SUMMER SEASON 

 

Make sure the fuel oil valve is closed when the boiler 
is not used for long period of time.

  

 
 

5) 

START-UP AT THE BEGINNING OF 
THE HEATING SEASON 

 
1.  Clean the chimney, the connecting flue pipes and 

the boiler. Follow steps in section 3, paragraph 6 
to proceed; 

2.  Replace the oil filter; 

3.  Have the burner electrodes cleaned along with the 

burner retention head and change the nozzle; 

4.  Check the operation of the high temperature 

control limit; 

5.  Check the operation of the circulating pump. 
 
 
 
 

 
 

PART 3 

MAINTENANCE 

 

 

1) 

MAINTENANCE 

 
The area around the boiler must be kept free of 
combustibles, excessive dust and humidity, and highly 
flammable products. Fresh air openings to the boiler 
and the boiler room must be kept clear. Repair any 
water and oil leaks without delay. 
 
 

2) 

NOZZLE 

 
A dirty or clogged nozzle can prevent ignition or cause 
odours. It must be replaced. 
 
 

3) 

FUEL TANK 

 
Regularly check the level in the fuel tank. Should the 
tank run dry, the fuel lines will have to be bled before 
restarting the burner. 
 
 

4) 

OIL FILTER 

 
Replace the oil filter at the beginning of the heating 
season. 
 
 

5) 

BURNER AND CIRCULATING PUMP 
MOTORS 

 
Motors should be lubricated at least once a year 
(except life time lubricated motors),  with 2 to 3 drops 
of SAE 20 non-detergent oil, put in the appropriate 
access. 
 
 

6) 

CLEANING THE BOILER 

 
1.  Put the main switch “OFF” before any cleaning 

works; 

2.  Remove and clean the connecting flue pipe and, 

sweep and check the chimney; 

3.  Remove the smoke box and the fire tube baffles 

and, with the help of a 2 inches diameter steel 
brush, clean the fire tubes; 

4.  Remove the burner and clean the combustion 

chamber. Take care to not damage the ceramic 
bottom pad; 

5.  Examine the cleaned surfaces for corrosion and 

correct the cause, if need; 

6.  Reinstall all components in their original position 

and re-adjust the unit. 

 
 

7) 

BOILER PURGE 

 
It is recommended to purge the boiler about 1 minute 
at least once a year, to evacuate mud and sediments 
accumulated at the bottom of the boiler. 

 

Proceed as follows : 

1.  Let the boiler cool down; 

2.  Hook-up a garden hose from the drain valve to an 

open bucket; 

3.  Open the drain valve until the water is clear. 
 
 

8) 

SPARE PARTS 

 

It is always recommend to replace a defective part by 
a genuine part, available at your supplier. 

Содержание HMD Series

Страница 1: ...ture reference Caution Do not tamper with the unit or its controls Call a qualified service technician HMD Models Manufactured by International Comfort Product 3400 Industriel blvd Sherbrooke Qc Canad...

Страница 2: ...nise the characteristics of the HMD serie HMD boiler with potable hot water stainless steel tank in tank and with a flue pipe of 7 inches diameter The models are identified HMD 124 HMD 135 HMD 146 HMD...

Страница 3: ...6 4 mm per foot 300 mm of run upward toward the chimney The use of a damper in the connecting flue pipe is strictly prohibited If more than one pipe are to be connected to the same chimney the sectio...

Страница 4: ...d air in the boiler d A correctly sized water circulator installed on the heating loop e Stop valves and threaded unions installed on return and supply boiler pipes Always use quality pipe sealant on...

Страница 5: ...he draft regulator and the outlet of the boiler 10 Adjust the burner air intake for a smoke scale reading of 0 on the Bacharrach scale 11 Analyse the combustion gases with an appropriate instrument an...

Страница 6: ...R Replace the oil filter at the beginning of the heating season 5 BURNER AND CIRCULATING PUMP MOTORS Motors should be lubricated at least once a year except life time lubricated motors with 2 to 3 dro...

Страница 7: ...vice telephones day Night Dealer s name and address RESULT OF START UP TEST Nozzle Pressure lbpsi Burner adjustments Primary air Fine air Draw Assembly CO2 Smoke scale Bacharach Gross stack temperatur...

Страница 8: ...FIGURE 1 HMD Boiler DNS 0214 Rev B 9...

Страница 9: ...or if thermostat opened Lo contact opened Start Hi Contact closed and therm closed or if therm opened Lo contact closed Circulator Stop Thermostat opened or Circ contact opened Start Thermostat close...

Страница 10: ...FIGURE 3 Finned tube baseboard piping FIGURE 4 Cast iron radiators piping DNS 0216 Rev B DNS 0217 Rev B 11...

Страница 11: ...ottom insulation B00618 03 8 Floor screws kit K08003 Kit of 4 9 Drain valve G11Z002 10 Heat exchanger insulation K09001 Includes 2 parts 11 Casing closure angle B00820 12 Casing C00157 13 Control pane...