background image

•  Disconnect power at the circuit breaker(s) or disconnect switch(es) before beginning 

installation or servicing.

•  More than one circuit breaker or disconnect switch may be required to de-energize the 

equipment before servicing.

•  Do not use the manual off position of the timer for equipment servicing. Always discon-

nect the power at the circuit breaker(s) or disconnect switch(es).

•  Use COPPER conductors ONLY.

•  For 40 amp loads, use #8 AWG wire, rated 90˚C min.

•  Wire in accordance with national and local electrical code requirements. 

GM40 Series

  

General Purpose 

Multi-Voltage Commercial 

DPDT Time Switch

        WARNING

Risk of Fire or Electric Shock

•  Rotate timer dial clockwise only.

        CAUTION

Risk of Damage to Timer

1

U.S. Patent #6,563,2371.

UL TYPE 3R Enclosure

MAXIMUM CONTACT RATINgs PER POLE: 

N.O. Contacts:
    40A Resistive @ 120~277VAC
  1HP, 16FLA, 90LRA @ 120VAC

    2HP, 12FLA, 52LRA @ 208~277VAC

    30A Ballast @ 120VAC

    20A Ballast @ 277VAC

    15A Tungsten @ 120VAC
    300VA Pilot Duty 120~240VAC
N.C. Contacts:
    30A Resistive @ 120~277VAC
  1HP, 12FLA, 30LRA @ 120VAC

    2HP, 10FLA, 30LRA @ 240VAC

    2A Tungsten @ 120VAC

    10A Ballast @ 277VAC

WIRINg CONNECTIONs:  

Screw box lug terminals. Up to one #8 AWG

 Wire.

ENVIRONMENTAL RATINgs:

Operating Temperature Range:  

–40°F to 131°F (–40°C to 55°C)

Operating Humidity: 0 - 95% RH non-condensing

ENCLOsURE DIMENsIONs:  

8.795” x 6.631” x 2.935” (H x W x D)

sHIPPINg WEIgHT:

 3 lbs.

Agency Approvals:

 UL Listed

INSTALLATION

Note: For outdoor locations, raintight or wet local conduit 

hubs that comply with requirements of UL 514B (standard 

for fittings for conduit and outlet boxes) must be used.

1.  Open door and then remove interior protective   

  cover by releasing spring clip on bottom.

2. Remove timer mechanism by releasing spring clip  

  on bottom.

3. Select knockouts to be used. Remove inner 1/2”  

  knockout by inserting a screwdriver in the slot and  

  carefully punch knockout loose. Remove slug. If 3/4”  

  knockout is required, remove the outer ring  with pliers  

  after removing the 1/2” knockout. Smooth edges with  

  knife if necessary.

4.  Place enclosure in desired mounting location and 

  mark the three mounting holes (refer to diagram).  

  Start by placing set screw on top and attaching  

  enclosure over keyhole; then screw in remaining  

  two screws on bottom.

5.  Connect conduit hubs to conduit before connecting the  

  hubs to the enclosure. After inserting hubs into enclo- 

  sure, carefully tighten hub lock nut. Do not over-torque.

6. Verify input voltage selection. Refer to DIP switch  

  diagram for desired input voltage.

7. Wire in accordance with National and Local Codes  

  (see wiring diagrams).

8.  Grounding: Terminate all ground wires to ground  

  lug on bottom of enclosure.

9. Replace interior protective cover.

ON

ON

ON

ON

120VAC

OFF

OFF

OFF

OFF

277VAC (Default)

OFF

ON

OFF

ON

208~240VAC

INPUT VOLTAgE DIP sWITCH sETTINg:

1. Do not apply power to the gM40 prior to setting correct 

  Input Voltage DIP switch.

2. Determine the input voltage which will be applied to the GM40 

  (i.e. L1 and L2/N terminals, see wiring diagrams).

3. Set the DIP Switch according to the diagram below. 

NOTE: 

Unit is shipped with DIP Switches set for 277VAC Input Voltage.

Ground Lug

2-1/2”

6-1/8”

TImer Mechanism

Step 2

Interior

Protective

Cover

Step 1

Отзывы: