FP/FR1100/1200/2000 V6: Installation and Commissioning Manual
43
6.4.4 230 V version (FP2xxx models)
Figure 33: FP2xxx power supply and associated connections (230 V version)
1. 230 VAC
5. To M5 earth stud mounted on back panel
2. Live
6. 24 V power to ancillary fire panel equipment
3. Neutral
7. 12 V batteries
4. Earth
The Direct Online power supply PSU-2000 has been designed according to EN54-4. A
mains switch (on the bottom) is provided, as well as a battery ON/OFF switch. Three
LED’s on top of the power supply indicate the following:
- Charger On
- Battery On
- Battery fail
On top there is a 24 volt auxiliary output for other fire panel equipment.
As part of the building installation, the 230 VAC should be derived directly from a separate
group in the distribution board. This group should have a bi-polar disconnect device,
clearly marked and only used for fire detection equipment.
The recommended mains cable is 3 x 1.5 mm² (live, neutral, earth).