25
Number 10009655. A1
Parameter
Unit
Range
Factory Setting
(24V)
Factory Setting
(48V)
Target Output Voltage
V
15.0 to 56.0
26
52
Delayed Start Under-Voltage
V
0.0 to 60.0
24
48
Delayed Start Qualification Time
s
0 to 14400
60
60
Immediate Start Under-Voltage
V
0.0 to 60.0
22
46
Delayed Stop Over-Voltage
V
0.0 to 60.0
32
54
Delayed Stop OV Qualification Time
s
0 to 3600
60
60
Delayed Stop Under-Current
A
0.0 to 120.0
6
6
Delayed Stop UC Qualification Time
s
0 to 3600
20
20
Deny Start Under-Voltage
V
0.0 to 50.0
20
40
System Index
-
1 to 8
1
1
Output Voltage Rise Rate
V/s
0.017 to 2000.00
0.017
0.017
Minimum Output Voltage
V
0.0 to 60.0
24
48
Output Current Limit
A
0.0 to 120.0
105
120
Hard Set Output Voltage
-
0 or 1
0
0
Output Power Limit
W
0.0 to 4000
2880
4000
Restart Delay
s
0 to 3600
20
20
Control parameters and standard factory setting
13
13.2
Power Setup Configuration (804)