![Intellihot iN199 Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/intellihot/in199/in199_installation-and-operation-manual_2074158009.webp)
5 iN199
Technical Specifications
Oct 2021 - Revision 01
3. Technical Specifications
3.1 Specifications Chart
Technical Data
iN199 Specification
Type
Indoor, Floor-Mounted
Fuel
Preset for natural gas but convertible to propane
Minimum Input (BTUs/hour)
30,000
Maximum Input (BTUs/hour)
199,950
Maximum Output (BTUs/hour)
191,952
Thermal Efficiency
96%
Turn Down Ratio (TDR)
6.7:1
Water Inlet / Outlet Connection
1-1/2" NPT
Gas Inlet Connection
1-1/2" NPT (3/4" w/nipple)
Condensate Drain Connection
3/4" PVC
Maximum Condensate Flow Rate (GPM)
1.4
Unit dimensions H X W X D (inches)
67.5 X 20 X 20 (15.6 cu. ft)
Service Clearances
4" on the back, 6" on the top, 12" on the front, and 6" on the sides
Unit weight (lbs)
273
Shipping Crate Dimensions H X W X D / Weight
27 X 29.5 X 85 (Inches) / 373 (LBS)
Venting Type
Direct Vent (2 pipe – air intake and exhaust gas outlet), Power Vent (1 pipe – exhaust gas only)
Venting Materials (USA)
Sch. 40 PVC, Sch. 80 CPVC, Polypropylene, Stainless Steel (AL29-4C)
Venting Materials (Canada)
Type BH Gas Vent Classes: II A (PVC), II B (CPVC), II C (Polypropylene), I (AL294C SS)
Venting Size (Diameter)
3"
Max 8" Vent Length – Single Pipe/Power Vent
195' *
Max 8" Vent Length – Two Pipe / Direct Vent
95' *
* Venting Note: From the maximum length above, deduct 5 ft. per 90° elbow and 2 ft. per 45° elbow.
Ignition
Electronic Spark Ignition
Temperature Range
100°F – 190°F
Temperature Stability
+/- 4°F (when on demand)
Installation Location Ambient Temperature
40°F – 130°F
Safety
Flame Rod, Thermal Fuse, Overheat Prevention Device, Fan Speed Monitor, Flue Temperature Monitor, Blocked Vent Detector, Dual
Flame Sensing
Water Pressure Min / Max (PSI)
30/150
NG/LP- Min. Static Gas Pressure (Full Fire)
2.5" WC (set regulators to 8" NC for NG or 11" for LP)
NG/LP - Maximum Static Gas Pressure
14" WC
Gas Pressure for Adjustments
8" WC for Natural Gas, 11" WC for Propane
Electrical
120V AC, 60 Hz
Power Consumption
Max 9.5 Amps, 16W (Standby)
Internal Water Volume (gallons)
1
Features and Approvals
iN199
Cascading
Masterless, 4-Unit, Automatic Rotation
Common Venting
Yes, Up to 4 Units
Heat Exchanger
Expandable, Stainless 316L
Appliance Certication to ANSI Z21.10.3
ETL
SCAQMD (Pending)
Ultra Low Nox (under 20 PPM)
Performance
Specification
Hot Water Output (45°F Rise)
8.5
Hot Water Output (70°F Rise)
5.5
Hot Water Output (90°F Rise)
4.3
Hot Water Output (100°F Rise)
3.8
Hot Water Output (140°F Rise)
2.7
Warranty
Heat Engine Coil - 6 years, All Other Parts - 1 year
Note: Due to continuous product improvements, the design and technical specifications are subject to change without notice.