at the time of installation, allowing the CO alarm to 
communicate with that specific control panel. 

Testing 

Note: 

This unit is sealed. The cover is not removable. 

 WARNING: 

The control panel must be placed into 

sensor test mode while conducting any tests. Placing the 
control panel into sensor test mode for all testing helps to 
protect against false alarms and unintentional central station 
reporting. 

Due to the loudness of the alarm, we suggest that you place 
your fingers over the sounder vent while testing your alarm. 

 Caution: 

Continuous exposure to the high sound level 

of this alarm over an extended period of time may cause 
hearing loss. 

The CO alarm provides three test modes: 

• 

Normal CO 

alarm 

test. 

Conducts an internal self-test and 

tests the sounder. 

• 

RF communication test. 

Tests the communication path 

with the control panel. 

• 

CO sensor functional gas test. 

Tests the functional 

operation of the CO sensing element. 

Normal CO alarm test 

1.  Wait at least 10 minutes after installation to test the CO 

alarm. 

2.  Make sure the green Power LED is flashing for normal 

operation. 

3.  Set the control panel to sensor test mode. 

4.  Press and hold the Test/Hush button until the unit beeps 

once (approximately 1 second), and then release the 
button. If the unit is operating properly, you will hear four 
quick beeps, followed by 5 seconds of silence, followed by 
four quick beeps. 

5.  At the control panel, exit sensor test mode. 

Note: 

This test mode does not test communication with the 

control panel. You will receive a “Sensor Test Fail or Abort” 
message when the control panel exits sensor test mode. 

RF communication test 

This section provides general guidelines for testing the CO 
alarm with the panel. Refer to the specific panel documentation 
for complete testing details. 

Before testing, ensure that your control panel is set to sensor 
test mode. Setting your panel to sensor test mode prevents an 
alarm signal from being transmitted to the central monitoring 
station (if you have a monitored system). 

1.  Wait at least 10 minutes after installation to test the CO 

alarm. 

2.  Make sure the green Power LED is flashing for normal 

operation. 

3.  Set the control panel to sensor test mode. 

4.  Press and hold the Test/Hush button until the unit beeps 

two times (approximately 5 seconds), and then release the 
button. If the unit is operating properly, you will hear four 
quick beeps. The unit will send the RF test packets after 
the first four beeps. 

5.  The control panel will beep and display the number of RF 

packets received. 

6.  At the panel, exit sensor test mode. 

CO inspection and functional gas test 

A canned CO testing agent must be used for the CO functional 
gas test. Contact local supplier for canned CO gas 

– solo C6 or 

equivalent.  

1.  Wait at least 10 minutes after installation to test the CO 

alarm. 

2.  Make sure the green Power LED is flashing for normal 

operation. 

3.  Set the control panel to sensor test mode. 

4.  Press and hold the Test/Hush button until the unit beeps 

three times (approximately 10 seconds), and then release 
the button. The unit will enter the functional gas test mode. 
The Power LED will blink once per second while in 
functional test mode. 

5.  Apply a CO test agent to the slit as shown in Figure 7 

below. When CO is detected, the unit will activate a CO 
alarm. The unit will send RF test packets to the control 
panel when the CO alarm is activated. 

Figure 7: CO testing slit 

 

(1)  CO testing slit 

6.  The control panel will beep and display the number of RF 

packets received. 

7.  At the control panel, exit sensor test mode. 

8.  Exit functional gas test mode: 

Press and release the Test/Hush button; or a 2 minute 
timeout will automatically cause the CO to return to normal 
operating mode. 

Troubleshooting 

This information is provided to help you diagnose and solve 
various problems that may arise while configuring or using the 
wireless CO alarm. 

Unit does not power up properly or reports low battery: 

• 

Make sure the batteries are fully seated within the battery 
compartment and the polarity is correct. 

• 

Make sure that all three batteries are installed. 

• 

Check the battery voltage (1.5 VDC nominal per battery). 

 

(1)

Содержание TX-6310-03-1

Страница 1: ...larms It is intended for residential indoor dwelling unit applications It is not intended for use in industrial applications WARNING After ten years from initial power up this alarm will beep two times every 30 seconds to indicate that it is time to replace the alarm Replace the alarm immediately It will not detect CO in this condition To help identify the date to replace the alarm an area has bee...

Страница 2: ...n rooms areas e g hallways landings remote from the fuel burning appliance should be located relatively close to the breathing zone of the occupants Figure 2 Recommended locations 1 Dining 2 Kitchen 3 Bedroom 4 Bedroom 5 Living room 6 Bedroom Locations to avoid Improper location can affect the sensitive electronic components in this alarm To avoid causing damage to the unit to provide optimum perf...

Страница 3: ...mounted To mount the alarm 1 Slide the body off of the mounting plate Place the mounting plate in the desired location and mark the location of the two mounting holes Orient the mounting plate vertically or horizontally as shown in the following figures Figure 5 Vertical mounting Figure 6 Horizontal mounting 1 Mounting hole 2 Mounting latch 3 Alarm procedure label 4 Mounting hole 2 Insert the two ...

