Page 18
Intellimeter Canada Inc.
1125 Squires Beach Road, Pickering, ON, L1W 3T9 • Tel: (905) 839-9199
Copyright 2019 © i-meter 45 Manual
41145
kVAh
UINT32
001kVAh
41149
Frequency
UINT32
0.01 Hz
41155
Voltage Average
UINT32
0.001V
41157
Meter Total Current
UINT32
0.001A
41161
Meter Total Watts
UINT32
0.001kWh
41163
Meter Total VA
UINT32
0.001kVA
Note
1.
Active Phases - 41100
: 0x0001 - Meter uses phase A; 0x0002 - Meter uses phase B;
0x0004 - Meter uses phase C.
2.
Voltage Average - 41155
: Average of the voltage from each phase.
3.
Meter Total Current - 41157
: Average of the current from each phase.
4.
Meter 0 is assigned to the main meter if you program the configuration with main
meter.
Table 5-3 Meter x Information
Modbus Address
Name
Format
Unit
Default
4xx00
Active Phases
Bit map
x1
4xx01
Voltage A
UINT32
0.001V
4xx03
Voltage B
UINT32
0.001V
4xx05
Voltage C
UINT32
0.001V
4xx07
Current A
UINT32
0.001A
4xx09
Current B
UINT32
0.001A
4xx11
Current C
UINT32
0.001A
4xx13
Watts A
INT32
W
4xx15
Watts B
INT32
W
4xx17
Watts C
INT32
W0.001kW
4xx19
Volt-Amp A
INT32
VA
4xx21
Volt-Amp B
INT32
VA
4xx23
Volt-Amp C
INT32
0.001kVA
4xx31
Power Factor A
INT32
0.001 Units
4xx33
Power Factor B
INT32
0.001 Units
4xx35
Power Factor C
INT32
0.001 Units
4xx43
kWh
UINT32
0.001kWh
Содержание I-METER 45