background image

FAULTY OPERATION AND ITS POSSIBLE DIAGNOSIS

 

LED indicator does not light up

 

AC power failure. 

LED indicator is red, the luminaire does not operate (AT or MT version, e.g. in SA / M mode) 

Battery pack is damaged or disconnected, damaged light source or electronic circuit. 

Red LED indicator lights up or blinks (AT version) 

The luminaire performs testing or damage of any part of the luminaire possible. Please, refer to the “TESTING” section. 

The luminaire does not operate in emergency mode the required time for a selected model

 

It  is  possible  that  the  battery  requires  a  full  charge  cycle  (48h).  If  after  48  hours  of  charging  the  luminaire  still  does  not  keep  a 
predefined autonomy, it is possible that the battery is run-down or damaged, e.g. due to possible incorrect formatting and needs to 
be replaced. 

 

RECOMMENDED PERIODICAL MAINTENANCE

 

The luminaire should  be  tested on regular basis in  accordance  with  valid laws and regulations. The  results of the tests should be 
recorded and stored for the use of a fire safety inspector. 

Once a day

 

It is suggested to check visually if the LED indicator in the luminaire lights up in green. 

Once a month

 

It  is  necessary  to  perform  a  function  test  (e.g.  by  disconnecting  the  AC  power  supply)  and  checking  whether  the  luminaire  is 
operating in emergency mode - the green LED indicator should turn off, and LED light source light up. 

Once a year

 

In  order  to  make  an  autonomy  test  (e.g.  by  disconnect  the  AC  power  supply)  and  check  if  the  luminaire  operates  in  emergency 
mode for a specified time. If the autonomy time of emergency operation is not sufficient, the battery needs to be fully recharged 
and the test is to be carried out again. If the result of the test continues to be negative, the battery needs to be replaced. 

CAUTION!

 

All  damage  that  might  occur  as  an  effect  of  the  device  being  used  not  in  accordance  to  this  instruction  will  result  in  loss  of 
guarantee. 
Used  or  damaged  lamps  including  batteries,  are  subject  to  be  recycled.  They  should  be  delivered  to  the  point  of  collection  of 
electrical and battery waste or to the manufacturer. 

 
The  light  source  contained  in  this  luminaire 
shall  only  be  replaced  by  the  manufacturer  or 
his service agent or a similar qualified person. 

 
 
 
 
 

 

 

 

 

 
 
Handling of obsolete equipment

 

 

 

Pursuant  to  the  Act  of  29  July  2005  on 
waste 

electrical 

and 

electronic 

equipment and the Act of 24 April 2009 
on  batteries  and  accumulators,  the 
presented  device,  after  use,  due  to 
hazardous substances contained in it, is 
subject  to  collection  of  waste  electrical 
and  electronic  equipment.  Detailed 
information  on  WEEE  collection  can  be 
obtained from municipal authorities.

 

 

 

Intelight Sp. z o.o.

 

8, Rydygiera str.

 

01 -793 Warsaw, Poland

 

 
KTM 97116 – Instruction Starlet External, P, EN, ver.20180110

 

 

STARLET EXTERNAL LED EMERGENCY LUMINAIRE 

Installation and maintenance instructions 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

  Version:  

  

STARLET EXTERNAL LED SO 

  STARLET EXTERNAL LED SC

 

OV 
 

 

TECHNICAL SPECIFICATIONS:

 

Light source* (non-replaceable): 

White LED: 3W or 5W 

Operating modes *: 

SA (M) - mains and emergency operation    or 
A (NM) - emergency operation  

Test versions*: 

MT – manual test    or 
AT – auto test     or 
CT – central test 

Emergency autonomy*:  

1 or 3 hours  

Battery* (non-replaceable): 

Ni-Cd: 1300-2500 lub Ni-MH: 2000-4200 mAh / 3,6V 

Battery charging duration: 

24h 

Power supply*: 

MT, AT and CT: 220-240V AC 50Hz 
CB (central battery): 220V AC/DC  

Max. power*: 

3W-9W 

Luminous flux*: 

3W: 120-200 lm; 5W: 250-300 lm 

Module: 

Starlet External 

Enclosure IP rating: 

IP41 

Ambient temperature: 

10-55°C 

*- depending on model 

 

 

 
 
 

INTRODUCTION

 

1.

 

The lamp should be installed when power supply is off. Safety rules, construction and electrical installation standards should 
be followed all the time. 

2.

 

The luminaire should not be powered with circuits connected to inductive power-receiving devices at the same time. This type 
of solution may cause damage to the electronic module of the luminaire. 

3.

 

The luminaire should be used indoors. 