Risk of injury or property damage!

Do not install or operate this equipment and other associated equipment without basic safety 

precautions.

Read and follow the safety instructions listed below and other basic safety precautions before 

installation or operation of this control and other associated equipment.

 

1. This control must be installed by a qualified person, according to the national and local electrical    

    codes.

  2. Install this control not less than 5 feet (3 meters in Canada) from inside edge of pool and 1 foot     

    (30cm) above ground.

  3. USE COPPER CONDUCTORS ONLY rated 75˚C minimum.

  4. Do not exceed maximum ratings of individual components, wiring devices and current carrying  

 

    capacity of conductors.

  5. For control grounding, bonding, installing and the wiring of underwater lights, refer to Article 680    

    of the National Electrical Code or Article 68 of the Canadian Electrical Code.

  6. The control should not operate any equipment which would cause bodily injury or property 

    damage should it be activated unexpectedly.

INSTALLATION 

1.  Select the proper outdoor location for the Control 

and prepare the necessary conduit run(s) required by 

the installation layout.

2.  Hang enclosure on a flat vertical surface or other 

support, using hardware suitable for the 

purpose.

3.  Properly terminate conduits at both ends and pull-in 

the conductors (Min.75˚C Rated) as 

specified by the installation layout.

4.  Select the appropriate wiring diagram (120V.or 

240V. installation) on page 4 of this manual and make 

LINE and LOAD (Pump) connections as shown. First 

identify each lead by color. The LINE connections for 

240 Volt supply are Black and Red. To operate the 

clock motor and relay coil, you also have to connect 

the NEUTRAL to the White lead. NOTE: If the 240 Volt 

supply is GFCI protected - Stop. This is not the right 

control for such applications. Use Model PF1102T 

instead. Otherwise connect pump to Blue and Yellow 

leads. Make sure the installation is properly grounded.

5.  If the Control is installed in location where it is 

exposed to direct sun most of the day, extend 8 inches 

of the copper capillary tube of the

 

thermostat into an open ended (plastic or metal) con-

duit, about 10 inches long, installed at bottom of the 

enclosure. Handle capillary tube with care!

6.  TEST INSTALLATION:

 

a.  Turn thermostat dial to its lowest setting and 

 

 

place crushed ice (in plastic bag) inside 

 

 

capillary coil of Thermostat.

 

b.  Turn power ON to Control, wait one minute

 

 

then slowly turn thermostat dial counter-

 

 

clockwise until Filter Pump starts.

 

c.  Turn power OFF to Control, remove ice, 

 

 

check wiring, reinstall front plate.

 

d.  Turn power ON to Control and set Timer 

 

 

and the Thermostat, see OPERATION

 

 

instructions on page 3.

INSTALLATION - MODEL PF1103MT

1.  Install mechanism in any Intermatic Pool Panel with 

only one Time Switch by snapping it into the unused 

mounting bracket, furnished with the Panel.

TO SET FILTER TIMER, follow instructions on page 3. The length of the daily filtration/heating cycle depends 

on many variables such as size, shape, and geographic location of the pool, water chemistry, type of pool equip-

ment, usage and season of year. If not sure, contact your local pool service professional for advice.

TO SET THERMOSTAT, turn dial to desired temperature between 33˚F and 42˚F. Remember, many variables, 

such as the location of this Control, the location of the pool or spa, the location and insulation of the plumbing, 

etc., must be considered before selecting the “turn ON” temperature of the Filter Pump. Your local pool service 

professional is the best source of information. The Thermostat is factory set to turn OFF the Filter Pump when the 

ambient temperature rises 5˚ F above its set point.

SETTING / OPERATING INSTRUCTIONS

2

   SYMPTOM 

CAUSE(S) 

CORRECTIVE ACTION

 
 

1.  Timer will not keep time 

 No trippers on dial 

  Install trippers

    

 Trippers are not installed properly 

  Re-install trippers on dial

 2.  Timer dial is not turning 

 Breaker OFF 

  Turn ON Power

    

 Timer motor dead due to lightning 

  Replace timer   

 

 3.  Pump operates off schedule 

 Power failure earlier 

  Reset timer

    

 Breaker was OFF for some time 

  Reset timer

 4.  Filter pump is ON at all timer 

 Timer contacts welded 

  Replace timer

    

      

    

   

 5.  Filter Pump will not start 

 Defective thermostat (see Test procedure) 

  Replace t.stat

   when temp.is below 32 deg. 

 Defective relay 

  Replace relay

    

 Defective wiring 

  Check wiring       

TROUBLESHOOTING

 

OPERATION 

(CONT.)

3

1. Insert ON (green) and OFF (red) 

  trippers into dial at desired ON 

  and OFF times (Fig. 1). 

2.  Be sure trippers are firmly 

  pressed against dial surface 

  and at least one space is left 

  between ON and OFF trippers

  (Fig. 2).

3. Turn dial clockwise one or more 

  revolutions until correct time of 

  day is next to arrow in center of 

  dial (Fig. 3).

 

Manual Knob

ON Tripper (Green)

OFF Tripper (Red)

1.  The  knob  in  the  upper  left  corner  of  timer  is 

  for  operating  the  Filter  pump  manually  when

  needed.  By  turning  it  COUNTERCLOCKWISE, 

  it  will  start  or  stop  the  filtering/heating  cycle 

  ahead  of  the  scheduled  start/stop  time. 

  Automatic  operation  will  resume  with  the 

  next scheduled cycle.

2.  Timer comes with two sets of trippers, allow-

  ing the choice of two cycles per day.If only  

 

  one cycle is needed, the extra trippers may 

  be stored on the dial by placing SAME color 

  trippers next to each other.

3.  To  suspend  automatic  operation,  remove  red 

  and  green  trippers  from  Dial  and  Store  them 

  in a convenient place.

4.  Additional  trippers  can  be  obtained  by  con-

  tracting an Intermatic distributor or Intermatic 

  Consumer  Service  at  (815-675-7000  and  ask-

  ing for 156PB10398A tripper kit (2 ON and 2 

  OFF trippers.)