OIL SUPPLY

 

 
The oil tank and lines must be installed in accordance 
with local codes and regulations. The burner can be 
hooked up with a one pipe system if the oil level in the 
tank is always over the burner level. For an outside 
aboveground fuel tank hook up, ideally use a one pipe 
system with nominal dimension of 12 mm (1/2”) 
diameter, and be sure to have the oil filter and at least 
3 meters  (10 ft) of piping installed inside, to allow the 
fuel oil to warm up before reaching the burner in very 
cold weather.  The following configurations must be 
respected regarding the oil pump by-pass plug. With 
Riello burner, remove the by-pass plug for one pipe 
system. 
 
The installation must include an oil filter and shutoff 
valve. Make sure the piping has no leaks or 
stoppages. Oil lines shall include no couplings. Never 
use compression fittings. For a 2 pipes system, use 
the same diameter for both the suction and the return 
lines and set them at the same depth in the oil tank. 
Additional information can be found in the burner 
installation brochure that came with your boiler. 

 
 

6) 

CHIMNEY 

 

6.1) 

Chimney draft 

 

Chimney draft must be strong enough to ensure safe, 
reliable operation of your unit. 

 
 

6.2) 

Installation

 

 

 
The connecting flue pipe diameter should never 
exceed that of the chimney and its horizontal runs 
should have a minimum slope of 1/4” (6.4 mm) per 
foot (300 mm) of run upward toward the chimney. The 
use of a damper in the connecting flue pipe is strictly 
prohibited. If more than one pipe are to be connected 
to the same chimney, the sectional area of the 
chimney must be equal to the total of individual 

sectional areas.  The usage of a draft control is 
compulsory. His omission constitutes sufficient 
grounds for voiding your warranty. 

 
 

NOTICE 

The formation of condensation on the three 
outer sides of an outside chimney is a 
possibility with efficient hot water boilers.  
Should this happen, a chimney liner or a 
“SMH” sidewall venting system should be 
installed. 

 
 

7) 

BURNER INFORMATIONS 

 
The burner is shipped in a separate box from the 
boiler and must be installed following the next steps : 
 
1.  Verify the model number on burner box to be 

match with the one on the boiler nameplate; 

2.  Install the nozzle supplied and verify the 

electrodes setting; 

3.  Install the burner on the boiler using supplied nuts 

already on the studs. Do not forget the fireproof 
gasket supplied with the burner. For the Riello 
burners with an adjustable flange, make sure that 
the end of the blast tube is flush with the inside 
surface of the combustion chamber; 

4.  Connect the oil pipe(s) to the burner pump; 

5.  Perform electrical connections in accordance with 

the appropriate diagram (See paragraph 4). 

 
 
 
 
 
 
 
 
 

 
 

TABLE 1 

Chimney draft 

 

Models 

Chimney size 

inches (mm) 

Connecting pipe 

inches (mm) 

Recommended draft 

inches (mm)  W.C. 

 

Minimum 

Maximum 

 

 

HMD-124 @ 146 

5  (127) 

6  (152) 

7  (178) 

0.035  (0.9) 

HMD-163 @ 179 

6  (152) 

8  (203) 

7  (178) 

0.05  (1.3) 

 
 
 

 

 

 

Содержание HMD Series

Страница 1: ...ture reference Caution Do not tamper with the unit or its controls Call a qualified service technician HMD Models Manufactured by International Comfort Product 3400 Industriel blvd Sherbrooke Qc Canad...

Страница 2: ...nise the characteristics of the HMD serie HMD boiler with potable hot water stainless steel tank in tank and with a flue pipe of 7 inches diameter The models are identified HMD 124 HMD 135 HMD 146 HMD...

Страница 3: ...6 4 mm per foot 300 mm of run upward toward the chimney The use of a damper in the connecting flue pipe is strictly prohibited If more than one pipe are to be connected to the same chimney the sectio...

Страница 4: ...d air in the boiler d A correctly sized water circulator installed on the heating loop e Stop valves and threaded unions installed on return and supply boiler pipes Always use quality pipe sealant on...

Страница 5: ...he draft regulator and the outlet of the boiler 10 Adjust the burner air intake for a smoke scale reading of 0 on the Bacharrach scale 11 Analyse the combustion gases with an appropriate instrument an...

Страница 6: ...R Replace the oil filter at the beginning of the heating season 5 BURNER AND CIRCULATING PUMP MOTORS Motors should be lubricated at least once a year except life time lubricated motors with 2 to 3 dro...

Страница 7: ...vice telephones day Night Dealer s name and address RESULT OF START UP TEST Nozzle Pressure lbpsi Burner adjustments Primary air Fine air Draw Assembly CO2 Smoke scale Bacharach Gross stack temperatur...

Страница 8: ...FIGURE 1 HMD Boiler DNS 0214 Rev B 9...

Страница 9: ...or if thermostat opened Lo contact opened Start Hi Contact closed and therm closed or if therm opened Lo contact closed Circulator Stop Thermostat opened or Circ contact opened Start Thermostat close...

Страница 10: ...FIGURE 3 Finned tube baseboard piping FIGURE 4 Cast iron radiators piping DNS 0216 Rev B DNS 0217 Rev B 11...

Страница 11: ...ottom insulation B00618 03 8 Floor screws kit K08003 Kit of 4 9 Drain valve G11Z002 10 Heat exchanger insulation K09001 Includes 2 parts 11 Casing closure angle B00820 12 Casing C00157 13 Control pane...

Отзывы: