Refrigerant Piping Connection

Safety Precautions

 WARNING

•  All field piping must be completed by a 

 

 

 

licensed technician and must comply with 

the local and national regulations. 

•  When the air conditioner is installed in a 

 

small room, measures must be taken to 

prevent the refrigerant concentration in 

the room from exceeding the safety limit 

in the event of refrigerant leakage. If the 

refrigerant leaks and its concentration 

exceeds its proper limit, hazards due to 

lack of oxygen may result.     

•  When installing the refrigeration system, 

 

 

 

ensure that air, dust, moisture or foreign 

substances do not enter the refrigerant 

circuit. Contamination in the system may 

cause poor operating capacity, high 

pressure in the refrigeration cycle, 

explosion or injury.     

 

•  Ventilate the area immediately if there is

 

   

refrigerant leakage during the installation. 

Leaked refrigerant gas is both toxic and 

flammable. Ensure there is no refrigerant 

leakage after completing the installation 

work.    

Notes On Pipe Length and Elevation

 

 

Ensure that the length of the refrigerant pipe, the 

number of bends, and the drop height between 

the indoor and outdoor units meets the 

requirements shown in Table 7.1:  

Table 7.1: The Maximum Length And Drop 

Height Based on Models. (Unit: m/ft.) 

Type of model

Capacity

 (Btu/h)

Length of 

piping

Maximum drop 

height

 

  North America, 

Australia and the 

  eu frequency 

conversion Split 

            Type

<15K

25/82

10/32.8

≥15K - <24K

30/98.4

20/65.6

≥24K - <36K

50/164

25/82

≥36K - ≤60K 

65/213

30/98.4

Other Split Type

12K

15/49

8/26

18K-24K

25/82

15/49

30K-36K

30/98.4

20/65.6

42K-60K

50/164

30/98.4

Refrigerant Piping with Twin Indoor Units

 

When installing multiple indoor units with a single outdoor unit, ensure that the length of the 

refrigerant pipe and the drop height between the indoor and outdoor units meet the requirements 

illustrated in the following diagram:

L

L1

L2

H2 

The line branch pipe     

Indoor unit     

Outdoor unit   

 

H1 

Indoor unit     

The drop height 

between two 

indoor units

 must be less 

than or equal to 

50cm (19.6”)

   

The drop height 

between indoor  

unit

and outdoor unit 

must be less than 

 or equal to 20m   

(65.6’) 

   

Fig. 7.1

ƒ

 Page 17

„

7

 Refrigerant Piping 

       Connection

 

Содержание IDUCOI12KC-3

Страница 1: ...MAN I FCI12K 48K 0318 intensity mx INSTALLATION MANUAL Fan Coil IDUFCI12KC 3 IDUFCI18KC 3 IDUFCI24KC 3 IDUFCI36KC 3 IDUFCI48KC 3 IDUCOI12KC 3 IDUCOI18KC 3 IDUCOI24KC 3 IDUCOI36KC 3 IDUCOI48KC 3...

Страница 2: ...or Unit Types and Speci cations 13 c Notes on Drilling Hole in Wall 14 Drainpipe Installation 15 Table of Contents Installation Manual Indoor Unit Installation 07 Installation Overview 06 1 2 5 3 4 6...

Страница 3: ...th and Elevation 17 B Refrigerant Piping Connection Instructions 18 Wiring 20 a Outdoor Unit Wiring 20 b Indoor Unit Wiring 21 c Power Speci cations 23 Air Evacuation 25 a Evacuation Instructions 25 b...

Страница 4: ...12 7 Packed with the indoor unit used for multi type models only NOTE Pipe size may differ from appliance to appliance To meet different pipe size requirements sometimes the pipe connections need a t...

Страница 5: ...might affect your unit and locate it accordingly Failure to do so could cause the equipment to fail After installation ensure there are no refrigerant leaks and that the unit is operating properly Ref...

Страница 6: ...2 3 4 5 MC MC 6 7 Install the indoor unit Page 7 INSTALLATION ORDER Install the outdoor unit Page 13 Install the drainpipe Page 15 Evacuate the refrigeration system Page 25 Connect the wires Page 20...

Страница 7: ...on The indoor unit should be installed in a location that meets the following requirements o Enough room for installation and maintenance o Enough room for the connecting pipe and drainpipe o The ceil...

Страница 8: ...2 11 8in 30cm 11 8in 30cm 0 4in 1cm 4in 10cm Service access Service access Unit A A 2 A 2 Filter service clearance only one side is required COIL CONNECTION AREA CONDENSATE DRAIN PIPING AREA CONDENSAT...

Страница 9: ...5 598 23 5 697 27 4 9K 200 7 9 506 19 9 700 27 6 12K 200 7 9 506 19 9 700 27 6 152 6 537 21 1 450 17 7 152 6 537 21 1 450 17 7 186 7 3 186 7 3 741 29 2 599 23 6 741 29 2 599 23 6 360 14 2 360 14 2 Pag...

Страница 10: ...nut Washer Hanging screw bolt Overhang part Shockproof cushion NOTE Confirm the minimum drain tilt is 1 100 or more CAUTION The unit body must be completely aligned with the hole Ensure that the unit...

Страница 11: ...air conditioner you have purchased may be slightly different in design though similar in shape Step 5 Fresh air duct installation Dimension Duct joint for fresh air 125mm 4 92 160mm 6 3 MODLE 18 60 S...

Страница 12: ...d indoor unit may not exceed the maximum allowable pipe length o If possible DO NOT install the unit where it is exposed to direct sunlight o If possible make sure the unit is located far away from yo...

Страница 13: ...to Fig 5 7 5 8 5 9 and Table 5 2 Fig 5 7 Fig 5 8 Fig 5 9 Fig 5 6 Fig 5 5 A B D W H W H Fig 5 4 Outdoor Unit Dimensions W x H x D Mounting Dimensions Distance A Distance B 770x555x300 30 3x21 85x11 81...

Страница 14: ...protects the edges of the hole and will help seal it when you finish the installation process Page 14 Outdoor Unit Installation Fig 5 11 L H 300 cm 118 or more A 60 cm 23 6 or more 150 cm 59 or more 2...

Страница 15: ...ensation which could lead to water damage If the drainpipe is bent or installed incorrectly water may leak and cause a water level switch malfunction In HEAT mode the outdoor unit will discharge water...

Страница 16: ...roper water drainage See Fig 6 5 Place the protective wall cuff in the hole This protects the edges of the hole and will help seal it once you finish installation Wall Indoor Outdoor 12mm 0 5 inch Fig...

Страница 17: ...otes On Pipe Length and Elevation Ensure that the length of the refrigerant pipe the number of bends and the drop height between the indoor and outdoor units meets the requirements shown in Table 7 1...

Страница 18: ...g connection They must be completely removed 1 Hold the pipe at a downward angle to prevent burrs from falling into the pipe 2 Using a reamer or deburring tool remove all burrs from the cut section of...

Страница 19: ...er tightening may damage the bell mouth and under tightening may lead to leakage NOTE ON MINIMUM BEND RADIUS Carefully bend the tubing in the middle according to the diagram below DO NOT bend the tubi...

Страница 20: ...made through a switch that disconnects all poles with contact gap of at least 3mm 0 118 DO NOT modify the length of the power cord or use an extension cord CAUTION Connect the outdoor wires before con...

Страница 21: ...l parts 6 Reinstall the cover of the electric control box Indoor Unit Wiring 1 Prepare the cable for connection a Using wire strippers strip the rubber jacket from both ends of the signal cable to rev...

Страница 22: ...orms with the designed airflow rate Make sure the unit is in FAN ONLY mode Press and set the airflow adjustment button on the remote control to change the airflow rate from H or L 4 Set the parameters...

Страница 23: ...1 Phase 1 Phase 1 Phase 1 Phase 1 Phase FREQUENCY AND VOLT 208 240V 208 240V 208 240V 208 240V 208 240V CIRCUIT BREAKER FUSE A 25 20 32 25 50 40 70 55 70 60 MODEL Btu h 36K 37K 60K 36K 37K 60K POWER P...

Страница 24: ...1 Phase 1 Phase 1 Phase 1 Phase FREQUENCY AND VOLT 208 240V 208 240V 208 240V 208 240V CIRCUIT BREAKER FUSE A 15 10 15 10 15 10 15 10 POWER outdoor PHASE 3 Phase 3 Phase 3 Phase 3 Phase FREQUENCY AND...

Страница 25: ...the manifold gauge Keep the High Pressure side closed 4 Turn on the vacuum pump to evacuate the system 5 Run the vacuum for at least 15 minutes or until the Compound Meter reads 76cmHG 1x105Pa 6 Close...

Страница 26: ...5m 16 The additional refrigerant to be charged can be calculated using the following formula Liquid Side Diameter 6 35 1 4 9 52 3 8 12 7 1 2 R22 orifice tube in the indoor unit Total pipe length stand...

Страница 27: ...correctly d Ensure the indicators on the remote control and the display panel on the indoor unit work properly e Ensure the manual buttons on the indoor unit works properly f Check to see that the dr...

Страница 28: ...Page 28 The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details...

Страница 29: ...Page 29 Test Run...

Страница 30: ...Test Run Page 30...

Отзывы: