OPERATING MANUAL and INSTALLATION INSTRUCTIONS for

 

Form HW+3250 rev 7.2

 

IntelliCon

®

-

HW+

 

HOT-WATER HEATING SYSTEM ECONOMIZER 

Description 

The 

IntelliCon

®

-HW+

  is  a  patented  microprocessor-based  fuel-saving 

controller for hydronic heating systems up to 300M BTUs.  It reduces fuel 
consumption,  wear  on  boiler  parts  and  burner  emissions  by  actively 
managing the  burner,  in conjunction  with  the  boiler  operating-control,  to 
properly  match  the  boiler  output  to  the  required  load.  This  controller 
indicates  actual  savings  on  a  burner  cycle  by  cycle  basis  and  also 
indicates  the  averages  of  these  cycles.    This  unit  is  compatible  with 
Intellidyne’s  Remote  Display  Unit  (model  RDU).  In  addition,  certain 
parameters are programmable.  All of the programmable parameters and 
savings values are stored in memory that will not be lost in the event of 
the unit being turned off or a power failure. 

Electric Ratings 

Power input: 24,115,220 VAC ± 10%, 5 Watts max., 50/60Hz 
Control circuit input: 24,115,220 VAC ± 10%, 0.1A max. Burden 
Relay Contact: Form B, 10A @ 220 VAC (General Purpose) 

Environmental Conditions 

For Indoor Use.

 

Maximum Altitude: 6500 Ft. (2000M)

 

Rated Ambient Temperature: -

20˚ -- 120˚F. (-29˚ -- 49˚C.) 

Maximum Rh: 80% non-condensing

 

Mains Supply Voltage Fluctuations: ± 10%

 

Transient Over-Voltage Category: (III)

 

Pollution Degree: (2) 

Note: The IntelliCon control must be operated within the specifications and 
protected from the elements. Failure to do so voids the warranty and 
guarantee. Below 32˚F (0˚C), the control will continue to operate but the LCD 
display may not function properly.  The display will return to normal above 
that temperature.

 

Operation 

After installation, setting the switch on the  controller 

to the ‘ON’ position 

activates  the control.    The  LCD  display 

indicates the various ‘modes’

 

of 

the  device,  sensed  temperatures,  and  percent  savings.    The  possible 
messages and their explanation are: 

The  boiler  is  operating  under  its  own  internal  operating-control,  which 
has turned the burner off. This occurs for a period of time after the burner 
has shut down. 

The boiler operating-control has requested the burner to come on but the 
controller  has  sensed  that  there  is  available  heat  which  can  be  used 
without  burning  fuel.    The  burner  will  remain  off  and  useful  heat  will  be 
delivered from the boiler’s existing supply of residual heat. 

The controller has released the burner to fire. 

The controller has released the burner to fire due to a load condition that 
has  caused  the  water  temperature  to  go  below  the  programmed  low 
limits.    This condition may  occur  occasionally.   If  this message  appears 
frequently, the  boiler  operating-control may  need to  be increased  in  5ºF 
(3ºC) increments until the condition stops or the 

“low limits” may need to 

be adjusted (see Programming section) 

During  normal  operation,  one  of  the  above  messages  will  be 
alternated with the message(s) below. 

The measured value of the boiler outflow water temperature is displayed 
in 

˚F (may be programmed for ˚C). 

The  measured  value  of  the  domestic  hot  water  outflow    temperature  is 
displayed  in 

˚F  (may  be  programmed  for  ˚C).  This  message  will  only 

appear  if  the  boiler  supplies  domestic  hot  water  and  the  optional  second 
sensor is installed (see Sensor Section of these instructions). 

The calculated average savings of all burner cycles since commissioning of 
the controller.  The option to display this screen is programmable (Default 
= ON). 

Note: The numeric value will not be displayed until a value that 

is greater than zero is calculated. 

Total hours of Standby time.  (maximum = 99,999.9 hours). 

Total hours of Economizer time.  (maximum = 99,999.9 hours). The option 
to display this screen is programmable (Default = ON). 

Total  hours  of Burner  run-time.    (maximum  =  99,999.9  hours).  The  option 
to display this screen is programmable (Default = ON). 

Installation 

The  controller  is  electrically  installed  in  series 

(NEVER  IN  PARALLEL)

 

with  the  boiler  operating-control  as  shown  in  the  wiring  diagrams  on  the 
back  page  of  these  instructions.    It  is  very  important  that  it  be  installed, 
electrically, before any interlocks to ensure proper operation of the burner 
and to eliminate any alarm or fault conditions  that could be caused by the 
IntelliCon  controller  holding  the  burner  off. 

AT  NO  TIME  SHOULD  ANY 

SAFETY  CONTROLS  OR  CIRCUITS  BE  CIRCUMVENTED.

    Check  and 

determine the voltages of the burner control circuit and power circuit prior 
to installation.  

To  ensure  maximum  savings  and  proper  operation,  the  following 
recommended settings should be made: 

For  Single  Aquastats 

–  HLOLIM  should  be  set  15

˚

F  (9˚C)  below  the 

aquastat setpoint minus the differential setting. (e.g. for an aquastat with a 
setpoint  of  170˚F,  with  a  10˚F  differential  the  HLOLIM  setting  should  be: 
170˚-10˚-15˚=145˚).  The  DLOLIM  should  be  set  to  the  minimum  desired 
temperature of the Domestic Hot-Water (if Domestic sensor is used).  

For Dual or Triple Aquastats: The HLOLIM parameter should be set 5˚F 
(3˚C) below the setting of the “B” stat. The DLOLIM parameter should be 
set 20˚F (12˚C) below the setting of the “B” stat. 

These values can be seen during power-up and are programmable. 

Positioning 
The unit may be mounted on the equipment either vertically or horizontally. 
For  readability  of  the  display,  the  vertical  position  is  preferred.  The  unit 
should be mounted directly on the existing electric enclosure via the unit’s 
standard  ½”  electrical  fitting  or  surface  mounted  using  the  accessory 
mounting bracket.  

Wiring 

All  wiring  and  connections  must  comply  with  Local  and  National 
Electrical  Codes.  The  unit  should  be  wired  as  shown  in  the  wiring 
diagrams  on  the  reverse  side.    It  is  important  to  read  all  of  the 
instructions  and  the  NOTE  on  the  other  side  of  these  instructions. 
Ensure  that  POWER  TO  THE  UNIT  IS  OFF  DURING  INSTALLATION 
and that all unused leads are individually taped/insulated. 

Sensors 
Insert  the  sensor  wire  plug 

into  the  ‘Heating  Water  Sensor’  connector 

located on the side of the unit.  Mount the sensor on the boiler outflow pipe 
using tie-wraps  (see  Fig.  2)  or  other  secure method  as  close to the  boiler 
as possible.  Make sure that the sensor makes good thermal contact with 
the  pipe.    Cover  the  sensor  with  a  small  piece  of  pipe  insulation  (not 
provided) and secure in place (see Fig. 3). 

 

S T A N D B Y   M O D E  

 

ECONOMIZER MODE 

 H E A T I N G   M O D E  

 HEATING   /    LO LIM 

 

HEAT TEMP = xxx˚F  

 

DOM   TEMP = xxx˚F      

 

A     S A V E     =   x x . x %    

 ST HRS = xxxxx. x 

 ET HRS = xxxxx. x 

  RT HRS = xxxxx. x 