Server Platform Features
Intel
®
Carrier Grade Server TIGI2U User Guide
27
Power Supply
The power supply cage supports up to two hot-swap power supplies (either AC input or
DC input) in a (1+1) redundant configuration. A power supply filler module for the empty
power supply site is supplied for systems without redundancy. Only the DC input version
is NEBS certified.
The power subsystem supports the implementation of remote management features
including remote enable, which permits power to be activated from a variety of sources.
The power supply is rated for 600 watts of power at the following voltages.
DC Power Supply:
PARAMETER
MIN
RATED
MAX
Max Input Current
DC Voltage
-38 VDC
-48VDC/-60VDC
-75VDC
20.5ADC
AC Power Supply:
PARAMETER
MIN
RATED
MAX
Start-up
Vac
Power
Off
Vac
Max Input
AC Current
Max Rated
Input AC
Current
Line Voltage
(110)
90V
rms
100-127 V
rms
140V
rms
85Vac
±4Vac
75Vac
±5Vac
10.0
A
rms
1,3
8.9A
rms
4
Line Voltage
(220)
180V
rms
200-240 V
rms
264V
rms
-
-
5.0 A
rms
2,3
4.5A
rms
4
Frequency
47 Hz
50/60Hz
63 Hz
Notes:
1. Maximum input current at low input voltage range shall be measured at 90Vac,
at max load.
2. Maximum input current at high input voltage range shall be measured at
180VAC, at max load.
3. This is not to be used for determining agency input current markings.
4. Maximum rated input current is measured at 100VAC and 200VAC