Menu 1, 12, 14 and 15 are reserved menus. 

Menu 2, LEDs offline 

Select either two-wire (default) or one-wire LED control.  

For two-wire LED control: 

• 

The brown wire controls LED 1 red (Arm). Wire grounded: 
LED 1 red on, wire open or at +5 to 14 V: LED 1 off. 

• 

The yellow wire controls the LED 1 green (Disarm). Wire 
grounded (0 V): LED 1 green on, wire open or at +5 to 
14 V: LED 1 off. 

• 

Both yellow and brown wires grounded (0 V), LED 1 is on 
yellow. Not valid when used on UTC products. 

For one-wire LED control, the brown wire controls LED 1 
green-red dual colour.  

• 

Grounded or 0 V, LED 1 green on. 

• 

+5 to 15 V: LED 1 red is on. 

• 

Open or high Z, or +2.5 V: LED 1 off. 

Menu 3, Valid card flash 

If enabled (default), the green LED will give one short flash 
when the card is badged. The panel controls subsequent 
flashes. 

Menu 4, Night light 

A dimly lit keypad backlight provides the night-light to easily 
locate the keypad in dark locations (enabled by default). 

Menu 5, Protocol options 

This option selects the method by which the reader sends data 
to the panel. The options are Wiegand (default) or Magnetic 
stripe. See option 16 for more data on transmitted data details. 

Menu 6, Card beep 

If enabled (default), the beeper will give a short beep when a 
card is badged. The panel controls subsequent beeper activity. 

Menu 7, Watchdog 

Offline mode only. If enabled, one byte of data is sent to the 
host every minute to indicate that the RAS is connected and 
operating normally. If the ATS1197 tamper is active, the data 
byte will not be sent (disabled by default). 

Menu 8, O/C output 

Select one of the following options: 

• 

Door relay (online mode only) 

— The open collector output 

activates (active low) when the door open signal is sent to 
the ATS1197 (default setting). 

• 

Tamper output (online or offline modes) 

— The open 

collector output activates (active low) when the ATS1197 
Tamper is active. 

• 

Card data present (offline mode only) 

— The open 

collector output activates (active low) when the card data 
is being sent to the host. 

Menu 9, Option card 

This option enables (default setting) and disables the use of 
reader configuration (option) cards at the reader. If an installer 

wishes to prevent the modification of the reader setup by 
configuration card, this option should be disabled. 

Menu 10, RTE (Egress) 

The RAS is fitted with Request To Exit (RTE) control (yellow 
wire). The open collector output (violet wire) may be used to 
control a door relay. RTE is only available in online mode. 

There are three options to choose from: 

• 

RTE disabled. When RTE is not used, it is recommended 
to disable it. 

• 

RTE only. This option requires a simple push button to be 
connected to the yellow wire. A press of the button will 
release the door lock relay. Used for a quick exit from an 
Area (enabled by default). 

• 

RTE arm/disarm. Do not use. 

Menu 11, Factory defaults 

This option returns all RAS settings to the factory default 
condition.  

Menu 13, Last card 

This option displays the number of the last card badged on the 
reader, in the format: facility code/system code, ID number or 
as raw card data (depends on setting of security mode). 

Menu 16, Security mode 

This option selects the type of user card the reader will 
recognise. The reader will recognise configuration and default 
cards in both modes. The possible modes are as follows: 

• 

Unsecured mode (default setting) 

— The reader will 

recognise blank or un-programmed cards only, by using 
the 

card’s unique serial number. The 4-byte security 

password is not used. Unsecured mode requires the use 
of an expanded memory system. 

• 

Secured mode 

— Only cards programmed on the 

ATS1620/1621/1622 programmer will be recognised in 
this mode. The 4-byte security password is used. 

Data transmission 

The following tables list the formats by which the card reader 
transmits data, as determined by: 

• 

whether the reader is used online or offline, and by 

• 

menu option 5-Protocol options (Wiegand or Magnetic 
stripe), and by 

• 

menu option 16-Security mode (secured or unsecured). 

Note: 

In online mode, select Wiegand in menu 5 to use 26 or 

27 bit data, or select Magnetic stripe to use 32 bit data. 

Online 

 

Reader protocol 

Card format 

Wiegand 

Magnetic stripe 

Secured 

When badged on a 
reader, 26 or 27 bit data 
is transmitted, 
depending on whether 
the card is programmed 
as Wiegand 26 bit or 
Aritech Wiegand ASC. 

When badged on a reader, 
32 bit data is transmitted. 

Содержание ATS1197

Страница 1: ...s 7 Mount the RAS on the back plate by engaging the top and then lowering the RAS to be flat against the back plate The rear tamper switch must be sealed for the system to work correctly Ensure that the back plate tamper spring rests on the tamper switch actuator protruding from the resin in the back of the RAS when the RAS is in position 8 Fix the RAS to the back plate using the two screws remove...

Страница 2: ...buzzer control Wire open or 5 to 12 V buzzer off absolute maximum is 14 V Wire grounded 0 V buzzer on Brown Application depends on selection of RAS menu option 2 Offline LED control See programming Colour Application Yellow Application depends on selection of RAS menu option 2 Offline LED control see programming When not used for two wire LED control yellow wire may be used for RTE input when onli...

