The SMG has three different modes: 

Charge

 

Standby

 and 

Off

.

Once connected, the converter will be in the “Off mode”. There will be 0 V on the output, the primary/yellow LED will flash with a 1 Hz frequency and the 

secondary/green LED is set to Off.

The converter will be set to the "Charge mode" if the following conditions are met:

The primary voltage is above 11.8 V for at least 5 seconds

Vibrations have been detected (see the Configuration Table for the operation of the vibration detection). (This only applies to the SMG360iM model)

The converter sends out 14.4 V in the “Charge mode” and both the primary/yellow and the secondary/green LED are on.

When a voltage of 14.2 V is measured on the output, a timer will start that will run for an hour. After this hour, the SMG will be set to the "Standby mode". The 

SMG sends out 13.8 V in the "Standby mode" and both the primary/yellow and the secondary/green LED are on.

The SMG will only again be switched to the "Charge mode" if:

The voltage on the output falls below 13.2 V (for 5 seconds).

The SMG has been in the "Standby mode" for 24 consecutive hours.

The converter will again be set to the "Off mode" from both the "Charge mode" and "Standby mode" if:

The voltage on the primary side falls under 11.6 V for 10 seconds.

The voltage on the primary side falls under 11.8 V for 5 minutes.

Vibrations are no longer detected (see the Configuration Table for the operation of the vibration detection). (This only applies to the SMG360iM 

model)

 Configuring

      Configuration table

The SMG360iM can be set on two fronts:

1. Its sensitivity.

2. The time that the SMG  remains switched on after detecting the last vibration.

When the programming button of the SMG has been pressed for 4 seconds, LED 1 will light up briefly. As

soon as this happens, the button must be released.

The button must again be pressed shortly to configure the correct configuration number. The LED will light up

as feedback. This means that configuration #1 has been selected at that moment. If the user again presses

the button briefly, configuration #2 will have been selected, etc.

When the button is not pressed for 4 seconds, the LED will again display the set position. (Example:

Configuration #4 has been set by the user, the LED will flash 4 times.)

  

* factory setting

#

Sensitivity

Time (sec)

1

(most sensitive)

1

2

5

  3*

30

4

2

1

5

5

6

30

7

3

5

8

30

9

60

10

4

5

11

30

12

60

13

5

 (least sensitive)

30

14

60

 Technical details

Input

Output

Supply voltage

12 V DC

Voltage

Charge

14.4 V DC

Input voltage range

9.0 V … 18.0 V DC

Rest

13.8 V DC

Start-up voltage

>11.8 V DC

Under voltage limit

Fast

<12.6 V DC

Slow

<12.8 V DC

General

Charge transition voltage

<13.2 V DC

Connections

6 x 6.3 mm faston

Charge forcing

every 24 hours

Cable advice

2.5 mm

2

Stabilization

±1 %

h x b x d

80 x 132 x 191 mm

Current limit

±20 A

Weight

1317 g

Operational temperature

-10 °C … +40 °C

Standby current

±23 mA

Part No:

 SMG-1212-360-CM

Ref: DS-PM-AR-SMG-M     21-2-17 

(v.2   8-6-17)

Location of sensitivity adjustment switch