FRONT PANEL DIAGNOSTICS

Page:  4

A

G
R
O
U
N
D

C

N
E
U
T
R
A

L

B

1. CONNECT THE GROUND WIRE TO THE 

SERVICE PANEL GROUND BUS.

2. CONNECT THE NEUTRAL WIRE FROM THE SERVICE PANEL NEUTRAL BUS TO

THE LUG LABELED NEUTRAL.  (Except for Delta Application)

3. CONNECT THE PHASE (HOT) WIRES FROM A 3 POLE BREAKER TO THE SPD      

DEVICE CONNECTORS LABELED PHASE "A", "B" AND "C", as appropriate.

CAUTION:

BEFORE ENERGIZING THE SPD:

ENSURE ALL CONNECTIONS ARE CORRECT.

DO NOT ENERGIZE WITH FRONT COVER OPEN.

8 8 8 8 8 8

 

A

 

C

 B

GREEN=PROTECTED

OFF=NO PROTECTION

SYSTEM

FAULT

N-G

VOLTAGES

RESET

ENABLE

TEST

EVENT COUNTER

TEST

DISABLE

ENABLE

STATUS INDICATORS

AUDIO ALARM

[Figure #10:  3 Phase Wye Configuration Shown]

1) For Single Phase Models:

Only 1 Green LED, in the
Phase “B” position, is provided.

3) For Delta Models:

There is no Yellow,

N-G, LED.

2) For Split Phase Models: 

2 Green LEDs, in Phase “A”
& “C” positions, are provided.

NOTES:

NOTES:

1)

For Single Phase Models, Phase “A”
& Phase “C” lines are left vacant.

2)

For Split Phase Models, Phase “B”
is left vacant.

3)

For Delta Configurations, the Neutral 
position is left vacant.

[Figure #9:  3 Phase Wye Wire Hook-up]

G

PHASE

FAULT

N-G

FAULT

TEST

DISABLE

ENABLE

PHASEPHASE

3 POLE BREAKER

KEEP WIRES

AS SHORT

AS POSSIBLE

CONDUIT

N
E
U
T
R
A
L

[Figure #8:  3 Phase Wye Breaker Hook-up]

Содержание SG160

Страница 1: ...R R LISTED LISTED TRANSIENT SURGE SUPPRESSORS FOR AC POWER PANEL APPLICATIONS USER MANUAL 1449 2nd Edition HARDWIRED SURGE PROTECTION DEVICES SG Modular Series...

Страница 2: ...rrect SPD Model has been selected DO NOT CONNECT WITHOUT SECURING POWER FROM THE DISTRIBUTION PANEL CHECK TO ENSURE THAT ALL CONNECTIONS ARE CORRECT AND SECURE BEFORE ENERGIZING DO NOT ENERGIZE WITH D...

Страница 3: ...a 2 Pole Breaker Requires a 3 Pole Breaker 120 240Vac Split Phase 3 Wire Ground PHASE A NEUTRAL GND 120 VAC 120 VAC PHASE B 120 or 240 VAC PHASE NEUTRAL GND PHASE A NEUTRAL GND PHASE B PHASE C 120 or...

Страница 4: ...FAULT N G VOLTAGES RESET ENABLE TEST EVENT COUNTER TEST DISABLE ENABLE STATUS INDICATORS AUDIO ALARM Figure 10 3 Phase Wye Configuration Shown 1 For Single Phase Models Only 1 Green LED in the Phase...

Страница 5: ...suppressor encounters Control of the Surge Counter is managed with a switch located to the left of the count er display The switch has three 3 settings Up momentary only for RESET Center this is the E...

Страница 6: ...160kA 240kA 320kA Phase C RPM SURGE RATING 160kA 240kA 320kA Phase B RPM SURGE RATING 160kA 240kA 320kA B SENSOR CABLE Figure 11 Internal Layout INTERNAL LAYOUT 1 Make Sure the power has been turned o...

Страница 7: ...ENANCE INSTRUCTIONS At intervals not to exceed two 2 months check and verify 1 Diagnostic and Indication display 2 Alarm Operation 3 Condition of ALL Connection Cables and Terminations ANY ALTERATIONS...

Страница 8: ...not apply to you This warranty gives you specific legal rights and you may also have other rights which vary from state to state This warranty service is available by either a returning the product t...

Отзывы: