background image

Specifications

Input Voltage:

 120-277 VAC, 60 Hz

Power Consumption:

 7 W MAX

Switch Configuration:

 SPST x 4. See wiring diagrams in this manual. 

Switch Ratings:

 

Rating

Load Type

Voltage

Frequency

30 A

Resistive

120-240 VAC

60 Hz

20 A

Resistive

28 VDC

30 A

Inductive

120-240 VAC

60 Hz

20 A

Magnetic Ballast

120-277 VAC

60 Hz

10 A

Electronic Ballast

120/277 VAC

60 Hz

5 A

Tungsten

120-277 VAC

60 Hz

1 HP

Motor

120 VAC

60 Hz

2 HP

Motor

240 VAC

60 Hz

Events:

 Time switch can support up to 48 fixed ON and 48 fixed OFF events.

Clock Backup:

 100-hour Supercapacitor

Wire Size:

 AWG #14-#8

Minimum ON or OFF time:

 1 minute

Maximum ON or OFF time: 

Indefinite

Shipping Weight:

 2.5 lb. (1.1 kg)

Enclosures:

 Rainproof Type 3R indoor/outdoor lockable metal enclosure (ET2745CR), Type 1 indoor lockable metal enclosure 

(ET2745C), Rainproof Type 3R indoor/outdoor lockable plastic enclosure (ET2745CP)

Knockouts:

 Combination 1/2-3/4 in. size, 1 on rear and each side, 2 on bottom

INTERMATIC INCORPORATED

7777 Winn Road 

SPRING GROVE, ILLINOIS 60081-9698

www.intermatic.com

158--01733

LIMITED TWO-YEAR WARRANTY

If within the warranty period specified, this product fails due to a defect in material or workmanship, Intermatic Incorporated will repair or replace it, 

at its sole option, free of charge. This warranty is extended to the original household purchaser only and is not transferable. This warranty does not 

apply to: (a) damage to units caused by accident, dropping or abuse in handling, acts of God or any negligent use; (b) units which have been subject 

to unauthorized repair, opened, taken apart or otherwise modified; (c) units not used in accordance with instructions; (d) damages exceeding the 

cost of the product; (e) sealed lamps and/or lamp bulbs, LED’s and batteries; (f) the finish on any portion of the product, such as surface and/or 

weathering, as this is considered normal wear and tear; (g) transit damage, initial installation costs, removal costs, or reinstallation costs.
INTERMATIC INCORPORATED WILL NOT BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES. SOME STATES DO NOT ALLOW THE 

EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATION OR EXCLUSION MAY NOT APPLY 

TO YOU. THIS WARRANTY IS IN LIEU OF ALL OTHER EXPRESS OR IMPLIED WARRANTIES. ALL IMPLIED WARRANTIES, INCLUDING THE 

WARRANTY OF MERCHANTABILITY AND THE WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE, ARE HEREBY MODIFIED TO EXIST 

ONLY AS CONTAINED IN THIS LIMITED WARRANTY, AND SHALL BE OF THE SAME DURATION AS THE WARRANTY PERIOD STATED ABOVE. 

SOME STATES DO NOT ALLOW LIMITATIONS ON THE DURATION OF AN IMPLIED WARRANTY, SO THE ABOVE LIMITATION MAY NOT APPLY TO 

YOU.
This warranty service is available by either (a) returning the product to the dealer from whom the unit was purchased or (b) completing a warranty 

claim online at www.intermatic.com. This warranty is made by: Intermatic Incorporated, Customer Service 7777 Winn Rd., Spring Grove, Illinois 

60081-9698.  For warranty service go to:  http://www.Intermatic.com or call 815-675-7000.

Содержание ET2745

Страница 1: ...environment This equipment generates uses and radiates radio frequency energy and if not installed and used in accordance with instructions may cause harmful interference to radio communications Oper...

Страница 2: ...the rear If a 3 4 inch knockout is needed remove the 1 2 inch knockout first then the 3 4 knockout 6 Place the enclosure in the desired location providing space for the enclosure door to swing open fu...

Страница 3: ...ON FOR TWO CONTACTOR CONTROLS COM4 NO 4 COM3 NO 3 COM2 NO 2 COM1 NO 1 AC IN TIMER POWER CIRCUIT 4 CIRCUIT 3 CIRCUIT 2 CIRCUIT 1 L2 N L1 OUTPUT CONFIGURATION PUL CIRCUIT 1 AND 2 OUTPUT CONFIGURATION PU...

Страница 4: ...te has not yet been entered the time switch will go to the Enter Date Mode Setting Date Follow this procedure below to set the date and time in the time switch NOTE If necessary hold or to scroll thro...

Страница 5: ...o save Go to step 9 MON FRI Press DAY once and then press ENTER NEXT to save Go to step 9 SAT SUN Press DAY twice and then press ENTER NEXT to save Go to step 9 SET EACH DAY INDIVIDUALLY On the displa...

Страница 6: ...day event to end 18 Press ON OFF buttons to remove each circuit not affected by this event All circuits are initially included with the event If the LOAD icon for the circuit is displayed then this ci...

Страница 7: ...TXT where xx is the schedule number selected in the previous step 6 After the file is written REMOVE is shown on the display 7 Remove the USB memory stick and the time switch will advance to the next...

Страница 8: ...o units caused by accident dropping or abuse in handling acts of God or any negligent use b units which have been subject to unauthorized repair opened taken apart or otherwise modified c units not us...

Отзывы: