Application diagram
12 to 24 VDC
15 to 24 VAC
Transistor
DIP switch
and Status LED’s
Redefine
“Master Code”
It is possible to redefine and restore the default setting if the Master code is forgotten.
1. Disconnect power and put the DIP switch1 to ON
2. Reconnect power
(Beep Beep ... + Orange LED blinks)
3. Put back the DIP switch1 to OFF
(Orange LED ON + Long beep)
4. Press 000
5. Press the new Master Code
6. Press A
(Beep Beep)
7. Press B
(Orange LED OFF)
Diode 1N4001
Default: 1
– OFF; 2 - ON
Green LED -
Output 1 Status
Red LED -
Output 2 Status
Orange LED -
Key press and Menu
Redefine Master Code
Backlight in Idle Mode ON/OFF
12 to 24
VDC
15 to 24 VAC
NOTE:
The PIN code is typed with A for confirmation.
Example:
123 + A
Note: Exit button (NO) automatically activates relay
output1.