Before starting the installation, measure the Line voltage with an AC voltmeter to ensure the
correct device has been selected for the current  application.  The MCOV (maximum continuous
operating voltage) Cannot exceed the maximum limits for the following service voltages:

INSTALLATION INSTRUCTIONS

120/208Vac, Three Phase Wye, 4 Wire + Ground

277/480Vac, Three Phase Wye, 4 Wire + Ground

120/240Vac, Three Phase Delta, 4 Wire + Ground

240 or 480Vac, Three Phase Delta, 3 Wire + Ground

120 or 240Vac, Single Phase, 2 Wire + Ground

Requires a 1 Pole Breaker

Requires a 2 Pole Breaker

Requires a 3 Pole Breaker

120/240Vac, Split Phase, 3 Wire + Ground

PHASE A

NEUTRAL

GND

120 VAC

120 VAC

PHASE B

120 or 240 VAC 

PHASE

NEUTRAL

GND

PHASE A

NEUTRAL

GND

PHASE B

PHASE C

120 or 277

VAC

208 or 480

VAC

PHASE A

PHASE B

PHASE C

NEUTRAL

208

VAC

240

VAC

240

VAC

(High Leg) “Orange”

240 or 480

VAC

PHASE B

PHASE A

PHASE C

GND

GND

OR

240 or 480

VAC

240 or 480

VAC

208 or 480

VAC

120 or 277

VAC

120 or 277

VAC

208 or 480

VAC

Requires a 3 Pole Breaker

Requires a 3 Pole Breaker

[Figure #6]

[Figure #7]

[Figure #5]

[Figure #4]

[Figure #3]

STANDARD ELECTRICAL CONFIGURATIONS

120VAC=150MCOV
220VAC=320MCOV
230VAC=320MCOV

240VAC=320MCOV
277VAC=320MCOV
480VAC=550MCOV

NOTE

Wye Configuration is applicable for:

220/380VAC 

230/400VAC 

240/415VAC 

120 VAC

120 VAC

Содержание SG160

Страница 1: ...R R LISTED LISTED TRANSIENT SURGE SUPPRESSORS FOR AC POWER PANEL APPLICATIONS USER MANUAL 1449 2nd Edition HARDWIRED SURGE PROTECTION DEVICES SG Modular Series...

Страница 2: ...rrect SPD Model has been selected DO NOT CONNECT WITHOUT SECURING POWER FROM THE DISTRIBUTION PANEL CHECK TO ENSURE THAT ALL CONNECTIONS ARE CORRECT AND SECURE BEFORE ENERGIZING DO NOT ENERGIZE WITH D...

Страница 3: ...a 2 Pole Breaker Requires a 3 Pole Breaker 120 240Vac Split Phase 3 Wire Ground PHASE A NEUTRAL GND 120 VAC 120 VAC PHASE B 120 or 240 VAC PHASE NEUTRAL GND PHASE A NEUTRAL GND PHASE B PHASE C 120 or...

Страница 4: ...FAULT N G VOLTAGES RESET ENABLE TEST EVENT COUNTER TEST DISABLE ENABLE STATUS INDICATORS AUDIO ALARM Figure 10 3 Phase Wye Configuration Shown 1 For Single Phase Models Only 1 Green LED in the Phase...

Страница 5: ...suppressor encounters Control of the Surge Counter is managed with a switch located to the left of the count er display The switch has three 3 settings Up momentary only for RESET Center this is the E...

Страница 6: ...160kA 240kA 320kA Phase C RPM SURGE RATING 160kA 240kA 320kA Phase B RPM SURGE RATING 160kA 240kA 320kA B SENSOR CABLE Figure 11 Internal Layout INTERNAL LAYOUT 1 Make Sure the power has been turned o...

Страница 7: ...ENANCE INSTRUCTIONS At intervals not to exceed two 2 months check and verify 1 Diagnostic and Indication display 2 Alarm Operation 3 Condition of ALL Connection Cables and Terminations ANY ALTERATIONS...

Страница 8: ...not apply to you This warranty gives you specific legal rights and you may also have other rights which vary from state to state This warranty service is available by either a returning the product t...

Отзывы: