background image

5.

Clamp fla

re form on the end of the pipe. 

The end of the pipe must extend beyond 

the fla

re form. 

Flare form

Pipe

Fig. 7.5

6.

 

Place flaring tool onto the form.

7.

 

Tur

n the handle of the flaring tool clockwise 

until the pipe is fully fla

red. Flare the pipe in 

accordance with the dimensions shown in 

table 7.5.  

Table 7.5: PIPING EXTENSION BEYOND FLARE FORM

8.

 

Remove the flaring tool and fla

re form, then 

inspect the end of the pipe for cracks and 

even flaring.  

Step 4:

 Connect pipes

Connect the copper pipes to the indoor unit first, 

then connect it to the outdoor unit. You should 

first connect

 the low-pressure pipe, then the high-

pressure pipe.  

1.

 

When connecting the fla

re nuts, apply a thin coat 

of r

efrigeration oil to the fla

red ends of the pipes.  

2.

 

Align the center of the two pipes that you 

will connect.  

Indoor unit tubing

Flare nut

Pipe

Fig. 7.7

3.

 

T

ighten the fla

re nut as tightly as possible by hand. 

4.

 

Using a spanner, grip the nut on the unit tubing.

5.

 

While firmly gripping the nut, use a to

rque 

wr

ench to tighten the fla

re nut according to 

the torque values in table 7.5.  

NOTE: Use both a spanner and a torque wrench 

when connecting or disconnecting pipes to/from 

the unit.

Fig. 7.8

 CAUTION

• 

Ensure to wrap insulation around the piping. 

Direct contact with the bare piping may result 

in burns or frostbite.  

• 

Make sure the pipe is properly connected. 

Over tightening may damage the bell mouth 

and under tightening may lead to leakage.   

NOTE ON MINIMUM BEND RADIUS

Carefully bend the tubing in the middle according 

to the diagram below. DO NOT bend the tubing 

more than 90° or more than 3 times.  

 

 

 

Bend the pipe with thumb

min-radius 10cm (3.9”)

Fig. 7.9

6.

 

After connecting the copper pipes to the 

indoor unit, wrap the power cable, signal 

cable and the piping together with binding 

tape.  

NOTE:

 

DO NOT intertwine signal cable with 

other wires. While bundling these items 

together, do not intertwine or cross the signal 

cable with any other wiring. 

7.

 

Thread this pipeline through the wall and 

connect it to the outdoor unit.  

8.

 

Insulate all the piping, including the valves 

of the outdoor unit.  

9.

 

Open the stop valves of the outdoor unit 

to start the flow of the 

refrigerant 

between the indoor and outdoor unit.  

 

 CAUTION

Check to make sure there is no refrigerant leak 

after completing the installation work. If there is 

a refrigerant leak, ventilate the area immediately 

and evacuate the system (refer to the Air 

Evacuation section of this manual).    

ƒ

 Page 19 

„

 

Refrigerant Piping 

       Connection

 

  Pipe 

gauge 

Tightening 

torque

Flare dimension (A) 

(Unit: mm/Inch)

Flare shape

Min.

Max .

Ø 6.4

R0.4~0.8

45 °±2

90 °     

± 4

A

Fig. 7.6

Ø 9.5

Ø 12.7

Ø 15.9

Ø 19.1

Ø 22

65-67 N.m 

(663-683 kgf.cm)

23.2/0.91

23.7/0.93

75-85N.m 

(765-867 kgf.cm)

26.4/1.04

26.9/1.06

18-20 N.m 

(183-204 kgf.cm)

8.4/0.33

8.7/0.34

25-26 N.m 

(255-265 kgf.cm)

13.2/0.52 13.5/0.53

35-36 N.m 

(357-367 kgf.cm)

16.2/0.64 16.5/0.65

45-47 N.m 

(459-480 kgf.cm)

19.2/0.76 19.7/0.78

Содержание IDUCOI12KC-3

Страница 1: ...MAN I FCI12K 48K 0318 intensity mx INSTALLATION MANUAL Fan Coil IDUFCI12KC 3 IDUFCI18KC 3 IDUFCI24KC 3 IDUFCI36KC 3 IDUFCI48KC 3 IDUCOI12KC 3 IDUCOI18KC 3 IDUCOI24KC 3 IDUCOI36KC 3 IDUCOI48KC 3...

Страница 2: ...or Unit Types and Speci cations 13 c Notes on Drilling Hole in Wall 14 Drainpipe Installation 15 Table of Contents Installation Manual Indoor Unit Installation 07 Installation Overview 06 1 2 5 3 4 6...

Страница 3: ...th and Elevation 17 B Refrigerant Piping Connection Instructions 18 Wiring 20 a Outdoor Unit Wiring 20 b Indoor Unit Wiring 21 c Power Speci cations 23 Air Evacuation 25 a Evacuation Instructions 25 b...

Страница 4: ...12 7 Packed with the indoor unit used for multi type models only NOTE Pipe size may differ from appliance to appliance To meet different pipe size requirements sometimes the pipe connections need a t...

Страница 5: ...might affect your unit and locate it accordingly Failure to do so could cause the equipment to fail After installation ensure there are no refrigerant leaks and that the unit is operating properly Ref...

Страница 6: ...2 3 4 5 MC MC 6 7 Install the indoor unit Page 7 INSTALLATION ORDER Install the outdoor unit Page 13 Install the drainpipe Page 15 Evacuate the refrigeration system Page 25 Connect the wires Page 20...

Страница 7: ...on The indoor unit should be installed in a location that meets the following requirements o Enough room for installation and maintenance o Enough room for the connecting pipe and drainpipe o The ceil...

Страница 8: ...2 11 8in 30cm 11 8in 30cm 0 4in 1cm 4in 10cm Service access Service access Unit A A 2 A 2 Filter service clearance only one side is required COIL CONNECTION AREA CONDENSATE DRAIN PIPING AREA CONDENSAT...

Страница 9: ...5 598 23 5 697 27 4 9K 200 7 9 506 19 9 700 27 6 12K 200 7 9 506 19 9 700 27 6 152 6 537 21 1 450 17 7 152 6 537 21 1 450 17 7 186 7 3 186 7 3 741 29 2 599 23 6 741 29 2 599 23 6 360 14 2 360 14 2 Pag...

Страница 10: ...nut Washer Hanging screw bolt Overhang part Shockproof cushion NOTE Confirm the minimum drain tilt is 1 100 or more CAUTION The unit body must be completely aligned with the hole Ensure that the unit...

Страница 11: ...air conditioner you have purchased may be slightly different in design though similar in shape Step 5 Fresh air duct installation Dimension Duct joint for fresh air 125mm 4 92 160mm 6 3 MODLE 18 60 S...

Страница 12: ...d indoor unit may not exceed the maximum allowable pipe length o If possible DO NOT install the unit where it is exposed to direct sunlight o If possible make sure the unit is located far away from yo...

Страница 13: ...to Fig 5 7 5 8 5 9 and Table 5 2 Fig 5 7 Fig 5 8 Fig 5 9 Fig 5 6 Fig 5 5 A B D W H W H Fig 5 4 Outdoor Unit Dimensions W x H x D Mounting Dimensions Distance A Distance B 770x555x300 30 3x21 85x11 81...

Страница 14: ...protects the edges of the hole and will help seal it when you finish the installation process Page 14 Outdoor Unit Installation Fig 5 11 L H 300 cm 118 or more A 60 cm 23 6 or more 150 cm 59 or more 2...

Страница 15: ...ensation which could lead to water damage If the drainpipe is bent or installed incorrectly water may leak and cause a water level switch malfunction In HEAT mode the outdoor unit will discharge water...

Страница 16: ...roper water drainage See Fig 6 5 Place the protective wall cuff in the hole This protects the edges of the hole and will help seal it once you finish installation Wall Indoor Outdoor 12mm 0 5 inch Fig...

Страница 17: ...otes On Pipe Length and Elevation Ensure that the length of the refrigerant pipe the number of bends and the drop height between the indoor and outdoor units meets the requirements shown in Table 7 1...

Страница 18: ...g connection They must be completely removed 1 Hold the pipe at a downward angle to prevent burrs from falling into the pipe 2 Using a reamer or deburring tool remove all burrs from the cut section of...

Страница 19: ...er tightening may damage the bell mouth and under tightening may lead to leakage NOTE ON MINIMUM BEND RADIUS Carefully bend the tubing in the middle according to the diagram below DO NOT bend the tubi...

Страница 20: ...made through a switch that disconnects all poles with contact gap of at least 3mm 0 118 DO NOT modify the length of the power cord or use an extension cord CAUTION Connect the outdoor wires before con...

Страница 21: ...l parts 6 Reinstall the cover of the electric control box Indoor Unit Wiring 1 Prepare the cable for connection a Using wire strippers strip the rubber jacket from both ends of the signal cable to rev...

Страница 22: ...orms with the designed airflow rate Make sure the unit is in FAN ONLY mode Press and set the airflow adjustment button on the remote control to change the airflow rate from H or L 4 Set the parameters...

Страница 23: ...1 Phase 1 Phase 1 Phase 1 Phase 1 Phase FREQUENCY AND VOLT 208 240V 208 240V 208 240V 208 240V 208 240V CIRCUIT BREAKER FUSE A 25 20 32 25 50 40 70 55 70 60 MODEL Btu h 36K 37K 60K 36K 37K 60K POWER P...

Страница 24: ...1 Phase 1 Phase 1 Phase 1 Phase FREQUENCY AND VOLT 208 240V 208 240V 208 240V 208 240V CIRCUIT BREAKER FUSE A 15 10 15 10 15 10 15 10 POWER outdoor PHASE 3 Phase 3 Phase 3 Phase 3 Phase FREQUENCY AND...

Страница 25: ...the manifold gauge Keep the High Pressure side closed 4 Turn on the vacuum pump to evacuate the system 5 Run the vacuum for at least 15 minutes or until the Compound Meter reads 76cmHG 1x105Pa 6 Close...

Страница 26: ...5m 16 The additional refrigerant to be charged can be calculated using the following formula Liquid Side Diameter 6 35 1 4 9 52 3 8 12 7 1 2 R22 orifice tube in the indoor unit Total pipe length stand...

Страница 27: ...correctly d Ensure the indicators on the remote control and the display panel on the indoor unit work properly e Ensure the manual buttons on the indoor unit works properly f Check to see that the dr...

Страница 28: ...Page 28 The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details...

Страница 29: ...Page 29 Test Run...

Страница 30: ...Test Run Page 30...

Отзывы: