6 / 6
P/N 466-
2914 • REV C • ISS 15MAR19
1. Contact the command wire to ground to activate the reset
procedure.
2. The LED lights up orange for several seconds to indicate
that the “Reset Detector” command was selected.
3. The LED then starts to flash orange for several seconds.
Contact the command wire to ground again to confirm the
command. If you do not want to execute the command, let
the confirmation time elapse.
4. If you confirm the command in time, the LED stops
flashing. The detector discards all changes and switches
to the “Detector Reset” state, in which you can learn-in the
unit to the environment.
Wiring configuration for EN version
Wire(s)
Type
Assignment
Red (RD)
Supply
Supply voltage (+)
Blue (BU)
Supply
Ground (-)
Pink (PK)
Input
Command input
Black (BK), brown (BN)
Output
Intrusion
Yellow (YE), green (GN)
Output
Tampering (removal protection)
White (WH), grey (GY)
Output
Fault (external field)
Note:
See Figures 9 and 10.
Distances
Mounted on non ferromagnetic material
Approach distance
15 mm ± 3 mm
Break distance
18 mm ± 3 mm
Fault trigger distance
−3 mm ± 1 mm
Mounted on ferromagnetic material
Approach distance
30 mm ±20%
Break distance
27 mm ±30%
Fault trigger distance
29 mm ±30%
See Figure 8.
The values refer to the Y-distance relative to the learning position.
Values along the Z-axis may differ. If required they are to be
determined separately.
The distances may vary depending on the installation situation, the
magnetic code and the learning distance. Before the device is brought
into service, they are to be verified.
Specifications
Operating voltage
12 to 24 V DC
Power consumption (monitoring mode)
Approx. 5 mA (typical)
Power consumption (learn-in mode,
LED)
max. 13 mA
Permitted installation gap between
magnet and detector
5 to 12 mm
Installation offset on the sides (revolving) max. 1.5 mm
Clearance from metal components
min. 2 mm
Permitted tolerance after learn-in (radial) max. 1.5 mm
Signal output
Electronic switch
Transfer resistance (closed)
approx. 7
Ω (typical)
Transfer resistance (open)
≥10 MΩ
Electrical isolation between input and
output
min. 30 V
Permitted output current
max. 50 mA
Permitted output voltage
max. 30 V
Measurement speed
approx. 100 ms
Connection cable
LIYY 9 x 0.14
mm² copper
tin
−plated
Cable conductors
See Table 1
Cable diameter
Ø 5.8 mm
Cable length
Up to 10 m
Contact dimensions
80 x 18 x 20 mm
Magnet dimensions
80 x 15 x 20 mm
Temperature range
-
40°C to +70°C
Regulatory information
Manufacturer
PLACED ON THE MARKET BY:
UTC Fire & Security Americas Corporation, Inc.
3211 Progress Drive, Lincolnton, NC, 28092, USA
AUTHORIZED EU REPRESENTATIVE:
UTC Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, Netherlands
Product warnings
and disclaimers
THESE PRODUCTS ARE INTENDED FOR SALE
TO AND INSTALLATION BY QUALIFIED
PROFESSIONALS. UTC FIRE & SECURITY
CANNOT PROVIDE ANY ASSURANCE THAT
ANY PERSON OR ENTITY BUYING ITS
PRODUCTS, INCLUDING ANY “AUTHORIZED
DEALER” OR “AUTHORIZED RESELLER”, IS
PROPERLY TRAINED OR EXPERIENCED TO
CORRECTLY INSTALL FIRE AND SECURITY
RELATED PRODUCTS.
For more information on warranty disclaimers and
product safety information, please check
https://firesecurityproducts.com/policy/product-
warning/
or scan the QR code.
Protection class
IP67 EN III/A
Certification
EN
Grade 4, EN-ST-000222
European Union
directives
UTC Fire & Security hereby declares that this
device is in compliance with the applicable
requirements and provisions of the Directive
2014/30/EU and/or 2014/35/EU. For more
information see www.utcfireandsecurity.com or
www.interlogix.com.
2012/19/EU (WEEE directive): Products marked
with this symbol cannot be disposed of as
unsorted municipal waste in the European Union.
For proper recycling, return this product to your
local supplier upon the purchase of equivalent
new equipment, or dispose of it at designated
collection points. For more information see:
www.recyclethis.info.
Contact information
www.utcfireandsecurity.com or www.interlogix.com.
For customer support, see www.utcfssecurityproducts.eu