Interlogix TruPortal TP-ADD-1DIP Скачать руководство пользователя страница 7

TruPortal IP-based Single Door Controller Quick Reference 

7

The following table lists the items shown in 

Figure 10

.

Callout

Description

Wire Color

Connector J1

1

Reader 1 (access)

2

+12 VDC

Red

3

Ground (0V)

Black

4

Reader Data 0

Green

5

Reader Data 1

White

6

Door DO (green LED)

Orange

7—9

Not used

10

Drain wire (cable shield)

[1]

Connector J2

11

Door DI (DC+)

12

Door DI Return (DC-)

13

Exit DI (REX+)

14

Exit DI Return (REX-)

15

Door Contact

[2]

16

REX 

[2]

17

1K EOL resistors typical

[3]

Connector J3

18

Reader 2 (egress)

19

+12 VDC

Red

20

Ground (0V)

Black

21

Reader Data 0

Green

22

Reader Data 1

White

23

Door DO; green LED

Orange

24—26

Not used

27

Drain wire (cable shield). See footnote 1

1. Use 20 AWG shielded cable and terminate drain wire 

(cable shield) at enclosure (see 

Figure 3

 on page 4). 

Use plenum-rated cable if cable will be run above a 
false ceiling in the air circulation space.

2. Door or Exit DIs Normally Open or Closed.
3. Include resistors for Wiegand Four-State interface. 

For Wiegand Two-State interface, omit resistors.

Callout

Description

Wire Color

Figure 10: Wiegand Wiring

Содержание TruPortal TP-ADD-1DIP

Страница 1: ...TruPortal IPSDC board only Capable of controlling one door No enclosure or readers included Installation Procedure To install the IPSDC perform the procedures described in the following sections in t...

Страница 2: ...stom Wiegand Card Format 1 1 Use the System Administration Card Formats page in the TruPortal User Interface to configure Wiegand card formats Set SW1 1 to OFF and set SW1 2 thru SW1 4 to ON SW2 Set a...

Страница 3: ...quirements Wattage Calculator worksheet included on the product disc for strike type and size 6 Strike voltage selection Jumper pins 1 and 2 for 24 VDC strikes jumper pins 2 and 3 for 12 VDC strikes 7...

Страница 4: ...the cable through ferrite provided as shown in Figure 5 Note Ferrite must be installed inside of the enclosure Figure 3 Using Shielded Cable and Drain Wire Figure 4 Wiring Earth Ground Figure 5 Instal...

Страница 5: ...ake sure that the PC is not blocked from connecting to IP address 192 168 6 6 If the workstation normally connects to the Internet via a proxy the proxy settings in the browser may need to be adjusted...

Страница 6: ...nclosure tamper W5 4 Strike Voltage Select W2 14 Boot Mode switch SW4 5 Custom Wiegand Card Format DIP switch SW1 15 Hardware Reset switch SW5 6 Reader Out Egress J3 16 Shutdown Request switch SW6 7 D...

Страница 7: ...REX 2 17 1K EOL resistors typical 3 Connector J3 18 Reader 2 egress 19 12 VDC Red 20 Ground 0V Black 21 Reader Data 0 Green 22 Reader Data 1 White 23 Door DO green LED Orange 24 26 Not used 27 Drain w...

Страница 8: ...uest Normally OFF Flashes and then ON 10 D33 StrikeActivated ON during strike activation 11 D24 FACP not supported by IPSDC ON contact open 12 D25 Door Contact ON contact closed OFF contact open Flash...

Страница 9: ...ratings Door DO Reader LED 20 mA 12 VDC maximum Door strike DO relay 2A 28 VDC or 30 VAC maximum Strikes Maximum current 390 mA per strike output See Table 2 on page 2 for recommended strike models a...

Отзывы: