Intergas Heating Ltd
39
10.9
Conversion to different gas type
CAUTION
Work on gas carrying parts may only be carried out by
a qualified competent person.
If a different type of gas is connected to the appliance than that for which the appliance has
been set by the manufacturer, the gas metering ring should be replaced. Conversion sets for
other types of gas are available to order.
10.9.1
Converting the gas restriction.
1.
Switch the boiler off and isolate the boiler from the mains power.
2.
Close the gas tap.
3.
Remove the front panel from the appliance.
4.
Unscrew the coupling (A) above the gas valve and twist the gas mixing tube towards
the rear (B).
5.
Replace the O-ring (C) and the gas restriction (D) with the rings from the conversion
set.
6.
Re-assemble in reverse sequence.
7.
Open the gas tap.
8.
Check the gas connections before the gas valve for gas-tightness.
9.
Switch on the mains power.
10.
Check the gas connections after the gas valve for gas-tightness (during operation).
11.
Now check the setting of the CO
2
percentage at high setting (H in display) and low
setting (L in display).
CAUTION
It is not possible to adjust the CO
2
level at high setting. When
the CO
2
percentage at high setting is not within the prescribed
tolerance band please contact Intergas Heating.
For adjusting CO
2
level at low setting see § 10.8.
12.
Place a sticker for the gas type set over the existing sticker next to the gas valve.
13.
Place a sticker for the gas type set next to the identification plate.