TruPortal IP-based Single Door Controller Quick Reference
7
The following table lists the items shown in
Callout
Description
Wire Color
Connector J1
1
Reader 1 (access)
2
+12 VDC
Red
3
Ground (0V)
Black
4
Reader Data 0
Green
5
Reader Data 1
White
6
Door DO (green LED)
Orange
7—9
Not used
10
Drain wire (cable shield)
[1]
Connector J2
11
Door DI (DC+)
12
Door DI Return (DC-)
13
Exit DI (REX+)
14
Exit DI Return (REX-)
15
Door Contact
[2]
16
REX
[2]
17
1K EOL resistors typical
[3]
Connector J3
18
Reader 2 (egress)
19
+12 VDC
Red
20
Ground (0V)
Black
21
Reader Data 0
Green
22
Reader Data 1
White
23
Door DO; green LED
Orange
24—26
Not used
27
Drain wire (cable shield). See footnote 1
1. Use 20 AWG shielded cable and terminate drain wire
(cable shield) at enclosure (see
Use plenum-rated cable if cable will be run above a
false ceiling in the air circulation space.
2. Door or Exit DIs Normally Open or Closed.
3. Include resistors for Wiegand Four-State interface.
For Wiegand Two-State interface, omit resistors.
Callout
Description
Wire Color
Figure 10: Wiegand Wiring