Страница 3: ... the bus is faulty usually cabling Tx The red Tx LED flashes to indicate the RAS is replying to polling from the control panel If the Rx LED flashes but the Tx LED does not the RAS is not programmed to be polled in the control panel or is addressed incorrectly Configuring the ATS1197 RAS To configure the RAS 1 Press 19 Enter followed by 3 Enter 2 Type the required RAS address 2 to 16 followed by E...

Страница 4: ... and disables the use of reader configuration option cards at the reader If an installer wishes to prevent the modification of the reader setup by configuration card this option should be disabled Menu 10 RTE Egress The RAS is fitted with Request To Exit RTE control yellow wire The open collector output violet wire may be used to control a door relay RTE is only available in online mode There are ...

Страница 5: ...marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union For proper recycling return this product to your local supplier upon the purchase of equivalent new equipment or dispose of it at designated collection points For more information see www recyclethis info Contact information www utcfireandsecurity com or www interlogix com For customer support see www i...

Страница 6: ...nschluss AUX PWR von einer AME oder einer Nebenmelderversorgung Schwarz 0 V Gleichspannung Grün D0 D Clock kann für D0 Wiegand Daten D RS485 Daten Magnetstreifen Clock verwendet werden Normale Betriebsspannung 0 bis 5 V absolutes Maximum 12 V Weiß D1 D Daten kann für D1 Wiegand Daten D RS485 Daten Magnetstreifendaten verwendet werden Normale Betriebsspannung 0 bis 5 V absolutes Maximum 12 V Das BD...

Страница 7: ...n damit die Scharfschaltung des Systems an Die Bereiche müssen unscharfgeschaltet werden damit auf die Optionen im Errichterprogrammiermenü zugegriffen werden kann Fehlerbehebung Allgemeine Störungen Keine LED Anzeige oder Hintergrundbeleuchtung für die Tastatur aktiviert Überprüfen Sie sowohl am BDT als auch am Netzteil die Kabelverbindungen für 13 8 und 0 V Spannungsversorgung Überprüfen Sie den...

Страница 8: ...der auf Minus 0 V LED 1 grün ein Ader offen oder an 5 bis 14 V LED 1 aus Gelbe und braune Ader auf Minus 0 V LED 1 leuchtet gelb Nicht zulässig bei Verwendung mit UTC Produkten Bei der 1 Draht LED Steuerung steuert die braune Ader die zweifarbige LED 1 grün rot Ader auf Minus 0 V LED 1 grün ein Ader an 5 bis 15 V LED 1 rot ist aktiv Offen oder Ader an 2 5 V LED 1 aus Menü 3 Anzeige Gültige Karte b...

Страница 9: ...erät programmiert wurden Es wird das 4 Byte lange Sicherheitspasswort verwendet Datenübertragung In den folgenden Tabellen werden die Formate aufgelistet die der Kartenleser zum Übertragen von Daten verwendet Die Formate werden durch folgende Faktoren beeinflusst Online oder Offline Modus des Lesers Menü 5 Protokolloptionen Wiegand oder Magnetstreifen Menü 16 Sicherheitsmodus Gesichert oder Ungesi...

Страница 10: ...ei cavi Il montaggio del dispositivo su una superficie metallica può comportare una riduzione della portata di lettura 4 Fissare la piastra posteriore su una superficie piana utilizzando quattro viti Per il corretto funzionamento dell interruttore antimanomissione il foro più vicino alla molla antimanomissione deve essere occupato da una vite 5 Terminare il cavo in base alle esigenze vedere più av...

Страница 11: ...u 2 della RAS Controllo LED fuori linea Vedere la sezione relativa alla programmazione Giallo L applicazione dipende dalla scelta dell opzione di menu 2 della RAS Controllo LED fuori linea Vedere la sezione relativa alla programmazione Quando non utilizzato per il controllo LED a due cavi il cavo giallo può essere utilizzato per le seguenti applicazioni Ingresso RU quando in linea con l ATS Colleg...

Страница 12: ...n lo specifico sistema LED Rx e Tx I LED Rx e Tx visibili sulla scheda dei circuiti quando il coperchio posteriore di plastica viene rimosso semplificano la diagnosi dei guasti Rx Il LED giallo Rx lampeggia per indicare la ricezione dei dati di interrogazione inviati dalla centrale al bus del sistema Se il LED non lampeggia la centrale non è operativa oppure il bus è guasto generalmente si tratta ...

Страница 13: ...al minuto per indicare che la RAS è collegata e funziona correttamente Se la protezione antimanomissione dell ATS1197 è attiva il byte di dati non verrà inviato opzione disattivata per impostazione predefinita Menu 8 uscita A C Selezionare una delle opzioni seguenti Relè varco solo modalità in linea l uscita open collector si attiva attiva bassa quando il segnale di varco aperto viene inviato all ...

Страница 14: ...iche Tensione di alimentazione Da 8 5 a 14 0 V Corrente massima di funzionamento 110 mA a 13 8 V Corrente normale di funzionamento tutte le aree inserite 40 mA a 13 8 V Uscita open collector terminale OUT 14 V max a 50 mA max Dimensioni L x A x P 140 x 121 x 22 mm Temperatura di esercizio Da 40 a 50 C Umidità relativa 95 senza condensa Informazioni sulle normative Produttore UTC Fire Security Amer...

Отзывы: