approved Cased Coil or Coil Casing 1 Determine applicatio...

Страница 11: ...20 508 20 508 HORIZONTAL INSTALLATION FIRE EXPLOSION AND CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in personal injury death and or property damage Do not install th...

Страница 12: ...ing the furnace the return air shall also be handled by duct s sealed to the furnace casing and terminating outside the space containing the furnace Secure ductwork with proper fasteners for type of d...

Страница 13: ...A02020 Fig 14 Duct Flanges 1 4 6mm THREADED ROD 4 REQ SECURE ANGLE IRON TO BOTTOM OF FURNACE WITH 3 8 x3 4 19mm SCREWS TYPICAL FOR 2 SUPPORTS 1 25mm SQUARE 1 1 4 x1 1 4 x1 8 32x32x3mm ANGLE IRON OR U...

Страница 14: ...CH STRAP THE STRAPS SHOULD BE VERTICAL AGAINST THE FURNACE SIDES AND NOT PULL AWAY FROM THE FURNACE SIDES METHOD 1 FOLD ALL STRAPS UNDER FURNACE AND SECURE WTH 4 8 x 3 4 19 mm SHEET METAL SCREWS 2 SCR...

Страница 15: ...pipe shall be installed at the furnace gas control valve and extend a minimum of 2 in 51 mm outside the furnace WARNING Gas piping must be installed in accordance with national and local codes Refer t...

Страница 16: ...ow performance included 3 4 in 19 mm washable filter media such as contained in factory authorized accessory filter rack To determine airflow performance without this filter assume an additional 0 1 i...

Страница 17: ...ge without notice 17 441 01 7201 00 A02075 Fig 19 Upflow Return Air Configurations and Restrictions A02163 Fig 20 Downflow Return Air Configurations and Restrictions A180279 Fig 21 Horizontal Return A...

Страница 18: ...n electrical fault should occur This may consist of electrical wire conduit approved for electrical ground or a listed grounded power cord where permitted by local code when installed in accordance wi...

Страница 19: ...ound wire to green ground screw on J Box bracket 5 Connect line voltage leads as shown in Fig 24 6 Reinstall cover to J Box Do not pinch wires between cover and bracket BX CABLE INSTALLATION IN FURNAC...

Страница 20: ...C LINE CONNECTION L1 INDUCER MOTOR AND IGNITER 115 VAC NEUTRAL CONNECTOR ECM BLOWER 115VAC PRIMARY OF TRANSFORMER 115 VAC EAC 115 VAC WHEN USED FLAME SENSOR HUMIDIFIER 115 VAC WHEN USED NO CONNECTION...

Страница 21: ...uilding codes the current edition of National Fuel Gas Code ANSI Z223 1 NFPA 54 NFGC Parts 12 and 13 the local building codes and furnace and vent manufacturers instructions These furnaces are design...

Страница 22: ...207 299 15 4 5 NR 152 233 334 20 6 0 NR NR 250 368 30 9 1 NR NR NR 404 Table 9 Minimum Allowable Input Rating of Space Heating Appliance in Thousands of BTUH per Hour VENT HEIGHT FT M INTERNAL AREA O...

Страница 23: ...Specifications are subject to change without notice 23 441 01 7201 00 A180242 Fig 25 Chimney Inspection Chart...

Страница 24: ...ow does NOT count as part of the number of vent connector elbows The vent connector can exit the furnace through one of two locations on the casing 1 Attach the single wall vent connector to the furna...

Страница 25: ...TES 1 2 4 7 8 9 on the page following these figures A03213 Fig 28 Horizontal Left Application Vent Elbow Left SEE NOTES 1 2 4 5 6 7 8 9 on the page following these figures A03207 Fig 29 Downflow Appli...

Страница 26: ...Failure to make proper con nections will result in improper operation See Fig 24 3 Gas supply pressure to the furnace must be greater than 4 5 In W C 0 16 psig but not exceed 14 In W C 0 5 psig 4 Chec...

Страница 27: ...liances and pilots served by the meter b Run furnace for 3 minutes in heating operation c Measure time in seconds for gas meter to complete 1 revolution and note reading The 2 or 5 cubic feet dial pro...

Страница 28: ...cord amp draw across terminals when furnace is in heating and after blower starts 4 Set heat anticipator on thermostat per thermostat in structions and install on subbase or wall R Y W G 10 TURNS THER...

Страница 29: ...kage from furnace vent elbow g Switch will auto reset when it cools h Re install vent connector Table 10 Gas Rate Cu Ft Hr SECONDS FOR 1 REVOLUTION SIZE OF TEST DIAL SECONDS FOR 1 REVOLUTION SIZE OF T...

Страница 30: ...tlet Pressure for Gas Heat Values at Altitude 100 000 Tabulated Data Based on 100 000 BTUH Input for 0 ft 0m to 2000 ft 1524 M above sea level ALTITUDE RANGE ft m RANGE ft m HEAT VALUE AT ALTI TUDE Bt...

Страница 31: ...trol See Fig 38 Any shorts of the 24 v wiring during installation service or maintenance will cause this fuse to blow If fuse replacement is required use ONLY a 3 amp fuse The control LED will display...

Страница 32: ...essary 4 Check electrical connections for tightness and controls for proper operation each heating season Service as necessary 5 Inspect the vent pipe vent system before each heating season for rust c...

Страница 33: ...6 If furnace is operating properly RELEASE BLOWER ACCESS DOOR SWITCH Remove any jumpers or reconnect any disconnected thermostat leads Replace blower access door 17 Reinstall outer door 18 Cycle furna...

Страница 34: ...equate seal may occur and RTV sealant G E 162 6702 or Dow Corning 738 are needed before starting installation NOTE DO NOT substitute any other type of RTV sealant 12 Apply new sealant to flange of col...

Страница 35: ...ation of the Heat Blower Off Delay timing The Heat Blower Off Delay is field selectable 90 120 150 180 NOTE 120 is default setting OFF The controls returns to the stand by mode until either a thermost...

Страница 36: ...Specifications are subject to change without notice 36 441 01 7201 00 A180211 Fig 38 Wiring Diagram...

Страница 37: ...ses and the CFH is present the furnace returns to normal operation Check Main limit Draft Safeguard Burner Thermal Switch are all in the Main Limit Circuit Check for any blockages in flue pipe or blow...

Страница 38: ...IZE MAJOR SERIES MINOR SERIES WFEU 060 C 60 A 1 TO OBTAIN INFORMATION ON PARTS Consult your installing dealer or the classified section of your local telephone directory under the Heating Equipment or...

Отзывы: