Page 5
Intellimeter Canada Inc.
1125 Squires Beach Road, Pickering, ON, L1W 3T9 • Tel: (905) 839-9199
Copyright 2020 © MF Series Manual
1.2 Specifications
Dimensions (Inches)
9.8 H x 7.3 W x 3.5 D
Dimensions (Millimeters)
275 H x 185 W x 89 D
Meter Constants (K
h
)
10 Wh
Measurements
1
Total Energy: kWh is accumulated in non-volatile memory on the meter;
Real Time Measurements: V (RMS) per phase, I (RMS) per phase, W per
phase, VA per phase, power factor per phase, frequency
Number of Meters
MF3:1/ MF6:2
Meter Elements (CTs)
MF3:1 to 3/ MF6 1 to 7 (1 Neutral)
Voltage Rating
Auto range 120 - 347VAC (L-N), -20% to +10% of rating
Rated VA
< 4 VA
Service Type
1Ø2W, 1Ø3W, 2Ø3W, 3Ø4W wye, 3Ø3W Delta*
Current Transformers
80/100 mA output, Self Shorting Protection
Current Range
0.08 – 80mA, 1 – 100mA
Instrument Transformers
Interface
Yes
Power Quality
Per phase V & I Total harmonic Distortion (THD), Per phase V & I
individual harmonic order up to 23
rd
Memory
45 days (5 min intervals) kWh
Pulse Output
Wh / VAh
Communications
ModBus RTU or TCP/IP, BACnet MSTP or TCP/IP and pulse output.
Frequency
45 to 65 Hz
Accuracy Class
0.5 (Meets ANSI C12.20)
Real Time Measurements
V, I, kW, kVA, kVar, PF, Hz , THd (V/I)
Operating Temperature
-10°C to +53°C
Regulatory Compliance /
Approvals
Measurement Canada,
C
CSA
US
CTEP (CA)
Patent
U.S. Patent No. 8,049,487
1
All instantaneous measurements and interval data must be with a wired/wireless communication
module.