Initial Setup

The following sections provide instructions for the initial setup of the time switch.

Setting The Output Configuration 

The time switch output configuration enables users to control multiple loads simultaneously (SIM), independently (IND), or with a 
2-second pulse (PUL). Output circuits are configured in pairs; circuits #1 and #2 first, followed by circuits #3 and #4.
In PUL mode, an ON event or manual override, causes circuit #1 to turn ON for two seconds, then OFF. An OFF event, or manual 
override, causes circuit #2 to turn ON for two seconds, then OFF.

NOTE:

 The output configuration setup can only be accessed at initial startup of the unit or after a “Clearing Time Switch Memory” 

operation. Follow this procedure to set the output configuration.
1.  Activate power to the time switch. The display shows 

IND

, the 

ARROW

 icon above the ENTER/NEXT button and the 

LOAD

 

icons for circuit #1 and circuit #2 turn on.

NOTE:

 If the display does not show 

IND

 the output configuration is already set and a “Clearing Time Switch Memory” operation 

must be performed. 

2.  Press + or - to scroll to the desired output configuration.
3.  Press ENTER/NEXT to save the setting for the first two circuits.
4.  The display now shows 

IND

, the 

ARROW

 icon above the ENTER/NEXT button and the 

LOAD

 icons for circuit #3 and circuit #4 

turn on.

5.  Press + or - to scroll to the desired output configuration.
6.  Press ENTER/NEXT to save the setting for the last two circuits.
7.  The output configuration is now completed.

Programming Overview

The steps to program the time switch include setting the current date, time, fixed events, DST, and holiday events, setting the time 
switch’s operation to AUTO mode, ENERGY SAVER mode or MANUAL mode (only MANUAL mode will appear if there are no 
scheduled events) and read or write an event schedule from a USB memory stick.

NOTE: 

If the time switch is left inactive for five minutes in a programming mode, it will return to the AUTO mode screen (

AUTO

 icon 

turned on). If no scheduled events are programmed, the time switch will return to MANUAL mode. If the date has not yet been 
entered, the time switch will go to the Enter Date Mode.

Setting Date

Follow this procedure below to set the date and time in the time switch. 

NOTE:

 If necessary, hold + or - to scroll through the digits rapidly. 

1.  Press MODE to scroll through the mode selections until 

SET

 and 

DATE

 icons appear at the top of the display. The month 

flashes.

2.  Press + or - to select the current month and then press ENTER/NEXT. The day of the month flashes.
3.  Press + or - to select the current day of the month, and then press ENTER/NEXT. The year flashes.
4.  Press + or - to enter the current year, and press ENTER/NEXT. The month will flash again.
5.  Press MODE to move to the next mode selection.

Setting Time

Follow the procedure below to set the time in the time switch. 

NOTE:

 If necessary, hold + or - to scroll through the digits rapidly.

1.  Press MODE to advance to the Set Clock mode selection if this selection is not already active. The 

SET

 and 

TIME

 icons appear 

on the display and a flashing 12:00 AM appears (if clock has not been set).

2.  Press + or - to select the current time (be aware of the AM/PM setting) NOTE: Seconds can be set to 00 by pressing ENTER/

NEXT.

3.  Press MODE to save the time and move to the Enable Daylight Saving Time mode selection.

NOTE:

 If the time switch programming data is to be read from a USB memory stick, refer to the “Read Time Switch Program 

Data…” section in these instructions.

Enable/Disable Daylight Saving Time and Setting Daylight Saving Time Rule

Configure the time switch to automatically adjust for Daylight Saving Time (DST). If DST does not apply to your region, disable the 
option as directed in this procedure. Follow this procedure to enable/disable the Daylight Saving Time feature, and if applicable, set 
the DST rule.
1.  Press MODE to advance to the Set DST mode selection if this selection is not already active. The 

SET

 and 

DST

 icons appear on 

the display.

2.  Press + to display ON (enable DST) or press – to display OFF (disable DST) and then press ENTER/NEXT to save.

If DST is

Then

Enabled

Go to step 3.

Disabled

Press MODE to save and exit. The procedure is complete.

3.  Press + or - to scroll to the desired DST rules for your area.

NOTE:

 The DST rules are US2007 (US rules), MX1986 (Mexico rules), and CUSTOM (user-defined start/end dates).

Содержание ET2745

Страница 1: ...environment This equipment generates uses and radiates radio frequency energy and if not installed and used in accordance with instructions may cause harmful interference to radio communications Oper...

Страница 2: ...the rear If a 3 4 inch knockout is needed remove the 1 2 inch knockout first then the 3 4 knockout 6 Place the enclosure in the desired location providing space for the enclosure door to swing open fu...

Страница 3: ...ON FOR TWO CONTACTOR CONTROLS COM4 NO 4 COM3 NO 3 COM2 NO 2 COM1 NO 1 AC IN TIMER POWER CIRCUIT 4 CIRCUIT 3 CIRCUIT 2 CIRCUIT 1 L2 N L1 OUTPUT CONFIGURATION PUL CIRCUIT 1 AND 2 OUTPUT CONFIGURATION PU...

Страница 4: ...te has not yet been entered the time switch will go to the Enter Date Mode Setting Date Follow this procedure below to set the date and time in the time switch NOTE If necessary hold or to scroll thro...

Страница 5: ...o save Go to step 9 MON FRI Press DAY once and then press ENTER NEXT to save Go to step 9 SAT SUN Press DAY twice and then press ENTER NEXT to save Go to step 9 SET EACH DAY INDIVIDUALLY On the displa...

Страница 6: ...day event to end 18 Press ON OFF buttons to remove each circuit not affected by this event All circuits are initially included with the event If the LOAD icon for the circuit is displayed then this ci...

Страница 7: ...TXT where xx is the schedule number selected in the previous step 6 After the file is written REMOVE is shown on the display 7 Remove the USB memory stick and the time switch will advance to the next...

Страница 8: ...o units caused by accident dropping or abuse in handling acts of God or any negligent use b units which have been subject to unauthorized repair opened taken apart or otherwise modified c units not us...