Страница 4: ...the central monitoring station if you have a monitored system 1 Wait at least 10 minutes after installation to test the CO alarm 2 Make sure the green Power LED is flashing for normal operation 3 Set the control panel to sensor test mode 4 Press and hold the Test Hush button until the unit beeps two times approximately 5 seconds and then release the button If the unit is operating properly you wil...

Страница 5: ...esentative UTC Fire Security B V Kelvinstraat 7 6003 DH Weert Netherlands Made in China Certification 0359 EN EN 50291 1 2010 Product warnings and disclaimers THESE PRODUCTS ARE INTENDED FOR SALE TO AND INSTALLATION BY QUALIFIED PROFESSIONALS UTC FIRE SECURITY CANNOT PROVIDE ANY ASSURANCE THAT ANY PERSON OR ENTITY BUYING ITS PRODUCTS INCLUDING ANY AUTHORIZED DEALER OR AUTHORIZED RESELLER IS PROPER...

Страница 6: ...cially in cold weather It is therefore possible that outdoor conditions could be a factor in triggering domestic carbon monoxide alarms b There may be another source of carbon monoxide emission inducing the alarm for example a large amount of tobacco smoke town gas emission from a smouldering fire c The alarm may be induced by other substances Some sensors may respond to common household substance...

Страница 7: ...u like symptoms 200 Dizziness and headache within 2 3 hours 400 Nausea frontal headache drowsiness confusion and rapid heart rate Risk to life after over 3 hours of exposure 800 Severe headache convulsions vital organ failure Death possible within 2 3 hours The relationship between the CO concentration and the duration of exposure can be calculated for a given COHb by parameterising the above fact...

Страница 8: ...8 25 P N 3102145 ML REV F ISS 11MAR19 http www euro who int __data assets pdf_file 0020 123059 A QG2ndEd_5_5carbonmonoxide PDF Contact information For servicing or contact information see interlogix com ...

Страница 9: ...ill silence the end of life signal for up to three days After three days the unit will resume end of life chirps Hush mode will silence the alarm ten times or up to 30 days After 30 days the unit can no longer be hushed Replace the CO alarm immediately The unit will not respond to CO Trouble service alarm Red Alarm LED flashes every 30 s One quick beep every 30 s Unit is in trouble condition Troub...

Страница 10: ...ontiert werden Es wird empfohlen auf jeder Etage einen Melder zu installieren Achten Sie bei der Auswahl des Montageortes darauf dass der Melder von allen Schlafbereichen aus gehört werden kann Wenn Sie nur einen CO Melder in Ihrem Haus installieren montieren Sie ihn in der Nähe der Schlafzimmer nicht im Keller oder Heizungsraum Montieren Sie den Melder außerhalb der Reichweite von Kindern Kinder ...

Страница 11: ...Fenstern oder Bereichen die dem Wetter ausgesetzt sind Installieren Sie den Melder nicht in stehenden Lufträumen wie Gewölbedecken oder Giebeln wo das CO den Melder nicht rechtzeitig erreicht Installieren Sie den Melder nicht in der Nähe von großen Deep Cell Batterien Autobatterien Große Akkus geben Emissionen ab die die Leistung des Melders beeinträchtigen können Bedecken Sie nicht die Lüftungsöf...

Страница 12: ...ligen Einbruchmeldezentrale Anmelden des CO Melders im Funkempfänger der Einbruchmeldezentrale 1 Schalten Sie die Einbruchmeldezenttrale in den Programmiermodus 2 Rufen Sie das Menü Learn Add Sensors Melder einlernen hinzufügen auf 3 Wählen Sie die Nummer des gewünschten Melders 4 Lösen Sie den Wandsabotagekontakt aus indem Sie das Meldergehäuse von der Montageplatte nehmen 5 Wenn Sie die Einbruch...

Страница 13: ...ittel verwendet werden Wenden Sie sich an Ihren lokalen Händler um eine CO Gasdose zu erhalten Solo C6 oder entsprechend 1 Warten Sie mindestens 10 Minuten nach der Installation um den CO Melder zu testen 2 Stellen Sie sicher dass die grüne Betriebs LED für den normalen Betrieb blinkt 3 Schalten Sie die Einbruchmeldezentrale in den Meldertestmodus 4 Drücken und halten Sie die Test Hush Taste bis d...

Страница 14: ... JURISTISCHE PERSONEN DIE UNSERE PRODUKTE ERWERBEN SOWIE AUTORISIERTE HÄNDLER ODER AUTORISIERTE WIEDERVERKÄUFER ÜBER DIE ERFORDERLICHE QUALIFIKATION UND ERFAHRUNG VERFÜGEN UM BRANDSCHUTZ ODER SICHERHEITSTECHNISCHE PRODUKTE ORDNUNGSGEMÄSS ZU INSTALLIEREN Weitere Informationen zu Haftungsausschlüssen sowie zur Produktsicherheit finden Sie unter https firesecurityproducts com policy product warning o...

Страница 15: ...in Innenräumen auftreten Beispielsweise könnte dies durch ein Fahrzeug in der Nähe oder bei starker Luftverschmutzung durch Verkehr bei kaltem Wetter eintreten Es könnte daher sein dass ein Kohlenmonoxidalarm im Innenraum durch äußere Umstände ausgelöst wird b Es gibt auch andere Quellen von Kohlenmonoxidemissionen die den Alarm auslösen können beispielsweise übermäßiger Tabakrauch Stadtgas Emissi...

Страница 16: ...ichtszustand erreicht ist hängt von mehreren Faktoren ab z B die Lungenaktivität und die alveolare Kapillarübertragung kardiale Parameter die Hämoglobinkonzentration im Blut Luftdruck Sauerstoff und Kohlendioxidkonzentration in der eingeatmeten Luft die zwei wichtigsten Faktoren zur Ermittlung der COHb Konzentration sind jedoch die CO Konzentration und die Dauer der Einwirkung Die Wirkung verschie...

Страница 17: ...los Dadurch wird der hörbare Piepton für 8 bis 11 Stunden ausgesetzt um die Batterien ungestört ersetzen zu können Anzeige für das Ende der Melder lebens dauer Rote Alarm LED blinkt zwei Mal alle 30 Sekunden Zwei schnelle Tonsignale alle 30 Sekunden Ende der CO Melderlebensdauer Störungs bedingung Störungston signal alle 60 Sekunden Drücken Sie die Test Hush Taste und lassen Sie sie los Dadurch wi...

Страница 18: ... les systèmes de ventilation et d évacuation appropriés Emplacement du détecteur Les détecteurs de CO doivent être montés à l intérieur ou à proximité des chambres et des salles de séjour Nous vous recommandons d installer un détecteur à chaque étage de votre domicile Lorsque vous choisissez les lieux d installation assurez vous que vous pouvez entendre l alarme dans toutes les chambres à coucher ...

Страница 19: ... ou d ouvertures de ventilation forcée non forcée Ne l installez pas sur des surfaces métalliques Évitez de placer l appareil dans des zones contenant une grande quantité de métal ou de fils électriques N installez pas le dispositif à proximité de ventilateurs de plafond de portes de fenêtres ou de zones directement exposées aux intempéries Ne l installez pas dans des espaces sans circulation d ai...

Страница 20: ...a programmation reconnaissance de l unité dans la mémoire de la centrale Reportez vous à la documentation de la centrale pour obtenir des informations complètes sur la programmation Pour ajouter le détecteur de CO dans la mémoire de la centrale 1 Placez la centrale en mode de programmation 2 Accédez au menu Apprentissage Ajouter des détecteurs 3 Sélectionnez le numéro du détecteur souhaité 4 Décle...

Страница 21: ... de CO solo C6 ou équivalent 1 Après l installation attendez au moins 10 minutes avant de tester le détecteur de CO 2 Assurez vous que le voyant d alimentation vert clignote pour indiquer un fonctionnement normal 3 Mettez la centrale en mode test du détecteur 4 Appuyez sur le bouton Test Silence et maintenez le enfoncé jusqu à ce que l unité émette trois bips environ 10 secondes puis relâchez le b...

Страница 22: ...formations supplémentaires sur les garanties et la sécurité rendez vous à l adresse https firesecurityproducts com policy product warning ou scannez le code QR Directives européennes UTC Fire Security déclare par la présente que cet appareil est conforme aux exigences applicables et aux dispositions de toutes les règles et règlements applicables y compris mais sans s y limiter de la Directive 2014...

Страница 23: ...déclenchement des alarmes de monoxyde de carbone domestiques b Une autre source d émission de monoxyde de carbone peut déclencher l alarme par exemple une grande quantité de fumée de tabac le gaz de ville l émission d un feu couvant c L alarme peut être déclenchée par d autres substances Certains détecteurs peuvent réagir aux substances domestiques communes telles que les solvants Les instructions...

Страница 24: ...ion ppm Effets sur adultes 100 Légers maux de tête nausée fatigue symptômes pseudo grippaux 200 Étourdissements et maux de tête dans les 2 3 heures 400 Nausées maux de tête frontal somnolence confusion et fréquence cardiaque rapide Risque vital après plus de 3 heures d exposition 800 Maux de tête sévères convulsions défaillance d un organe vital Mort possible dans les 2 3 heures Le rapport entre l...

Страница 25: ... bips rapides toutes les 30 s Fin de vie de l alarme de CO Condition de défaut Émission de bips de défaut toutes les 60 s Appuyez sur le bouton Test Silence puis relâchez le Le signal de fin de vie sera désactivé pendant trois jours Passé ce délai il sera réactivé Le mode silence désactivera l alarme dix fois ou 30 jours maximum Passé ce délai le signal ne pourra plus être désactivé Remplacez immé...

Отзывы: