background image

INSTALLATION

ACCESSORIES

TROUBLESHOOTING

1. Remove the two #10 hex head screws from the back

of the enclosure and attach mounting bracket to 
enclosure.

2. Select the proper location for the control panel and 

hang enclosure on a flat vertical surface or other 
support. When mounting the enclosure, be sure to 
use hardware capable of supporting its weight.
NOTE: The feeds may enter through any one of 
the 1/2, 3/4, or 1 inch knockouts at the bottom or 
back of the enclosure. A dimple is positioned on the 
top of the enclosure for piloting a drill to create an 
overhead entrance into the panel. The main feed 
must also pass through a listed outdoor conduit hub, 
mounted at the time of installation.

3. Prepare the necessary conduit runs, terminate them 

at both ends and pull in the conductors as specified 
by the installation layout. If this control is used for 
direct conduit connection to a wet-niche or no-niche 
luminaire, order one of the following:

1/2” non-metallic - order 156PA13713A

3/4” non-metallic - order 156PA13714A

1” non-metallic - order 156PA13715A
1/2” metallic - order 156PA14336

4. Refer to Figure 1 below.

Note that though this
figure shows a P1353ME 
Digital Time Clock installed, 
the P1353ME is not 
included on all models.
See door panel for the specific configuration and 
rating of the model you are installing. To wire the 
panel, follow the wiring diagram located inside the 
enclosure door. When wiring the P1353ME, make 
sure that the connections are tight (25 lb.-in.
minimum) and

insulation clears the pressure plate

(see illustration).

5. If required by the heater manufacturer, the P1353ME

includes a connection for a fire-man switch. This 
switch only works in conjunction with circuit #1 (Load 
#1)  the P1353ME. Refer to pages 6 & 7 of the 
instruction manual for connection information, and 
refer to page 28 for fireman switch programming 
information. Use at least #18 AWG wiring with insula-
tion rated 300 volt or higher. Some heaters may 
require a special connecting harness, contact heater 
manufacturer for details. Place heater ON/OFF 
switch on heater to ON position.

6. To install additional wiring devices  inside the enclo-

sure, first remove rectangular knockout(s) in dead 
front. Next, remove hex head screws in back of 
enclosure and install stand-offs* in place of screws.
Attach wiring device to stand-offs.

*Stand-offs are not furnished. Order 21T156A for 
a set of four (4) stand-offs and mounting 
hardware.

7. If external bonding is required, install a bonding 

lug at bottom of enclosure and bond installation
according to code requirements (Order 
156T11047A for Bonding Lug Kit).

8. Testing of the installation is optional and recom-

mended only if the desired loads are securely in 
place and will not be damaged by this test:
a. Turn ON power at breaker panel.
b. P1353ME display should fully illuminate and 
then start to blink 12:00 a.m. Time clock will not 
blink only if time has been maintained by internal 
battery.
c. Push each of the ON/OFF buttons to verify 
devices cycle on and off.
In case of unsatisfactory results, turn OFF power,
check your wiring, refer to Troubleshooting on Page 3.

9. Install front panel over wiring compartment.

The control is now ready for programming, 
see OPERATION section on Page 4.

2

3

IMPORTANT SAFETY INSTRUCTIONS

When installing and operating this Product and other associated equipment, basic safety precautions should always be followed,
including the following:

1. Read and follow all instructions.
2. This Control must be installed by a qualified electrician, according to National and Local Electrical Codes.
3. Install this control not less than 5 feet (3 meters in Canada) from inside edge of pool. USE COPPER CONDUCTORS ONLY.
4. Do not exceed the maximum ratings of individual components, wiring devices, and current carrying capacity of conductors.
5. For Control grounding, bonding, installing and the wiring of underwater lights, refer to Article 680 of the National Electrical

Code or Article 68 of the Canadian Electrical Code.

6. The Control should not operate any equipment which would cause bodily injury or property damage should it be activated unexpectedly.

READ, FOLLOW AND SAVE THIS INSTRUCTION MANUAL

PRESSURE PLATE

TERMINAL SCREW

MAKE SURE INSULATION

CLEARS PRESSURE PLATE

Figure 1

SYMPTOM

CAUSE(S)

CORRECTIVE ACTION    

1. Display will not come “ON”

1a. Jumper on back of clock is missing

Set Jumper to proper location. See

when unit is powered up?

or set incorrectly.

Pg.7 of instruction manual.

1b. Fuse on back of clock blown open.

Replace fuse with 1/8 amps fuse.
See Pg. 7 of instruction manual.

1c. Power to clock not present.

Check connections to clock.
Check circuit breakers.

2. Freeze protection circuit not 

2a. Freeze Probe (P/N 178PA28A)

Install Intermatic freeze probe. See

working?

not installed or bad.

Pg. 7 of instruction manual.

2b. Clock programming not setup.

Setup freeze programming. See
Pg. 7 of instruction manual.

3. Unit does not turn “ON” or

3a. Internal ON/OFF Times have 

Setup ON/OFF programming. See

“OFF” at desired times?

not been defined.

Pg.’s 24-27 of instruction manual.

3b. ON or OFF time is in override mode.

Cycle through programming menu.
See Pg.’s 24-27 of instruction 
manual.

3c. Clock is in Freeze protection

Review programming menu. See

Countdown Mode.

Pg.’s 29 & 33 of instruction manual.

4. Display continues to blink ON 

4a. Power to clock was interrupted long 

Set time of day on clock.See Pg. 23 

and OFF?

enough to loose time of day.

of instruction manual.

4b. Clock still in programming mode.

Press “ENTER KEY” or wait 1
minute for clock to time out.

5. Fireman switch not working?

5a. Fireman switch wires not hooked up

Connect fireman switch wires to

correctly from heater.

clock. See Pg. 7 of instruction
manual.

5b. Fireman switch programming not

Program fireman switch settings.

defined.

See Pg. 28 of instruction manual.

FLTR

PUMP

2

PUMP

1

HTR

SPA

JETS

AIR

CLNR

LITE 1

LITE 2

HIGH

LOW

AUX 1

AUX 2

AUX 3

W/FA

External Wired Remote Accessory
Part Number 133PE1484A 
(not included with all models)
The New Intermatic Wired Remote 
Control allows you to control the
P1353ME  from a remote 
location. Included with the Wired
Remote Control is a label 
arrangement allowing you to identify 
each button specific to your pool or spa equipment
pad. The new wired remote control comes standard
with 100 foot of cable and is designed to slip fit into
any standard 1 1/2” conduit adapter. This remote works
in conjunction with the P1353ME and displays feedback
information on the present state of the pool or spa
equipment pad. For more information refer to instruc-
tions provided with the accessory.

Freeze Probe Accessory 
Part Number 178PA28A
(not included with all models)

The New Intermatic Freeze
Probe allows you to protect
your pool or spa equipment
during an unexpected freeze
condition. The freeze probe
comes with a 10 foot cable
and  plugs into the back of the
P1353ME. The P1353ME can
be programmed to turn on

each or all-individual loads at any desired
outside temperature.
Heater Protection (Fireman) Switch is
standard with each Digital Time Clock.
It comes standard with a Fireman Switch
connection for your pool or spa heater.
Simply connect the two wires from your
heater thermostat to the back of the
P1353ME. The fireman switch is only 
associated with circuit one on the P1353ME,
therefore the filter pump should be 
connected to circuit one. Program the time
desired for the cool down period and the
P1353ME will take over.
For more details, refer to instruction manual.

Отзывы: