background image

INST

ALL
ATIONGUIDE

GDMS 2

 

 

 

 

 

 

 

 

Interlock inputs, mains installation and output attributes

The Emergency stop, fire and thermal link
interlocks are all normally closed circuits. If 
these aren’t being used then they must be 
linked out. As many estops, thermal links and 
fire alarm signals can be added, as is neces-
sary, as long as the loop is broken by each 
device connected.

See “setting up zone 
attributes” on page 4

Beacon output activates on pre alarm and alarm

24v Sounder output activates on alarm and deactivates on
pressing the mute button

Thermal link relay output can be used to operate fire alarms or
I/O modules programmed to alert the buildings occupier.

Pre-alarm and alarm relays operate in conjunction with the fascia LED
indicators. They are reset when the system is reset via the fascia pushbutton

Mains supply
should be via a
local fused spur
fitted with a 
5amp fuse using 
suitable mains 
cable 

The feed out to
the gas valve
should also have 
a local isolator 
near the gas 
valve