EPRO-31 20K & 20K-NB
Output 1: L1-N1:
This is the standard UPS output. It can provide 100% of the total capacity in watts of the UPS. In
battery mode this output is powered until UPS shutdowns because energy of the batteries has been drained.
Output 2: L2-N2
: This is a programmable output able to provide 100% of total UPS capacity. This output can be
configured to power off automatically in battery mode by reaching a programmable timer. In this way non critical
equipments connected to output 2 can be disconnected when timer limit is reached leaving battery energy available for
critical loads connected to output 1. Programmable function of output 2 is disable in factory settings. It must be enable
if required. When programmable function is disable output 2 operates in same manner than output 1.