INSTALLATION INSTRUCTIONS

Description:

The passive infrared sensors work by detecting the difference between heat emitted from the human body in motion and the background space. 

The sensor switch can turn a load ON and hold it as long as the sensor detects occupancy. After no motion is detected for the set time delay, the 

load turns OFF automatically. The sensor switch has one relay (equal to single pole switch), it also includes Auto Set and Walk Through features.

Coverage Area:

The coverage range of the sensor switch is specified and illustrated in Figure 1. Large objects and some transparent barriers like glass windows 

will obstruct the sensor’s view and prevent detection, causing the light to turn off even though someone is still in the detection area.

LOCATION/MOUNTING

Since this device responds to temperature changes, care should be taken when mounting the device. DO NOT mount directly above a heat 

source, in a location where hot or cold drafts will blow directly on the sensor, or where unintended motion will be within sensor’s field-of-view.

INSTALLATION

  1. Connect lead wires as shown in WIRING DIAGRAM (see Figure 2): Black lead to Line (Hot), Red lead to Load wire, Green lead to Ground.

  2. Gently position wires in wall box, attach sensor switch to the box.

  3. Mount device “TOP” up. 

  4. Restore power at circuit breaker or fuse, wait 

three

 minutes.

  5. Remove the small cover plate. (Illustrated as Figure 3.)

  6. Locate the adjustment knobs on the control panel to perform test and adjustment. (Illustrated as Figure 4.)

  7. Replace the small cover plate after testing and adjustment.

  8. Attach the wallplate.

NOTE: If twist on wire connector is provided, use to join one supply conductor with one 16 AWG device control lead.

ADJUSTMENT

Band Switch

Time Delay Knob

Default position: 15 Seconds (Test mode)

Adjustable: from 15 Seconds to 30 Minutes (clockwise)

Sensor Sensitivity Range Knob

Default position: Center at 65%

Adjustable: 30% (Position 1) to 100% (Position 4)

Note: Turn clockwise for larger rooms. Turn counter clockwise to avoid false alerts in smaller rooms or near doorway or heat 

source.

Back to factory default (daylight):

Set the Band Switch to VAC, press and hold the Manual ON/OFF Button for 6 seconds until the Load turns on, continue 

holding the button for another 5 seconds until the Load turns off, then release the button and set the Band switch to OCC or 

AUTO mode, it confirms that the sensor switch has reset to factory default.

OPERATION

The Sensor Switch is programmed independently for any Mode (AUTO, OCC or VAC) as referred to the Band Switch position 

under the control panel cover. Some might call the Vacancy mode as “Manual ON Occupancy Mode”.

Manual On/Off Button:

By pushing the Control Panel Cover, the load can be turned ON/OFF under either OCC or VAC mode. (Illustrated as Figure 5) 

There is a 5 seconds re-trigger delay between ON and OFF.

Turning On the load under Occupancy Mode:

Load will turn ON once occupancy is detected.

Turning On the load under Vacancy Mode:

Manual ON/OFF Button has to be pushed to turn On the Load.

Automatic Turning Off the load:

Under any Mode, the sensor keeps the Load ON until no motion is detected and the set time delay, Loads will turn Off automatically.

Manual Turning Off the Load:

By pushing the Manual ON/OFF Button, the Load can be turned OFF under any mode. Under AUTO/OCC Mode, the Load cannot automatically 

turn On 5 mins after the last motion is detected.

Auto Set Occupancy Mode:

Automatically set the time delay between 7 to 30 minutes based on occupancy patterns. Auto set behavior starts after the time delay knob is turned away 

from Test Mode, also including the walk-through mode.

Walk-Through Mode:

During walk-through mode, the Load automatically turns ON and then turns OFF 2.5 minutes later, after an occupancy moment of 30 seconds. If motion 

is detected within the first 30 seconds and in the coming 2.5 minutes, Auto Set Occupancy Mode applies.

Occupancy / Vacancy

(2-IN-1)

Sensor Switch

MODEL: IOS-DSR

Ratings:

Incandescent / Tungsten: 800W-120VAC

Fluorescent / Ballast:  800VA-120VAC 

1600VA-277VAC

Motor: 1/4HP-120VAC

Time Delay: 15 Sec to 30 Min

Light Level: 30 Lux--Daylight

Operation Temperature: 32˚F--131˚F / 0-55˚C

No minimum Load required.

Figure 3

Figure 2

Mode

Position

Description

React to the pushbutton

AUTO

LEFT

Auto Set Occupancy Mode: 

Automatic ON Automatic OFF after 

digital auto set delay time, including 

walk-through Mode

Manually toggles ON / OFF 

the load.

OCC

Center

Occupancy Mode:

Automatic ON automatic OFF 

after set 

time delay.

Manually toggles ON/OFF 

the load.

VAC

RIGHT

Vacancy Mode: Manual ON only auto-

matic OFF after set time delay

Manually toggles ON/OFF 

the load.

Figure 4

Figure 5

IOS-DSR

Neutral

White

Hot

Black

Ground

Green

Load

Red

Load

Wiring Diagram

Control Panel Cover

LED Indicator

AUTO   OCC   VAC

TIME

TEST

10

20

30

Min

Min

Min

RANGE

3

2

Mounting Yoke

Fresnel Lens

 AUTO  OCC  VAC

4

1

(Push-button)

Risk of Fire, Electrical Shock or Personal Injury

 

•  Turn OFF power at circuit breaker or fuse and test that the power is OFF before wiring.

  •  To be installed and/or used in accordance with appropriate electrical codes and regulations.

  •  If you are not sure about any part of these instructions, consult a qualified electrician.

  •  Use this device only with copper or copper clad wire. 

 • 

INDOOR USE ONLY

WARNING

Maximum: 1200 sq.ft.

40'

Top View

20'

10'

20'

10'

20'

5'

4'

180˚ Field of View

Figure 1