Power up
Upon initial power up, the buzzer will sound two beeps
indicating that the internal non-volatile memory is OK. All of the
area LEDs may illuminate indicating that the system is armed.
All areas must be disarmed in order to enable access to the
installer programming menu options.
Troubleshooting
General faults
No LED display or keypad backlight:
•
Verify the +13.8 and 0 V wire connections on both the
RAS and the power supply.
•
Verify power output on the control panel, 4-door DGP, or
external power supply.
All three status LEDs are flashing:
•
Verify the D+ and D
− wire connections (may be reversed
or open circuit).
•
Verify the address DIP switches of the RAS are set to the
proper address.
•
Verify that the control panel or 4-door controller is polling
the RAS address.
The RAS does not respond to a Smart Card:
•
The RAS may not be programmed correctly or card beep
and LED flash may be disabled. Refer Programming for
details.
•
The Smart Card may not be programmed for use with the
particular system.
Rx and Tx LED Indications
Rx and Tx LEDs are provided on the circuit board to assist in
fault diagnosis and are visible when the rear plastic cover is
removed.
•
Rx: The yellow Rx LED flashes to indicate polling data is
being received on the system bus from the panel. If the
LED does not flash, the control panel is not operational or
the bus is faulty (usually cabling).
•
Tx: The red Tx LED flashes to indicate the RAS is replying
to polling from the control panel. If the Rx LED flashes but
the Tx LED does not, the RAS is not programmed to be
polled in the control panel or is addressed incorrectly.
Configuring the ATS1197 RAS
To configure the RAS:
1. Press 19, Enter followed by *, 3, Enter.
2. Type the required RAS address (2 to 16) followed by
Enter.
3. Select the RAS.
4.
Disable the option ’LCD Arming Station’.
5. Enable the option
“3 LED RAS”.
Programming map
UTC F&S, RAS1197.V10
0-EXIT, Menu:
2-LEDs offline
0-EXIT, Menu:
Two wire LED control
*-Change, #-Exit
3-Valid Card Flash
0-Exit, Menu:
Enabled
*-Change, #-Exit
4-Night Light
0-Exit, Menu:
Enabled
*-Change, #-Exit
5-Protocol Options
0-Exit, Menu:
Wiegand
*-Change, #-Exit
6-Card Beep
0-Exit, Menu:
Enabled
*-Change, #-Exit
7-Watch Dog
0-Exit, Menu:
Enabled
*-Change, #-Exit
8-O/C output
0-Exit, Menu:
Door Output
*-Change, #-Exit
9-Option Card
0-Exit, Menu:
Enabled
*-Change, #-Exit
10-RTE (Egress)
0-Exit, Menu:
RTE Disabled
*-Change, #-Exit
11-Factory Defaults
0-Exit, Menu:
Set Defaults?
*-Yes, #-No
13-Last Card
0-Exit, Menu:
00,00,00,00,00,00
#-Exit
16-Security Mode
0-Exit, Menu:
Un-Secured Mode
*-Change, #-Exit
Note:
Reserved menus are not shown.
Programming options
The ATS1197 provides for a menu through which a number of
options can be set.
To enter the programming menu for the ATS1197:
1. Enter menu 28 of the control panel installer menu.
2. Press 2, Enter, followed by the RAS address selected and
Enter to enter the RAS menu.
3. Press Enter to proceed to the menu or press the menu
number followed by Enter to go to a menu item directly.